TROUBLESHOOTING
GUIDE
STANDBY CODES
Code Symptom
Action
Visual
09
Standby Interloop
Pilot/Main burner not
running.
No activity when
attempting startup.
Ports 20 and 21 have
been activated.
1. System detecting an open
circuit.
2. Customer supplied switch is
activated.
3. Check switching device for
faulty operation.
4. Verify wiring from switching
device.
5. Verify jumper is installed.
6. Jumper is required if function
is not being utilized
Blinking Green LED.
10
Loss of Fuel Gas
Pilot/Main burner not
running.
No activity when
attempting startup.
Ports 22 and 23 have
been activated.
1. System detecting an open
circuit
2. Customer supplied switch is
activated.
3. Check switching device for
faulty operation.
4. Verify wiring from switching
device.
5. Verify jumper is installed.
6. Jumper is required if function
is not being utilized
Blinking Green LED.