Actionair DWFX-C Installation Guide

Actuators

Control Mode Installation Procedure

1. Remove transit plate and recycle.
2. Slide the interface and mode assembly into the shroud. 

Ensure the slots in the interface casing and the drive 

coupling located on the rear of the interface are in line.

3. Push the assembly fully home until the interface sprung 

retaining pin engages through the locating hole in the 

damper shroud (snaplock™). 

4. 

The control mode can be fitted in any of three orienta

-

tions i.e. vertically down, horizontally and vertically up 

(For height restrictions). This can easily be carried out 

by the following:

5. Remove and retain screw (8mm A/F) and washer, 

through the position indicator on the control mode.

6. Remove the control mode and interface adapter plate.
7. 

Taking care not to disturb the drive hexagon. Replace 

the interface adapter plate and control mode in the 

new orientation.

8. 

Replace the washer and screw tight (Max 5Nm) Select 

a suitable position for the Electrical Thermal Release 

(ETR) to be mounted through the ductwork.

9. Ideally this should be in the top half of the duct and/ or 

above the level of the interface.

10. Apply the self-adhesive template (located on the rear 

of the ETR) and drill the necessary holes (Ø3mm & 

Ø9.5 & Ø11mm). Push the ETR through the duct and 

ensure both screws are used to hold it in position. 

Both screws should be tightened fully to ensure that 

both sections of the ETR are closed together. It is a 

safety feature, if both sections are not closed the unit 

will not operate. For ductless installations the ETR 

should be fitted onto the damper spigot (not casing) 

above the damper interface shroud and in accordance 

with the fitting instructions. If the ETR is not fitted in 

the exact manner described above, the unit will not 

operate.

11. The damper should be manually reset and released 

using the winder provided to ensure that correct 

mechanical operation is achievable. It is possible to 

mechanically lock open the SmokeShield PTC damper 

to allow air to pass through it using the winder pro-

vided, this may be necessary if electrical power isn’t 

available yet. The ETR is not operable in this instance, 

the damper will not release automatically if the tempe-

rature rises or a fire occurs. 

12. The unit must be wired as detailed. When power is 

available, the unit must be checked for correct electri-

cal operation. Power on to reset, power off to release.

13. The unit must also be checked by pushing and holding 

the test switch on the ETR to confirm that the damper 

releases. When pressure is removed from the switch 

the damper resets. This may also be done after the 

initial installation test, to provide periodic operation of 

the damper to simulate actual fail-safe release under 

smoke/fire conditions. 

14. The ETR cable must not cut to shorten or lengthen, 

and care must be taken not to damage it. Either will 

render the unit inoperable and void any warranties. 

This is due to a built in safety feature.

Содержание actionair DWFX-C

Страница 1: ...y a competent person Care must be taken when installing and inspecting dampers as they are likely to close without warning due to loss of electrical power or a temperature rise in the ductwork This is their prime function Do not insert any items fingers or limbs between the blades Larger dampers must be handled in accordance with current regula tions and good practice due to weight Drawings Please...

Страница 2: ...s as early as possible in the project to get important stakeholders engaged and ensure an instal lation solution can be found The instructions are based on the tested method using Actionair SmokeShield PTC and FireShield products Our SmokeShield dampers are designed to be used with fire separating elements to maintain fire compart ments The SmokeShield is an actuated failsafe close damper with low...

Страница 3: ... 1227 Email actionair sw www swegon c Plea for la co Inst and SC G ECN2227 Vertical Damper Installation in a Plasterboard Wall with Pattress Actionair SmokeShield PTC AA F 10708 Illustrated above Actionair FireShield AA F 10709 Installation Method 1 Fit track of partition to the ceiling 2 Suspend the damper from the ceiling through the centre of the partition ceiling track using 10mm stud ding dro...

Страница 4: ...99 MJB 04 11 20 Swegon Air Management Limited South Street Whitstable Kent CT5 3DU Tel 44 0 1227 276100 Email actionair swegon com www swegon com uk Please refer to the DoP for latest classifications for CE UKCA compliance and the Installation Operation and Maintenance Guide SCAN ME D ECN2227 JPM 13 04 22 Vertical Damper Installation in a Plasterboard Wall without Pattress Actionair FireShield AA ...

