background image

Actionair DWFX-C Installation Guide

4

Swegon reserves the right to alter specifications.           20220503 - LNNN00353 (5.0)                                                                               






Comments:

Rev:

Drawn By:

S. Wehrle

Approved By:

Kimberley.M

1  of 1 

Reference No:

Gore.S

Date:
Date:

By:

Date:

13/04/2022

08/11/2011

13/04/2022

Date:

D

Checked By:

Sheet

Rev

AAF10723

Description:

If your proposed installation details differ from 

that shown here, please discuss this with the 

authority having jurisdiction, referencing this 

documentation.  

 

Deviation from this drawing requires approval 

of the relevant authority. 

 

Connecting ductwork omitted for clarity. 

Ductwork must be independently supported.  

There must be an appropriate break-away 

joint between the damper and the connecting 

ductwork on both sides of the installation. 

 

A minimum of 200mm between fire dampers 

installed in separate ducts and 75mm between

fire damper and construction elements/edges 

needs to be observed unless otherwise 

specified in the drawing.

Installation Detail

















³









³












































IF YOUR PROPOSED

INSTALLATION DETAIL DIFFERS

FROM THAT SHOWN, YOU MUST

DISCUSS THIS WITH THE

BUILDING CONTROL AUTHORITY

(BCA), REFERENCING THIS

DOCUMENT AND THE

ASSOCIATED FIRE TESTS,

ASSESSMENTS AND OTHER

DOCUMENTS SHOWN BELOW.

DEVIATION FROM THIS DRAWING

REQUIRES THE APPROVAL OF

THE RELEVANT AUTHORITY.









A

EC1770

MJB 20-02-18

Damper Size Range (mm)

VERTICAL APPLICATION

FIRE SHIELD DWFX-C IN

PLASTERBOARD WALL

100 x 100 to 1250 x 1000

B

EC1830

RTC 20/03/18

C

ECN1999

MJB 04-11-20







 

 

 

 

© Swegon Air Management Limited

South Street, Whitstable, Kent CT5 3DU

Tel:  +44 (0)1227 276100

Email: [email protected]

 www.swegon.com/uk



Please refer to the DoP

for latest classifications

for CE/UKCA

compliance and the

Installation, Operation

and Maintenance Guide

 SCAN ME

D

ECN2227

JPM 13/04/22

Vertical Damper Installation in a 

Plasterboard Wall without Pattress

Actionair FireShield - [AA/F 10723]

Installation Method

1. Fit track (of partition) to the ceiling.
2. Suspend the damper from the ceiling through the 

centre of the partition ceiling track using 10mm stud-
ding drop rods.  

3. Frame out the damper using tracks and studs lined 

with board. This is done with a lined track above the 
damper crossing between the nearest two full height 
studs, two vertical lined studs as close to the damper 

as possible from the top cross track to the floor and a 

lined cross track below the damper between the two 
vertical studs.

4. Build the partition to the track and stud framework, 

coming as close to the damper spigot as possible.

5. Seal the damper spigot to the partition (all round, both 

sides) with low pressure intumescent sealant.

6. 

A minimum of 200 mm between fire dampers installed 
in separate ducts and 75 mm between fire damper and 
a construction element (wall/floor).

7. Finish the wall as standard practice.

Содержание actionair DWFX-C

Страница 1: ...y a competent person Care must be taken when installing and inspecting dampers as they are likely to close without warning due to loss of electrical power or a temperature rise in the ductwork This is their prime function Do not insert any items fingers or limbs between the blades Larger dampers must be handled in accordance with current regula tions and good practice due to weight Drawings Please...

Страница 2: ...s as early as possible in the project to get important stakeholders engaged and ensure an instal lation solution can be found The instructions are based on the tested method using Actionair SmokeShield PTC and FireShield products Our SmokeShield dampers are designed to be used with fire separating elements to maintain fire compart ments The SmokeShield is an actuated failsafe close damper with low...

Страница 3: ... 1227 Email actionair sw www swegon c Plea for la co Inst and SC G ECN2227 Vertical Damper Installation in a Plasterboard Wall with Pattress Actionair SmokeShield PTC AA F 10708 Illustrated above Actionair FireShield AA F 10709 Installation Method 1 Fit track of partition to the ceiling 2 Suspend the damper from the ceiling through the centre of the partition ceiling track using 10mm stud ding dro...

