Superior SSDVPF-CNE-B Скачать руководство пользователя страница 15

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

15

Blocking

Support Straps

(Plumber's tape)

8 feet (2.4 m)

Maximum

1 inch (25.4 

mm) minimum 

clearance to 

combustibles

Figure 19

Roof

Framing

Ceiling

Framing

Plumb

Bob

 Figure 21

Another method, where the vent is not adjacent 

to a wall, is illustrated in Figure 22 on Page 

16.  Here, support straps (96K93) and support 

plates  (96K92)  can  be  used  to  support  the 

weight of the vent. 

D.

 

Install firestop / spacer at ceiling -

 When 

using  Secure  Vent,  use  SV4.5VF  firestop  / 

spacer  at  ceiling  joists;  when  using  Secure 

Flex, use SF4.5VF firestop / spacer. If there is 

living space above the ceiling level, the firestop 

/ spacer must be installed on the bottom side 

of the ceiling. If attic space is above the ceiling, 

the firestop / spacer must be installed on the 

top side of the joist. 

Route the vent sections through the framed open-

ing and secure the firestop / spacer with 8d nails 

or other appropriate fasteners at each corner. 

 

Remember to maintain 1" (25 mm) clearance 

to combustibles, framing members, and attic or 

ceiling insulation when running vertical chim-

ney sections. Attic insulation shield (H3907) 

may be used to obtain the required clearances 

indicated here. See installation accessories o 

Pages 33 and 34.  The gap between the vent 

pipe and a vertical firestop can be sealed with 

non-combustible caulking.

E.

 

Support the vertical vent run sections -

Note - Proper venting support is very important. 

The weight of the vent must not be supported 

by the fireplace in any degree. 

Support the vertical portion of the venting system 

every 8 feet (2.4 m) above the fireplace vent 

outlet. One method of support is by utilizing 

field  provided  support  straps  (conventional 

plumber's tape). Secure the plumber's tape to 

the framing members with nails or screws.

Loop  the  tape  around  the  vent,  securing  the 

ends  of  the  tape  to  the  framing.    If  desired, 

sheet  metal  screws  #6  x  1/2"  length  may  be 

used to secure the support straps to the vent 

pipe.   See Figure 21

10-1/2" Min. 

(267 mm)

10-1/2" Min. 

(267 mm)

Figure 20

Align the dimple (four places) of the 

upper vent section with the opening 

of the locking incline channel on the 

lower vent section or appliance col-

lar.  Twist vent component clockwise 

to engage and seal until arrow and 

dimple align.

Dimple

Locking Incline 

Channel

Connected Vent 

Sections

Arrow

Arrow

Appliance Collar or 

Vent Section

Vertical (offset) Installation

Analyze  the  vent  routing  and  determine  the 

number of vent sections and elbows required. 

Refer to Vertical Vent Figures and Table

on 

Pages 17 and 18  to select the type of vertical 

installation desired. Refer to the 

Vent Section 

Length Charts on 

Page 14  for an aid in selecting 

vent length combinations.  Elbows are available 

in 45° and 90° configurations.  Refer to Figure 

23 on Page 16 for the SV4.5E45 and SV4.5E90 

elbow dimensional specifications.   
Where  required,  a 

telescopic  vent  section  

(SV4.5LA)

  may be used to provide the installer 

with an option in installing in tight and confined 

spaces or where the vent run made up of fixed 

length pieces develops a joint in a undesirable 

location, or will not build up to the required 

length. The SV4.5LA Telescopic Vent Section 

has an effective length of from 1-1/2" (38 mm) 

to 7-1/2" (191 mm). The SV4.5LA  is fitted with 

a locking inclined channel end (identical to a 

normal vent section component) and a plain end 

with 3 pilot holes. Slip the plain end over the 

locking channel end of a standard  SV4.5 vent 

component the required distance and secure 

with three screws.

Maintain a minimum 1" (25 mm) clearance 

to combustible materials for all vertical ele-

ments. Clearances for all horizontal elements 

are 3" (76 mm) on top, 1" (25 mm) on sides 

and 1" (25 mm) on the bottom.
A.

 

Frame ceiling opening -

 Use a plumb line 

from the ceiling above the appliance to locate 

center of the vertical run. Cut and/or frame an 

opening,  10-1/2"  x  10-1/2"    (267  mm  x  267 

mm) inside dimensions, about this center mark 

(Figure 19).

