DRAIN INSTALLATION
The blower draws air through the
dehumidifier, putting the cabinet under
negative pressure� As a result, the included
P-trap is required for proper draining� The
installed drain fitting on the dehumidifier is
3/4" FNPT� Use the included fittings to trap
and install the drain� See
FIGURE 6
� The
drain tubing can be hard pipe or flexible
tubing�
NOTE:
PTFE thread seal tape is
recommended for the threaded connections
and
hand tighten only
� Use PVC primer and
cement for all slip fit connections to prevent
leaks� After installing the drain connections,
trap, and tubing, pour enough water (about
2 pints) into the dehumidifier drain pan to
prime the trap�
If the drain tubing will be installed to a
condensate pump, or if a common drain
tube will serve multiple dehumidifiers
or air conditioners, a vacuum break is
recommended to prevent the p-trap from
being unintentionally siphoned� Install a
T-fitting with a short section of drain tubing
pointed vertically and extending above the
start of the filter (see
FIGURE 6
)� Install the
vacuum break after the P-trap�
CONDENSATE PAN, CONDENSATE PUMP AND FLOAT SWITCH
A condensate pan is recommended when suspending
the dehumidifier over finished areas or product� Adhere
to local codes regarding draining of the condensate
pan� If a condensate pump is needed, install it in the
condensate pan as well�
Install a condensate overflow safety switch (i�e� float
switch) in the condensate pan, remove the factory
installed jumper wire between the Float Switch
terminals on the control and wire the float switch to the
dehumidifier as shown in
FIGURE 7
� Overflow safety
switches on condensate pumps can be wired to the
Float Switch terminals in a similar fashion�
3/4" MNPT X 3/4"
FEMALE PIPE
(INCLUDED)
P-TRAP
(INCLUDED)
3/4" PIPE X 3/4" PIPE COUPLING
(NOT INCLUDED)
PVC HARD PIPE
(NOT INCLUDED)
3/4" PIPE TEE
(INCLUDED)
3/4" MNPT X 3/4"
FEMALE PIPE
(INCLUDED)
P-TRAP (INCLUDED)
3/4" FEMALE PIPE X 3/4" FNPT (INCLUDED)
3/4" MNPT X 3/4" BARB (INCLUDED)
3/4" FLEXIBLE TUBE
(NOT INCLUDED)
HIGHER
THAN
FILTER
FRAME
OPTIONAL
VACUUM
BREAK
FL
OAT
Swit
ch
DH
DH
NORMALLY CLOSED
FLOAT SWITCH
FIGURE 6
– DRAIN ASSEMBLY
FIGURE 7
– FLOAT SWITCH WIRING
3/4" MNPT X 3/4"
FEMALE PIPE
(INCLUDED)
P-TRAP
(INCLUDED)
3/4" PIPE X 3/4" PIPE COUPLING
(NOT INCLUDED)
PVC HARD PIPE
(NOT INCLUDED)
3/4" PIPE TEE
(INCLUDED)
3/4" MNPT X 3/4"
FEMALE PIPE
(INCLUDED)
P-TRAP (INCLUDED)
3/4" FEMALE PIPE X 3/4" FNPT (INCLUDED)
3/4" MNPT X 3/4" BARB (INCLUDED)
3/4" FLEXIBLE TUBE
(NOT INCLUDED)
HIGHER
THAN
FILTER
FRAME
OPTIONAL
VACUUM
BREAK
English
7