Sutron Corporation Satlink Operations & Maintenance Manual, Rev 8.04.2 11/3/2016 pg. 65
Read access is the lowest access level. A customer with read access may not make
any changes to the system. Read access allows one to view measurement readings,
view status, and view setup, and the like.
Maintenance access
Maintenance access provides everything that read access does, plus the ability to
calibrate sensors, clear status, reboot unit, and other station maintenance related
functions.
Full access
Full access provides complete access to the station.
Each tier has its own password. Access granted depends on the password entered.
The default passwords are SUTRON1 for read access, SUTRON2 for maintenance access, and
SUTRON3 for full access. Please change ALL THREE passwords when securing your system.
Blank passwords are NOT allowed. All ASCII bytes are allowed except comma, equals, and white
space. Passwords may be up to 19 bytes long.
7.2.2.
Password Protection Setting
A setting called Password Protection needs to be set in order to secure a station. Password
Protection may be set to one of the following:
DISABLED
In this scenario, full access is allowed without a password. This is the default.
SETUP
In this scenario, the system’s setup is write-protected. Maintenance and read
access are allowed without a password.
Station setup cannot be changed. Transmissions may not be started.
Status may be cleared, measurements may be calibrated and forced, failsafe may
be reset, unit may be rebooted, clock may be set.
MAINTENANCE
System write and maintenance operations are restricted. Read access is allowed
without a password.
Setup can be read, but not written. Status can be checked, but not cleared.
FULL
System is fully protected.
No access at all is allowed without a password, except for the following commands:
EXIT, HELLO, PASSWORD PROTECTION, VER.