To attach a vent component to the appliance 

collar,  align the  dimpled end over  the collar, 

adjusting  the  radial  alignment  until  the  four 

locking  dimples  are  aligned  with  the  inlet  of 

the four inclined channels on the collar (refer to 

Figure 20).  Push the vent component against 

the collar until it fully engages, then twist the 

component  clockwise,  running  the  dimples 

down and along the incline channels until they 

seat at the end of the channels.  The unitized 

design of the 

Secure Vent™

 components will 

engage and seal both the inner and outer pipe  

without  the  need  for  sealant  or  screws.    If 

desired a #6 x 1/2" screw may be used at the 

joint, but it not required as the pipe will securely 

lock when twisted.

Note: An elbow may also be attached to the 

appliance collar.  Attach in the same manner 

as you would a vent section. 

C.  Attach  vent  components  to  each  other 

-

  Other  vent  sections  may  be  added  to  the 

previously installed section in accordance with 

the requirements of the vertical vent Figures 

and Tables.  To add another vent component 

to a length of vent run, align the dimpled end 

over the inclined channel end of the previously 

installed section, adjusting the radial alignment 

until the four locking dimples are aligned with 

the inlets of the four incline channels of the 

previous section.  

Push the vent component against the previous 

section  until  it  fully  engages,  then  twist  the 

component clockwise running the dimples down 

and along the incline channels until they seat at 

the end of the channels.  

This seating position 

is indicated by the alignment of the arrow and 

dimple as shown in

 Figure 20.

B.

 

Attach vent components to appliance -

 

Se-

cure Vent 

 SV4.5 direct-vent system compo-

nents are unitized concentric pipe components 

featuring positive twist lock connections (see 

Figure 20).  

All of the appliances covered in this document 

are fitted with collars having locking inclined 

channels.  The dimpled end  of the vent com-

ponents fit over the appliance collar to create 

the positive twist lock connection.

Содержание SSDVPF-CNE-B

Страница 1: ...de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l entretien doivent tre assur s par...

Страница 2: ...e installed the electrical power must be provided at the time of appliance in stallation The Electronic appliances have an electronic intermittent pilot ignition system External electrical power is re...

Страница 3: ...y be required due to excessive lint from carpeting bed ding material etcetera It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean Remarque...

Страница 4: ...e reduced by either Using gas that has been derated by the gas company Changing the burner orifice to a smaller size as regulated by the local authorities having jurisdiction and by the USA National F...

Страница 5: ...rer s instructions and the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 in the United States or the StandardforInstallationinMobileHomes CAN CSA Z240 MH Series in Canada C...

Страница 6: ...54 ANSI Z223 1 Roof Pitch Feet Meters Flat to 6 12 1 0 0 3 6 12 to 7 12 1 25 0 38 7 12 to 8 12 1 5 0 46 8 12 to 9 12 2 0 0 61 9 12 to 10 12 2 5 0 76 10 12 to 11 12 3 25 0 99 11 12 to 12 12 4 0 1 22 12...

Страница 7: ...cm for appliances 10 000 BTU hr 3kW 12 in 30 cm for appliances 10 000 BTU hr 3kW and 100 000 BTU hr 30kW 36 inches 91 cm for appliances 100 000 BTU hr 30kW 6 in 15 2 cm for appliances 10 000 BTU hr 3...

Страница 8: ...owing exception If the optional radiant panels are installed the non combustible material may cover any portion of the top radiant panel or the air gaps surrounding the top radiant panel down to the t...

Страница 9: ...plates and remove the cardboard from beneath each plate be careful not to damage the white gasket See Figure 10 NOTE INSTALLATION DIAGRAMS AND INSTRUCTIONSSHOWTHEFRONTOFTHE APPLIANCEASTHESIDEWHICHHAS...

Страница 10: ...108 679 11 3 8 267 289 7 178 5 1 8 130 12 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Lou...

Страница 11: ...uance without notice Appliance has a factory installed vent seal cap see Figures 15 and 16 on Page 13 in each flue outlet EFFICIENCIES SSDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louv...

Страница 12: ...torand1 2inchshutoff valve see Figure 47 on Page 27 See Massachusetts Requirements on Page 4 foradditionalrequirementsfor installations in the state of Massachusetts in the USA The gas supply line sho...

Страница 13: ...1 in Canada Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier D gagementconformeauxcodesd installationlocauxetauxexigences du foumisseunde gaz...

Страница 14: ...0 0 3 5 4 5 7 3 0 0 2 0 0 2 5 6 4 5 7 8 3 0 0 0 0 1 1 5 9 4 5 2 1 4 1 0 2 0 0 3 1 5 5 2 4 1 0 0 0 1 2 5 5 5 5 2 6 4 0 1 2 0 0 3 7 5 5 7 4 0 0 1 1 0 2 6 6 5 2 5 0 2 2 0 0 4 5 7 6 5 2 6 5 0 0 3 0 0 3 9...

Страница 15: ...4 5LA may be used to provide the installer with an option in installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location or...

Страница 16: ...ections see Figure 23 Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary It is important to maintain the required clear ancestocombustibles 1 25mm at...

Страница 17: ...ori zontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio Forevery1footof V verti cal you are allowed 5 feet of H horizontal run up to a...

Страница 18: ...4 2 0 610 1 0 305 10 3 048 4 1 219 2 0 610 15 4 572 6 1 829 3 0 914 20 6 096 8 2 438 4 1 219 V V1 H H1 40feet 12 2m Max H 8 feet 2 438 meters Max H H1 20 feet 6 096 meters Max Example If 20 feet total...

Страница 19: ...geandsealboththe inner and outer pipe elements with the same procedure Sealant and securing screws are not required Note An elbow may also be attached to the appliance collar Attach in the same manner...

Страница 20: ...ey are in the same area as a hot termination To prevent contact with hot surfaces we recommend the use of a Termination Guard See Page 33 This can be purchased at your local dealer SV4 5HT 2 Terminati...

Страница 21: ...hes mm Termination Kit Only 6 to 9 1 4 152 to 235 TerminationKitand 6In Vent Section SV4 5L6 10 3 4 to 14 273 to 356 Termination Kit and 12 in Vent Section SV4 5L12 16 3 4 to 20 426 to 508 Termination...

Страница 22: ...5HF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF Note See Table 9 as an aid in venting component selection for a particular range of exterior...

Страница 23: ...meters Max H H1 H2 20 feet 6 096 meters Max Example If 20 feet total H H1 H2 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio F...

Страница 24: ...nner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pull a...

Страница 25: ...es 43 and 44 b Optional Wall Switch Wall Thermostat OrRemoteControlReceiver Installsnap bushing provided in Electrical Outlet Kit See Figure 44 into control switch knock out in side panel see Figures...

Страница 26: ...x Wiring when using unit mounted relay module BK W G C A V 0 2 1 Igniter Connector Leave the OFF ON switch which is integral with the gas valve in the ON position Optional Control Switches Wall Switch...

Страница 27: ...that will allow the shut off valve to be easily attached by hand to the gas flex line Using pipe dressing materials appropriate for the gas type securely affix the shut off valve to this determined pi...

Страница 28: ...al tongues of flame on the burner Make sure all ports are open and producing flame evenly across the burner If any ports are blocked or partially blocked clean out the ports With the gas line installe...

Страница 29: ...ers as it is being installed c Asafinalcheckforcorrectlogsetplacement check that the four outer notches on the underside of the log set fit over the burner tines as indicated in Figure 53 Burner Grate...

Страница 30: ...ld be increased If air shutter is open too far Flame will be blue Air shutter gap should be decreased Step 9 INSTALLATION AND REMOVAL OF GLASS DOOR Only doors certified with the appliance shall be use...

Страница 31: ...lly clockwise Propane fully counter clockwise Settings are shown for each burner Air Shutter Adjusting Rod Air Shutter Adjusting Arms Orifice Increase Shutter Opening In This Direction Decrease Shutte...

Страница 32: ...ur liminer la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisis...

Страница 33: ...flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashing 6 77L79 SV4 5FA 1 2 to 7 12 Adjustable Flashing 6 77L80 SV4 5FB 7 2 to 12 12 Adjustable Flashing 7 77L81 SV4 5SC6 Storm Co...

Страница 34: ...12 Mill Pac Black High Temperature Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 25 H1988 CTSA 33 Ch...

Страница 35: ...th the re quirements of the CAN CSA B149 1 Installation code Laconversiondevra treeffectu e conform ment aux recommanda tions des autorit s provinciales ayant juridiction et conform ment aux exigences...

Страница 36: ...rimary air opening setting NOTE Each model has two burners and 2 Orifices Pilot Orifice Pilot Assembly Igniter Assembly Retaining Clip Flare Nut Note If the igniter is damaged a replacement kit is ava...

Страница 37: ...S NOTE INSTALL REAR BURNER FIRST THEN FRONT BURNER BURNER ORIFICE Step 10 Reassemble the remaining compo nents by reversing the procedures outlined in the preceding steps Step 11 Attach the conversion...

Страница 38: ...38 NOTES...

Страница 39: ...39 39 NOTES...

Страница 40: ...earth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor...

Отзывы: