background image

6  |  SmithsEP.co.uk  |  Issue 002 - November 2022

Issue 002 - November 2022  |  SmithsEP.co.uk  |  7

Model

Heat Output at 80°

Heat Output at 75°

Heat Output at 70°

Heat Output at 65°

Low 

(kW)

Med 

(kW)

High 
(kW)

Low 

(kW)

Med 

(kW)

High 
(kW)

Low 

(kW)

Med 

(kW)

High 
(kW)

Low 

(kW)

Med 

(kW)

High 
(kW)

CASPIAN LST 60

1.0 

1.6

2.2

0.9

1.4

1.9

0.8

1.3

1.7

0.8

1.1

1.5

CASPIAN LST 90

3.0

3.5

3.9

2.8

3.2

3.7

2.6

3.0

3.5

2.4

2.8

3.2

CASPIAN LST 120

5.0

5.3

5.7

4.7

5.1

5.5

4.4

4.8

5.2

4.0

4.4

4.8

CASPIAN LST 150

6.2

6.7

7.2

6.0

6.5

7.0

5.7

6.2

6.7

5.3

5.8

6.3

CASPIAN LST 180

7.7

8.2

8.7

7.5

8.0

8.5

7.2

7.7

8.2

6.8

7.3

7.8

Model

Heat Output at 60°

Heat Output at 55°

Heat Output at 50°

Low 

(kW)

Med 

(kW)

High 
(kW)

Low 

(kW)

Med 

(kW)

High 
(kW)

Low 

(kW)

Med 

(kW)

High 
(kW)

CASPIAN LST 60

0.7

1.0

1.3

0.6

0.8

1.1

0.6

0.7

0.8

CASPIAN LST 90

2.1

2.5

2.9

1.9

2.2

2.6

1.6

2.0

2.3

CASPIAN LST 120

3.6

4.0

4.4

3.2

3.6

4.1

2.8

3.2

3.7

CASPIAN LST 150

4.9

5.4

5.9

4.6

5.1

5.6

4.2

4.7

5.2

CASPIAN LST 180

6.4

6.9

7.4

6.1

6.6

7.1

5.7

6.2

6.7

Product performance

 

Heat output testing based on BS EN442 using mean water temperature, 20°C 
entering air temperature, 10° temperature drop.  
Sound levels measured at 3m in front of the floor mounted model.

Model

Pressure Drop

Total Power Consumption

High  

(kPa)

Medium 

(kPa)

Low 

(kPa)

Flow & return 

connections

Fused 

spur

Low 

(Watts)

Medium 

(Watts)

High 

(Watts)

Water Capacity 

(Litres)

CASPIAN LST 60

1.5

1.1

0.9

22mm 

3A

26

41

55

0.92

CASPIAN LST 90

3.9 

2.3

1.6

22mm 

3A

33

59

85

1.50

CASPIAN LST 120

7.3 

5.5

5.3

22mm 

3A

33

79

125

2.08

CASPIAN LST 150

8.6 

6.8

6.2

22mm 

3A

50 

119 

188 

2.58 

CASPIAN LST 180

11.3

8.6

7.9

22mm 

3A

66

158

250

3.18

 
 

Model

Sound Levels

High  

(dBA)

Medium 

(dBA)

Low 

(dBA)

Casting  

colour

Fan  

only

CASPIAN LST 60

50 

43

35

white

CASPIAN LST 90

53 

45

37

white

CASPIAN LST 120

57 

48

38

white

CASPIAN LST 150

59 

47

36

white

CASPIAN LST 180

59

47

36

white

 
 

Wiring diagrams

Caspian LST 60

Caspian LST 90 | 120 | 150 | 180

+10V

Control

Ground

Tacho

Speed Control

VR2

VR1

FAN

MVALVE

S                 W

LTC FAN

DIGITAL

11 10 L7 N6 3 2

PROBE

Brown

Black

Grey

Blue

Blue

Brown

Brown

Blue

Green

Mains Supply

Green

Blue

Brown

Thermostat Link 

(optional)

Brown

1

2

3

4

5

6

7

8

9

E

N

L

E

N

L

Blue

Green

Brown

Brown

Brown

Brown

Blue

Brown

Brown

Brown

Brown

Brown

Brown

Red

White

ROOM STAT

Summer Winter Switch

BYPASS 

TUBE  

LTC

+10V

Control

Ground

Tacho

Speed Control

VR2

VR1

FAN

MVALVE

1

3

4

8

9

E

S                 W

DIGITAL

11 10 L7 N6 3 2

Brown

ROOM STAT

BYPASS 

TUBE  

LTC

LTC FAN

EC DC 

Filter

PROBE

Mains Supply

Green

Blue

Brown

E

N

L

Thermostat Link 

(optional)

Brown

Blue

Brown

Brown

Blue

Green

Brown

Black

Grey

Blue

Blue

Brown

Summer Winter Switch

Brown

Red

White

Blue

Brown

Brown

Green

Blue

Brown

Blue

Brown

Brown

Brown

Brown

Brown

Note: The earth link 

is directly above the 

negative terminal on  

the EC DC filter

5

N

6
L

7

2

Содержание Smith's Caspian EC 120

Страница 1: ...Issue 002 November 2022 SmithsEP co uk 1 Issue 002 November 2022 ENGLISH UK IRL SmithsEP co uk Caspian LST Installation commissioning and user manual 60 90 120 150 180 EC Series Fan Convectors...

Страница 2: ...e body of the valve These heaters are classified as a fixed appliance and the electrical connection should be via a 3A fused spur The fused spur must not be directly below the heater but should be acc...

Страница 3: ...of and protected place with sufficient ventilation around it Make sure that the appliance is securely and correctly installed before operating it and that there is enough room around it for maintenanc...

Страница 4: ...spur Low Watts Medium Watts High Watts Water Capacity Litres CASPIAN LST 60 1 5 1 1 0 9 22mm 3A 26 41 55 0 92 CASPIAN LST 90 3 9 2 3 1 6 22mm 3A 33 59 85 1 50 CASPIAN LST 120 7 3 5 5 5 3 22mm 3A 33 79...

Страница 5: ...L via the cable entry hole in the top chassis of the heater Supply L N remove screw pipe knockouts at rear of unit remove screw remove screw remove screw Pipe knockouts at rear of unit Supply 3 Amp f...

Страница 6: ...tically with the central heating system In the event of any difficulty please contact us on 44 0 1245 324560 It will be helpful if you do not disconnect the heater from the central heating system Regi...

Страница 7: ...ockists All products are available nationally from Builders Merchants Plumbers Merchants Heating Equipment Distributors and Kitchen Equipment Distributors In the event of difficulty please contact us...

Отзывы: