10 Sensor signal outputs
Response message
In the response message that the device returns to the master:
•
Function code: 03
•
Byte order (32-bit data): MID-LITTLE-ENDIAN.
Remarks
: To properly decode the 4-byte float and unsigned
integer data in the response message, the master must change the
byte order from MID-LITTLE-ENDIAN to the order that it is using
(LITTLE-ENDIAN or BIG-ENDIAN).
Byte sequencing
Byte order
Byte sequencing
(HEX)
Example
MID-LITTLE-ENDIAN
(Read from the device)
A B C D
0x 0A 11 42 C5
LITTLE-ENDIAN
B A D C
0x 11 0A C5 42
BIG-ENDIAN
C D A B
0x 42 C5 0A 11
10.4 M-Bus output
Communication parameters
Primary Address
: 1
Secondary Address
: 8-digit serial number of the sensor
Manufacturer Code
: 0x15C4
M-Bus version
: 1
Baud rate
: 2400
Response delay (ms)
: 7
Response timeout (ms)
: 100
Receive timeout (ms)
: 500
Value register
M-Bus Addr.
Description
Data bytes
1
Total consumption
4-byte
2
Flow
4-byte
3
M-Bus status
4-byte
31