Страница 4: ...99 MJB 04 11 20 Swegon Air Management Limited South Street Whitstable Kent CT5 3DU Tel 44 0 1227 276100 Email actionair swegon com www swegon com uk Please refer to the DoP for latest classifications for CE UKCA compliance and the Installation Operation and Maintenance Guide SCAN ME D ECN2227 JPM 13 04 22 Vertical Damper Installation in a Plasterboard Wall without Pattress Actionair FireShield AA ...

Страница 5: ... Manag South Street Whitstable Tel 44 0 1227 Email actionair s www swegon Plea for l co Inst and SC H ECN2227 Vertical Damper Installation in a Plasterboard Wall against a Floor Slab Actionair SmokeShield PTC AA F 10730 Actionair FireShield AA F 11682 Installation Method 1 Apply a bead of low pressure intumescent mastic along top edge of damper as a gap filler and Install the damper against the fl...

Страница 6: ... are only available for 72 C For Dampers where alternative thermal link temperatures are required a chain link can be offered in place of a cassette Electrical release is only available with a cassette i e 72 C Please refer to Actionair Sales Office Please note For dampers with dimensions of 150mm and below ensure that there is adequate access to enable re setting Self Latching Removable Release M...

Страница 7: ...ion Both screws should be tightened fully to ensure that both sections of the ETR are closed together It is a safety feature if both sections are not closed the unit will not operate For ductless installations the ETR should be fitted onto the damper spigot not casing above the damper interface shroud and in accordance with the fitting instructions If the ETR is not fitted in the exact manner desc...

Страница 8: ...nths A comprehensive example of the maintenance pro cedure is given in Annex D of the standard Some automatic systems may allow more frequent testing 48hr or less and this may be required by a national standard Approved Document B Volume 2 Clause 10 12 states adequate means of access must be provided to allow inspection testing and maintenance of both fire damper and its actuating mechanism BS 999...

Страница 9: ... CONTACT WHEN DAMPER MADE BETWEEN 1 2 FULLY RELEASED VOLT FREE CONTACT MADE BETWEEN 4 6 WHEN DAMPER FULLY RESET TF 72 C AC 250V 6 3 A CONTINUITY WITH COMMON ELECTRICAL THERMAL RELEASE ETR MUST BE FITTED TO DUCTING FOR DAMPER OPERATION SPRING BIASED TEST SWITCH WHEN DAMPER CLOSED CONTINUITY WITH COMMON WHEN DAMPER OPEN CONTINUITY WITH COMMON WHEN DAMPER CLOSED CONTINUITY WITH COMMON WHEN DAMPER OPE...

Страница 10: ...OR S AND HEIGHTS OF 100 150MM FOR DUCT WITH WIDTHS AND HEIGHTS OF 200 1000MM FOR DUCT WIDTHS AND HEIGHTS OF 151 199MM FOR DUCT WIDTHS 200MM 1000MM WITH HEIGHTS OF 100 199MM Base Dampers Circular Dampers Series 601 For Circular and Flat Oval Dampers spigots are 3mm under duct size Diameters and flat oval diameters in 1mm increments Circular Dampers Series 601 FOR DAMPERS 100 150MM D FOR CIRCULAR AM...

Страница 11: ...es partly in airstream Damper spigots stream OVERALL WIDTH OF INSTALLATION FRAME IS DUCT WIDTH 114 Series 301 spigots 5mm under duct size 100 249 high use Series 101 Damper as OVERALL WIDTH OF INSTALLATION FRAME IS DUCT WIDTH 114 spigots 3mm under duct size OVERALL WIDTH OF INSTALLATION FRAME IS DUCT WIDTH 114 OVERALL WIDTH OF INSTALLATION FRAME IS DUCT WIDTH 114 FireShield ...

Страница 12: ...Actionair DWFX C Installation Guide 12 Swegon reserves the right to alter specifications 20220503 LNNN00353 5 0 Cleat dimensions FireShield SmokeShield PTC ...

Страница 13: ...y wired Check wiring in accordance with procedures The ETR cables have been damaged or tampered with Replace with new mode Control Mode operates but limited or no movement of damper blades is observed The mode is not correctly synchronised with the interface Remove motor from interface Check motor in fully released state Set position of interface and refit motor with label upmost include motor loc...

Страница 14: ...ess permitted under the respective DoP 6 Is access through the ductwork to the damper unob structed Unobstructed space should be provided for safe access to the damper This must include access through ceiling voids and ad jacent services Damper installer to advise the system designer if problems are foreseen 7 Has the space around the damper and within the opening been left clear and not been used...

Отзывы: