5
External Device Terminals Connections. (fig. 8)
1) GND & PB =
Push Button
terminals. Step by step command input (open, stop, close).
2) 12V & GND & PE =
Photo beam
terminals.
3) 12V & GND & PB =
External receiver
terminals
To avoid damaging components while wiring, disconnect the unit from all power.
1. Select Installation Side
Note:
The operator is factory set to operate on the right side of the door by default.
To set for left hand side installation, press and hold the
SET
button until the LED displays
5
.
Using the
UP
or
DOWN
buttons select
1
for left installation or
0
for right side installation.
Press
SET
to confirm the setting.
WARNING:
This step must be completed prior to setting Open and Close limits and safety
reverse force adjustment if utilizing a lift side installation. If using the standard right-side
installation, this step can be ignored.
2. Setting Open and Close Limits
a. Move the door to the halfway position and engage the opener using the release cord.
b. Press and hold
SET
button until the
LED
displays the number
1.
c. Press and hold
UP
button, the door will travel to the open position, release the button
when the door has reached the desired open position.
d. Fine tune the open position by pressing
UP
and
DOWN buttons
.
e. Press
SET
to store the open position, the LED will display the number
2
, it is now
ready to set the close position
f. Press and hold
DOWN
, the door must travel to the close position, release the button
when the door has reached the desired close position.
g. Fine tune the close position by pressing UP and DOWN buttons.
h. Press
SET
to store the close position.
The door will then open and close automatically to map the open and close sensitivity force
requirements.
SETTINGS AND ADJUSTMENTS
Fig. 8