NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Also see 

Figures 12 and 

13 on Pages 10 

and 11

5-5/8"

(143 mm)

3-1/8"

(79 mm)

Figure 14 - 

ROUTE GAS LINE

Proper Sizing of Gas Line

Properly  size  and  route  the  gas  supply  line 

from the supply regulator to the area where 

the  appliance  is  to  be  installed  per  require-

ments outlined in the National Fuel Gas Code, 

NFPA 54 - latest edition (USA) or B149 - latest 

edition (Canada).  

Never  use  galvanized  or  plastic  pipe.    Refer 

to Table 7 for proper sizing of the gas sup-

ply line, if black iron pipe is being used. Gas 

lines must be routed, constructed and made 

of materials that are in strict accordance with 

local codes and regulations. We recommend 

that a qualified individual such as a plumber 

or gas fitter be hired to correctly size and route 

the gas supply line to the appliance. Installing 

a gas supply line from the fuel supply to the 

appliance involves numerous considerations of 

materials, protection, sizing, locations, controls, 

pressure, sediment, and more. Certainly no one 

unfamiliar and unqualified should attempt sizing 

or installing gas piping.

Schedule  40 / Black Iron Pipe

Inside Diameter (Inches)

Schedule  40 Pipe

Length (feet)

Natural

Gas

Propane

Gas

0-10

1/2

3/8

10-40

1/2

1/2

40-100

1/2

1/2

100-150

3/4

1/2

150-200

3/4

1/2

Table 7

Notes:

•  All  appliances  are  factory-equipped  with  a 

flexible gas line connector and 1/2 inch shutoff 

valve (see Figure 47 on Page 27).

•  See Massachusetts Requirements on Page 

4  for additional requirements for installations 

in the state of Massachusetts in the USA.

•  The gas supply line should Not be connected 

to the appliance until Step 6 (Page 27).

•  A pipe joint compound rated for gas should be 

used on the threaded joints. 

Ensure propane 

resistant compounds are used in propane 

applications.

  Be  very  careful  that  the  pipe 

compound does not get inside the pipe.

•  It is recommended to install a sediment trap 

in the supply line as close as possible to the 

appliance (see Figure 47).  Appliances using 

Propane  should have a sediment trap at the 

base of the tank.

•  Check with local building official for local code 

requirements (i.e. are below grade penetrations 

of the gas line allowed?, etc).

IMPORTANT: If propane is used, be aware that 

if tank size is too small (i.e. under 100-lbs, if 

this is the only gas appliance in the dwelling. 

Ref. NPFA 58), there may be loss of pressure, 

resulting  in  insufficient  fuel  delivery  (which 

can result in sooting,  severe delayed ignition 

or other malfunctions). Any damage resulting 

from an improper installation, such as this, is 

not covered under the limited warranty.

Step 2. ROUTING GAS LINE

Route a gas line along the inside of the right 

side  framing  as  shown  in  Figure  14.    Gas 

lines must be routed, constructed and made 

of materials that are in strict accordance with 

local codes and regulations.  All appliances are 

factory-equipped with a flexible gas line con-

nector and 1/2 inch shutoff valve (see 

 

Step 

on

 

Page 27).

Содержание SSDVPF-CNE-B

Страница 1: ...de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l entretien doivent tre assur s par...

Страница 2: ...e installed the electrical power must be provided at the time of appliance in stallation The Electronic appliances have an electronic intermittent pilot ignition system External electrical power is re...

Страница 3: ...y be required due to excessive lint from carpeting bed ding material etcetera It is imperative that control compartments burners and circulating air passageways of the appliance be kept clean Remarque...

Страница 4: ...e reduced by either Using gas that has been derated by the gas company Changing the burner orifice to a smaller size as regulated by the local authorities having jurisdiction and by the USA National F...

Страница 5: ...rer s instructions and the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 in the United States or the StandardforInstallationinMobileHomes CAN CSA Z240 MH Series in Canada C...

Страница 6: ...54 ANSI Z223 1 Roof Pitch Feet Meters Flat to 6 12 1 0 0 3 6 12 to 7 12 1 25 0 38 7 12 to 8 12 1 5 0 46 8 12 to 9 12 2 0 0 61 9 12 to 10 12 2 5 0 76 10 12 to 11 12 3 25 0 99 11 12 to 12 12 4 0 1 22 12...

Страница 7: ...cm for appliances 10 000 BTU hr 3kW 12 in 30 cm for appliances 10 000 BTU hr 3kW and 100 000 BTU hr 30kW 36 inches 91 cm for appliances 100 000 BTU hr 30kW 6 in 15 2 cm for appliances 10 000 BTU hr 3...

Страница 8: ...owing exception If the optional radiant panels are installed the non combustible material may cover any portion of the top radiant panel or the air gaps surrounding the top radiant panel down to the t...

Страница 9: ...plates and remove the cardboard from beneath each plate be careful not to damage the white gasket See Figure 10 NOTE INSTALLATION DIAGRAMS AND INSTRUCTIONSSHOWTHEFRONTOFTHE APPLIANCEASTHESIDEWHICHHAS...

Страница 10: ...108 679 11 3 8 267 289 7 178 5 1 8 130 12 1 8 308 10 1 2 22 3 4 578 6 1 4 159 A 7 178 5 1 8 130 12 1 8 308 26 3 4 Provide additional space for Side Vent Seal Cap if installing against a solid wall Lou...

Страница 11: ...uance without notice Appliance has a factory installed vent seal cap see Figures 15 and 16 on Page 13 in each flue outlet EFFICIENCIES SSDVPF 58 NG 61 LP Steady State 72 NG 73 LP AFUE 68 NG 68 LP Louv...

Страница 12: ...torand1 2inchshutoff valve see Figure 47 on Page 27 See Massachusetts Requirements on Page 4 foradditionalrequirementsfor installations in the state of Massachusetts in the USA The gas supply line sho...

Страница 13: ...1 in Canada Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier D gagementconformeauxcodesd installationlocauxetauxexigences du foumisseunde gaz...

Страница 14: ...0 0 3 5 4 5 7 3 0 0 2 0 0 2 5 6 4 5 7 8 3 0 0 0 0 1 1 5 9 4 5 2 1 4 1 0 2 0 0 3 1 5 5 2 4 1 0 0 0 1 2 5 5 5 5 2 6 4 0 1 2 0 0 3 7 5 5 7 4 0 0 1 1 0 2 6 6 5 2 5 0 2 2 0 0 4 5 7 6 5 2 6 5 0 0 3 0 0 3 9...

Страница 15: ...4 5LA may be used to provide the installer with an option in installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location or...

Страница 16: ...ections see Figure 23 Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary It is important to maintain the required clear ancestocombustibles 1 25mm at...

Страница 17: ...ori zontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio Forevery1footof V verti cal you are allowed 5 feet of H horizontal run up to a...

Страница 18: ...4 2 0 610 1 0 305 10 3 048 4 1 219 2 0 610 15 4 572 6 1 829 3 0 914 20 6 096 8 2 438 4 1 219 V V1 H H1 40feet 12 2m Max H 8 feet 2 438 meters Max H H1 20 feet 6 096 meters Max Example If 20 feet total...

Страница 19: ...geandsealboththe inner and outer pipe elements with the same procedure Sealant and securing screws are not required Note An elbow may also be attached to the appliance collar Attach in the same manner...

Страница 20: ...ey are in the same area as a hot termination To prevent contact with hot surfaces we recommend the use of a Termination Guard See Page 33 This can be purchased at your local dealer SV4 5HT 2 Terminati...

Страница 21: ...hes mm Termination Kit Only 6 to 9 1 4 152 to 235 TerminationKitand 6In Vent Section SV4 5L6 10 3 4 to 14 273 to 356 Termination Kit and 12 in Vent Section SV4 5L12 16 3 4 to 20 426 to 508 Termination...

Страница 22: ...5HF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF Note See Table 9 as an aid in venting component selection for a particular range of exterior...

Страница 23: ...meters Max H H1 H2 20 feet 6 096 meters Max Example If 20 feet total H H1 H2 horizontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio F...

Страница 24: ...nner flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pull a...

Страница 25: ...es 43 and 44 b Optional Wall Switch Wall Thermostat OrRemoteControlReceiver Installsnap bushing provided in Electrical Outlet Kit See Figure 44 into control switch knock out in side panel see Figures...

Страница 26: ...x Wiring when using unit mounted relay module BK W G C A V 0 2 1 Igniter Connector Leave the OFF ON switch which is integral with the gas valve in the ON position Optional Control Switches Wall Switch...

Страница 27: ...that will allow the shut off valve to be easily attached by hand to the gas flex line Using pipe dressing materials appropriate for the gas type securely affix the shut off valve to this determined pi...

Страница 28: ...al tongues of flame on the burner Make sure all ports are open and producing flame evenly across the burner If any ports are blocked or partially blocked clean out the ports With the gas line installe...

Страница 29: ...ers as it is being installed c Asafinalcheckforcorrectlogsetplacement check that the four outer notches on the underside of the log set fit over the burner tines as indicated in Figure 53 Burner Grate...

Страница 30: ...ld be increased If air shutter is open too far Flame will be blue Air shutter gap should be decreased Step 9 INSTALLATION AND REMOVAL OF GLASS DOOR Only doors certified with the appliance shall be use...

Страница 31: ...lly clockwise Propane fully counter clockwise Settings are shown for each burner Air Shutter Adjusting Rod Air Shutter Adjusting Arms Orifice Increase Shutter Opening In This Direction Decrease Shutte...

Страница 32: ...ur liminer la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisis...

Страница 33: ...flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashing 6 77L79 SV4 5FA 1 2 to 7 12 Adjustable Flashing 6 77L80 SV4 5FB 7 2 to 12 12 Adjustable Flashing 7 77L81 SV4 5SC6 Storm Co...

Страница 34: ...12 Mill Pac Black High Temperature Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 25 H1988 CTSA 33 Ch...

Страница 35: ...th the re quirements of the CAN CSA B149 1 Installation code Laconversiondevra treeffectu e conform ment aux recommanda tions des autorit s provinciales ayant juridiction et conform ment aux exigences...

Страница 36: ...rimary air opening setting NOTE Each model has two burners and 2 Orifices Pilot Orifice Pilot Assembly Igniter Assembly Retaining Clip Flare Nut Note If the igniter is damaged a replacement kit is ava...

Страница 37: ...S NOTE INSTALL REAR BURNER FIRST THEN FRONT BURNER BURNER ORIFICE Step 10 Reassemble the remaining compo nents by reversing the procedures outlined in the preceding steps Step 11 Attach the conversion...

Страница 38: ...38 NOTES...

Страница 39: ...39 39 NOTES...

Страница 40: ...earth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor...

Отзывы: