Superior WCT3036RH Скачать руководство пользователя страница 5

SuperiorFireplaces.us.com

126619-01_K

5

FIREPLACE INSTALLATION

SELECTING LOCATION

To determine safest and most efficient location for fireplace, you 

must take into consideration the following guidelines:
1.  Location must allow for proper clearances (see Figures 1 and 2).
2.  Consider a location where fireplace will not be affected by drafts, 

air conditioning ducts, windows or doors.

3.  A location that avoids cutting of joists or roof rafters will make 

installation easier.

4.  An outside air kit is available with this fireplace (see Optional 

Outside Air Kit on page 7).

MINIMUM CLEARANCE TO COMBUSTIBLES

Back and sides of fireplace                                  3/4" (19 mm) minimum*
Floor**                                                                    0" (0 mm) minimum
Perpendicular wall to opening                              12" (305 mm) minimum
Top spacers                                                             0" (0 mm) minimum
Mantel clearances                                             see Mantels, page 6
Chimney outer pipe surface                            1" (26 mm) minimum

* Not required at nailing flanges

** See step 2 of Framing

 WARNING: DO NOT PACK REQUIRED AIR SPACES 

WITH INSULATION OR OTHER MATERIALS.

Minimum/Maximum Chimney Height

Minimum height of chimney, measured from base of fireplace to 

flue gas outlet of termination, is 14-½ feet for straight flue or a flue 

with one elbow set. Maximum distance between elbows is 6 feet. For 

systems with two elbow sets, minimum height is 22 feet. Maximum 

height of any system is 50 feet. This measurement includes fireplace, 

chimney sections and height of termination assembly at level of flue 

gas outlet (see Figure 20, page 12).

FRAMING

1.  Frame opening for fireplace using dimensions shown in Figures 

1 and 2.

2.  If fireplace is to be installed directly on carpeting, tile or any 

combustible material other than wood flooring, fireplace must 

be installed upon a metal or wood panel extending full width and 

depth of fireplace.

3.  Set fireplace directly in front of this opening and slide unit back 

until nailing flanges touch side framing.

4.  Check level of fireplace and shim with sheet metal if necessary.
5.  Before securing fireplace to prepared framing, ember protector 

must be placed between hearth extension (not included) and 

under bottom front edge of fireplace to protect against glowing 

embers falling through. If fireplace is to be installed on a raised 

platform, a Z-type ember protector (not included) must be fabri-

cated to fit your required platform height. Ember protector should 

extend under fireplace a minimum of 1 

1

/

2

". Ember protector 

should be made of galvanized sheet metal (28 gauge minimum) 

to prevent corrosion.

6.  Using screws or nails, secure fireplace to framing through flanges 

located on sides of fireplace.

Figure 1 - Framing Dimensions

Figure 2 - Corner Installation

HEARTH EXTENSION

A hearth extension projecting a minimum of 16" in front of and a 

minimum of 8" beyond each side of fireplace opening is required to 

protect combustible floor construction in front of fireplace. Fabri-

cate a hearth extension using a material which meets the following 

specifications: a layer of noncombustible, inorganic material having 

a thermal conductivity of k = .84 BTU IN/FT

2

 HR °F (or less) at 1" 

thick. For example, if material selected has a k factor of 0.25, such 

as glass fiber, the following formula would apply:
  0.25 x 1.0" = 0.30" thickness required

 0.84
Thermal conductivity "k" of materials can be obtained from manu-

facturer or supplier of noncombustible material. If hearth extension 

is to be covered, use noncombustible material such as tile, slate, 

brick, concrete, metal, glass, marble, stone, etc. Provide a means to 

prevent hearth extension from shifting and seal gap between fireplace 

frame and hearth extension with a non-combustible material such 

as sand-cement grout (see Figure 3, page 6).

41 

3

/

4

"

(1061 mm)  

41 

3

/

4

"

(1061 mm)  

21 

7

/

8

"

(556 mm)  

Maintain 

3

/

4

Clearance at 

Sides and 

Back of 

Fireplace

   

3

/

4

" Clearance Not 

Required at Nailing Flanges 

  

 24 

1

/

2

(623 mm) 

 52 

1

/

4

(1328 mm) 

 17 

3

/

8

(442 mm) 

 73 

7

/

8

" (1877 mm) 

Содержание WCT3036RH

Страница 1: ...age 20 FOR CANADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation to determine the need to obtain a permit POUR...

Страница 2: ...tested for the fireplace system you may cause a fire hazard The IHP warranty will be voided by and IHP disclaims any respon sibility for the following actions a Modification of the fireplace componen...

Страница 3: ...nposeasignificanthazard IMPORTANT See appendix A page 21 for additional information regarding draft requirements smoking causes and troubleshooting WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESUL...

Страница 4: ...8 232 mm 3 1 2 89 mm 3 1 2 89 mm 11 1 2 292 mm 22 559 mm 29 737 mm 41 1042 mm 1 26 mm 1 26 mm 21 534 mm 8 204 mm 35 889 mm 37 940 mm 41 1042 mm 1 26 mm AIRSPACE TO COMBUSTIBLE MATERIAL 0 0 mm TO TOP S...

Страница 5: ...nailing flanges touch side framing 4 Check level of fireplace and shim with sheet metal if necessary 5 Before securing fireplace to prepared framing ember protector must be placed between hearth exten...

Страница 6: ...ss than 12 from top opening of fireplace NFPA 211 Section Clearance from Combustible Material Mantels or any other combustible material also may come up to side edge of black metal face of fireplace a...

Страница 7: ...ttic space The maximum height for the air vent can not exceed 3 feet below the flue gas outlet of the termination CHIMNEY PIPE WARNING Label part number 900599 01 must be applied by the installer to a...

Страница 8: ...e inner flue pipe section must be installed first with lanced side up Outer pipe section can then be installed over flue pipe section with hemmed end up Press down on each pipe section until lances se...

Страница 9: ...Support Pipe 12S 8DM 1 26 mm Min Straps Straps Straps Straps Detail A Return Elbow Detail B Angle Firestop See Detail A See Detail B Ceiling Support Pipe 12S 8DM VENTING INSTALLATION Continued Offset...

Страница 10: ...n Figure 13 Figure 12 Firestop Spacer with Living Space Above Ceiling Figure 13 Firestop Spacer with Attic Space Above Ceiling If area above is a living space install firestop below framed hole If are...

Страница 11: ...a tions Apply waterproof caulk around perimeter of collar to provide a proper seal Figure 16 Storm Collar Chimney Pipe Waterproof Caulk Storm Collar Flashing Terminations Spark Arrestor Fireplace syst...

Страница 12: ...als such as wallboard sheet rock drywall ply wood etc may make direct contact with sides and top around fire place face It is important that combustible materials do not overlap face itself Brick glas...

Страница 13: ...ent Install gas appliance or cap off gas line if desired CAUTION All gas piping and connections must be tested for leaks after installation is completed After ensuring that gas valve is on apply soap...

Страница 14: ...ss doors operates much differently than a fireplace with an open front A fireplace with glass doors has a limited amount of air for combustion Excessive heat within fireplace can result if too large a...

Страница 15: ...used if installed in accordance with the instructions by its manufacturer A locally fabricated shroud may be used with IHP Shroud Leg Spacer Kit SLK in accor dance with instructions provided with the...

Страница 16: ...TS WOOD BURNING FIREPLACE MODELS MODEL CATALOG NO WRT3036WS F0659 WRT3036WSI F0660 WRT3036WH F0661 WCT3036WS F0662 WCT3036WSI F0663 WCT3036WH F0664 9 4 28 29 19 12 20 26 17 8 1 5 21 2 30 18 11 14 3 13...

Страница 17: ...mper Can Collar 1 16 J8007 Screen Assembly Kit 1 17 Firebox Top Assembly 1 18 Air Kit Door Assembly 1 19 Face Weldment 1 20 J3991 Smoke Deflector 1 21 Fireplace Top Insulation 1 22 Access Panel 1 23 J...

Страница 18: ...ight Stacked White 1 4 Refractory Rear Stacked White 1 5 Refractory Bottom Rear White 1 6 Refractory Bottom Front White 1 WARNING Contact an IHP dealer to obtain any of these parts Never use substitut...

Страница 19: ...HT 18 Section Hi Temp Double Wall Pipe Snap Lock F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp D...

Страница 20: ...Section F0893 ETL 8HT Hi Temp Large Pyramid Top with Slip Section MESH SQUARE TOP TERMINATION F0922 ETO 8DM Square Top with Mesh MESH SQUARE TOP TERMINATION WITH SLIP SECTION F0923 ETLO 8DM Square To...

Страница 21: ...nditions inadequate chimney heights adversewindconditionsand orunusualenvironmental factors or conditions beyond our control take into account all variables within the installation and install the app...

Страница 22: ...ance The best location to install your appliance is determined by consid ering the location of windows doors and the traffic flow in the room where the appliance is located allowing space in front of...

Страница 23: ...be subject to normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with a...

Страница 24: ...6619 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult yo...

Отзывы: