Chapter 4 Configuration description
41
Fig.4-1 high alarm, low alarm and hysteresis
4.2 Function setting
4.2.1 Communication setting
The instrument supports communication operations with PC, to realize
real-time monitoring. The instrument only supports Modbus protocol.
Configuration item descriptions:
Configuration item
Function descriptions
Parameters range
Instrument address
Modbus device address
1~254
Baud rate
Communication rate
9600,57600,115200
Check bit
Communication check
No check, odd number check,
even number check, normal 0
Floating point format
Format of floating point
number
1234,2143,3412,4321
4.2.2 Pen driver operation
The instrument supports to save the current configuration to USB disk, or
read configuration file in USB disk.