Страница 5: ... Manag South Street Whitstable Tel 44 0 1227 Email actionair s www swegon Plea for l co Inst and SC H ECN2227 Vertical Damper Installation in a Plasterboard Wall against a Floor Slab Actionair SmokeShield PTC AA F 10730 Actionair FireShield AA F 11682 Installation Method 1 Apply a bead of low pressure intumescent mastic along top edge of damper as a gap filler and Install the damper against the fl...

Страница 6: ... are only available for 72 C For Dampers where alternative thermal link temperatures are required a chain link can be offered in place of a cassette Electrical release is only available with a cassette i e 72 C Please refer to Actionair Sales Office Please note For dampers with dimensions of 150mm and below ensure that there is adequate access to enable re setting Self Latching Removable Release M...

Страница 7: ...ion Both screws should be tightened fully to ensure that both sections of the ETR are closed together It is a safety feature if both sections are not closed the unit will not operate For ductless installations the ETR should be fitted onto the damper spigot not casing above the damper interface shroud and in accordance with the fitting instructions If the ETR is not fitted in the exact manner desc...

Страница 8: ...nths A comprehensive example of the maintenance pro cedure is given in Annex D of the standard Some automatic systems may allow more frequent testing 48hr or less and this may be required by a national standard Approved Document B Volume 2 Clause 10 12 states adequate means of access must be provided to allow inspection testing and maintenance of both fire damper and its actuating mechanism BS 999...

Страница 9: ... CONTACT WHEN DAMPER MADE BETWEEN 1 2 FULLY RELEASED VOLT FREE CONTACT MADE BETWEEN 4 6 WHEN DAMPER FULLY RESET TF 72 C AC 250V 6 3 A CONTINUITY WITH COMMON ELECTRICAL THERMAL RELEASE ETR MUST BE FITTED TO DUCTING FOR DAMPER OPERATION SPRING BIASED TEST SWITCH WHEN DAMPER CLOSED CONTINUITY WITH COMMON WHEN DAMPER OPEN CONTINUITY WITH COMMON WHEN DAMPER CLOSED CONTINUITY WITH COMMON WHEN DAMPER OPE...

Страница 10: ...OR S AND HEIGHTS OF 100 150MM FOR DUCT WITH WIDTHS AND HEIGHTS OF 200 1000MM FOR DUCT WIDTHS AND HEIGHTS OF 151 199MM FOR DUCT WIDTHS 200MM 1000MM WITH HEIGHTS OF 100 199MM Base Dampers Circular Dampers Series 601 For Circular and Flat Oval Dampers spigots are 3mm under duct size Diameters and flat oval diameters in 1mm increments Circular Dampers Series 601 FOR DAMPERS 100 150MM D FOR CIRCULAR AM...

Страница 11: ...es partly in airstream Damper spigots stream OVERALL WIDTH OF INSTALLATION FRAME IS DUCT WIDTH 114 Series 301 spigots 5mm under duct size 100 249 high use Series 101 Damper as OVERALL WIDTH OF INSTALLATION FRAME IS DUCT WIDTH 114 spigots 3mm under duct size OVERALL WIDTH OF INSTALLATION FRAME IS DUCT WIDTH 114 OVERALL WIDTH OF INSTALLATION FRAME IS DUCT WIDTH 114 FireShield ...

Страница 12: ...Actionair DWFX C Installation Guide 12 Swegon reserves the right to alter specifications 20220503 LNNN00353 5 0 Cleat dimensions FireShield SmokeShield PTC ...

Страница 13: ...y wired Check wiring in accordance with procedures The ETR cables have been damaged or tampered with Replace with new mode Control Mode operates but limited or no movement of damper blades is observed The mode is not correctly synchronised with the interface Remove motor from interface Check motor in fully released state Set position of interface and refit motor with label upmost include motor loc...

Страница 14: ...ess permitted under the respective DoP 6 Is access through the ductwork to the damper unob structed Unobstructed space should be provided for safe access to the damper This must include access through ceiling voids and ad jacent services Damper installer to advise the system designer if problems are foreseen 7 Has the space around the damper and within the opening been left clear and not been used...

Отзывы:

Похожие инструкции для actionair DWFX-C