![Surefire BMS-350 Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/surefire/bms-350/bms-350_installation-and-operation-manual_1406932045.webp)
45
MODBUS
INFORMATION
Modbus
address
Register name
Modbus master does
R (Read) or RW
(Read or Write)
Data type
Notes
40013
Command execute
(RW)
unsigned int
16
Set to non-zero to request that the command in regis-
ter 40011 be executed with the parameter in register
40012(if needed). Will continue to execute until set
to zero.
40014
thru
40019
Unallocated
unsigned int
16
Read as zero, can be written but will be ignored
40020
Bit 0 – Light status
0:RED light is on solid
1:GREEN light is on
solid
unsigned int
16
Bit #0 of register 40005 unpacked into a single regis-
ter for use by controllers with primitive bit manipula-
tion capabilities.
40021
Bit 1 – Temperature
units
0 : Degrees
1 : Degrees F
unsigned int
16
Bit #1 of register 40005 unpacked into a single regis-
ter for use by controllers with primitive bit manipula-
tion capabilities.
40022
Bit 2 – Input sense
0 : RTD
1 : ALT (pressure
switch)
unsigned int
16
Bit #2 of register 40005 unpacked into a single regis-
ter for use by controllers with primitive bit manipula-
tion capabilities.
40023
Bit 3 - Igniter volts
0 : 14V
1 : 13V
unsigned int
16
Bit #3 of register 40005 unpacked into a single regis-
ter for use by controllers with primitive bit manipula-
tion capabilities.
40024
Bit 4 – Pilot mode
0 : Intermittent pilot
1 : Standing pilot
unsigned int
16
Bit #4 of register 40005 unpacked into a single regis-
ter for use by controllers with primitive bit manipula-
tion capabilities.
40025
Bit 5 – Flame sensed
0 : No flame sensed
1 : Flame sensed
unsigned int
16
Bit #5 of register 40005 unpacked into a single regis-
ter for use by controllers with primitive bit manipula-
tion capabilities.
40026
Bit 6 – Factory use on-
ly
unsigned int
16
Bit #6 of register 40005 unpacked into a single regis-
ter for use by controllers with primitive bit manipula-
tion capabilities.
40027
Bit 7 – Factory use on-
ly
unsigned int
16
Bit #7 of register 40005 unpacked into a single regis-
ter for use by controllers with primitive bit manipula-
tion capabilities.
Содержание BMS-350
Страница 1: ...Proudly Made in the USA BMS 350 Installation and Operations Manual...
Страница 18: ...18 INSTALLATION WIRING DIAGRAM...
Страница 19: ...19 FUEL TRAIN DIAGRAMS Piloted Fuel Train Pilotless Fuel Train...
Страница 29: ...29 INTERMITTENT PILOT OPERATION Flow Chart...
Страница 31: ...31 STANDING PILOT OPERATION Flow Chart...
Страница 33: ...33 PILOTLESS OPERATION Flow Chart...