background image

8  |  SmithsEP.co.uk  |  Issue 002 - November 2022

Issue 002 - November 2022  |  SmithsEP.co.uk  |  9

1.

 Unlock the front access panel 

Unlock and lower the front access panel using the 
keys supplied. 

 

2.

 Fix unit to wall 

Fix the unit to the wall via suitable fixings.

3.

 Connect the pipes

Connect the heating system flow and return pipes 
to the heater pipe work. Pipe entry/exit can be 
made through either the back of the unit or by 
using the pipe knockouts on the bottom of the 
unit. Do not use soldered fittings to the heater 
pipe work as the heat generated may cause 
damage to internal wiring and components. 
Compression fittings should be used.

Installation

 

Note: We recommend the use of full-flow service 
valves. The valves should be accessible after 
completion of the installation. We also advise the 
fitting of an air vent at the highest point on either 
the flow or return pipe to remove any air trapped 
within the system. 

4.

 Open the service valves  

Open the full flow service valves and check for 
water leaks. Remove any trapped air from the 
unit via the built in bleed screws as shown in the 
diagram below. Note: Ensure the motorised valve 
is set to the auto position.

5.

 Electrical supply  

Isolate the electrical supply 

6.

 Connect the power supply  

Connect the power supply from the fused spur (3 
Amp) to the heater terminal block marked Supply 
E N L via the cable entry hole in the top chassis of 
the heater.

Supply

L

N

remove screw

pipe knockouts at rear of unit

remove screw

remove screw

remove screw

Pipe knockouts 

at rear of unit

Supply

3 Amp 

fused spur

7.

 Connect a room thermostat  

To connect a room thermostat (not supplied)  
1.  Unscrew and remove electric panel 
2.  Remove link wire between terminals 7 & 8 and  
 

fit thermostat wires 

3.  Refit electric panel

For further information refer to the room 
thermostat manufacturers instructions.

The fused spur must not be directly below the 
heater and must be accessible after the installation 
is complete. All electrical work should be carried 
out in accordance with current IEEE regulations.

1

2

3

4

5

6

7

8

9

10

3 Amp  

fused spur

to fan

supply

Thermostat 

link (optional)

Commissioning

 

1.   Turn on the electrical supply at the fused spur. 
2.   Turn the thermostat control (if fitted) to  
 maximum. 
3.   Turn on the central heating system. 
4.   If these heaters are installed on the same 
 

circuit as panel radiators balance the central  

 

heating system. 

5.   If the installation is working correctly  
 

remember to reset the thermostat control to  

 

its required setting.

6.   Set the fan speed control to the desired  
 

position. Note: To decrease motorised valve 

 

cycles it is recommended that the flow is 

 

reduced. (Please ensure adequate flow 

 

through heater).

  

7.   Lift up and close front access panel, ensure 
 

this is secure and locked in place with  

 

keys provided. 

8.   Please leave this Installation & User Guide with 
 

the user for future reference. 

Fan speed control

MED

HIGH

LOW

Содержание Smith's Caspian EC 120

Страница 1: ...Issue 002 November 2022 SmithsEP co uk 1 Issue 002 November 2022 ENGLISH UK IRL SmithsEP co uk Caspian LST Installation commissioning and user manual 60 90 120 150 180 EC Series Fan Convectors...

Страница 2: ...e body of the valve These heaters are classified as a fixed appliance and the electrical connection should be via a 3A fused spur The fused spur must not be directly below the heater but should be acc...

Страница 3: ...of and protected place with sufficient ventilation around it Make sure that the appliance is securely and correctly installed before operating it and that there is enough room around it for maintenanc...

Страница 4: ...spur Low Watts Medium Watts High Watts Water Capacity Litres CASPIAN LST 60 1 5 1 1 0 9 22mm 3A 26 41 55 0 92 CASPIAN LST 90 3 9 2 3 1 6 22mm 3A 33 59 85 1 50 CASPIAN LST 120 7 3 5 5 5 3 22mm 3A 33 79...

Страница 5: ...L via the cable entry hole in the top chassis of the heater Supply L N remove screw pipe knockouts at rear of unit remove screw remove screw remove screw Pipe knockouts at rear of unit Supply 3 Amp f...

Страница 6: ...tically with the central heating system In the event of any difficulty please contact us on 44 0 1245 324560 It will be helpful if you do not disconnect the heater from the central heating system Regi...

Страница 7: ...ockists All products are available nationally from Builders Merchants Plumbers Merchants Heating Equipment Distributors and Kitchen Equipment Distributors In the event of difficulty please contact us...

Отзывы: