Chapter 2: Server Installation
2-5
Installing the Outer Rails
Begin by measuring the distance from the front rail to the rear rail of the rack. Attach
a short bracket to the front side of the right outer rail and a long bracket to the rear
side of the right outer rail. Adjust both the short and long brackets to the proper
distance so that the rail can fi t snugly into the rack. Secure the short bracket to the
front side of the outer rail with two M4 screws and the long bracket to the rear side
of the outer rail with three M4 screws. Repeat these steps for the left outer rail.
Locking Tabs
Both chassis rails have a locking tab, which serves two functions. The fi rst is to
lock the server into place when installed and pushed fully into the rack, which is
its normal position. Secondly, these tabs also lock the server in place when fully
extended from the rack. This prevents the server from coming completely out of
the rack when you pull it out for servicing.
Figure 2-2. Installing the Rack Rails
Содержание 8015C-T
Страница 1: ...SUPER SUPERSERVER 8015C T USER S MANUAL Revision 1 0...
Страница 5: ...v Preface Notes...
Страница 22: ...2 8 SUPERSERVER 8015C T User s Manual Figure 2 4 Accessing the Inside of the System...
Страница 24: ...2 10 SUPERSERVER 8015C T User s Manual Notes...
Страница 28: ...3 4 SUPERSERVER 8015C T User s Manual Notes...
Страница 66: ...6 10 SUPERSERVER 8015C T User s Manual Figure 6 6 Removing Replacing the Power Supply...
Страница 92: ...7 26 SUPERSERVER 8015C T User s Manual Notes...
Страница 98: ...A 6 SUPERSERVER 8015C T User s Manual Notes...
Страница 104: ...B 6 SUPERSERVER 8015C T User s Manual Notes...
Страница 118: ...D 4 SUPERSERVER 8015C T User s Manual Notes...