background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

9

Note:

 If there is a room above ceiling level,

firestop spacer must be installed on the bottom
side of the ceiling. If an attic is above ceiling
level, firestop spacer must be installed on top
side of ceiling joist (Figures 21 and 22 ).

Figure 21

Figure 22

CHIMNEY 30

°

 OFFSET THROUGH FLOOR

OR CEILING

It may be necessary to assemble the chimney at
30

°

 when passing through the floor or ceiling

area. Use the F8FS30 firestop spacer as shown
in 

Figures 23 and 24. Support the chimney at

floor or ceiling penetration with a FTF8 stabi-
lizer if distance of chimney below ceiling is 10'
or more. Maintain 1"* minimum air space to
combustibles from chimney sections.

*Note:

 2" clearance to combustibles required

in Canada.

Firestop Spacer

Room Above

Firestop Spacer

Attic Above

F8FS30

Firestop Spacer

FTF8-S4 Stabilizer

1"* Min.

Air Space

30

°

 Firestop

And Attic Above

10'

Max.

Attic Space

1"* Min.

Air Space

Figure 23

F8FS30

Firestop Spacer

FTF8-S4 Stabilizer

30

°

 Firestop

And Room Above

10'

Max.

Room Above

1"* Min.

Air Space

1"* Min.

Air Space

Figure 24

For Canada Only

When installing the chimney system through
an open attic space, the attic shield assembly-
firestop spacer must be used (

Figure 25 ). This

installation is required only for use in Canada.

Note:

 For Canadian installations, all chimney

installed outside the building must be constructed
with galvalume (outer sections only) effective
January 1, 1992. The appropriate model desig-
nations are located in the back of this manual.

Step 4.

 Note:

 Chimney sections are con-

structed with a unique locking tab design,
which ensures an immediate, tight assembly
between sections. Plan your chimney require-
ments carefully before assembly as chimney
is difficult to disassemble after installation. If
disassembled, the tabs might become dam-
aged. Be certain tabs are properly formed to
ensure locking tabs engage properly.

The Security Chimneys FTF8 chimney system
is a two piece chimney, which snap together
from the fireplace up. Start with the inner flue
section with the lanced end up, snap lock it in to
the matching collar on top of the fireplace. At all
subsequent joints, the upper flue section fits
into the preceding flue section. Each piece
snaps together by means of locking tabs (9
locking tabs per joint). Check each piece by
pulling up slightly from the top to ensure proper
engagement before installing the next section.

Figure 25

Open Attic Space

If the flue has been installed correctly, it will not
separate when you test it. Also, the inner flue
joint where each section is joined should be
tight and flat without gaps (

Figure 26 ).

Figure 26

Outer pipe section installs in just the opposite
way; the lanced end goes down and each new
section goes OVER the outside of the previous
section installed (

Figure 27 ).

Figure 27

Note:

 Assemble one component of chimney at a

time (inner section first, then outer section last)
before proceeding with the next complete section.

Continue to assemble the chimney up through
framed opening. Assemble just enough to pen-
etrate the roof flashing openings (

Figure 28 ).

Always maintain 1"* minimum air space to
combustible materials and always check each
chimney joint (inner and outer) to ensure proper
engagement. Check vertical alignment of chim-
ney so that it projects from the roof in true
vertical position.

Figure 28

Locking

Tabs

(Lances)

1"* Min. Air Space
To Combustibles

Содержание BC-42

Страница 1: ...r or modify the fireplace or its components under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney components and accessories...

Страница 2: ...hysical damage as a result of handling or transporta tion These items should be inspected by your distributor or qualified factory representative to ensure safe condition When in doubt con sult your d...

Страница 3: ...11 and in accordance with codes such as the BOCA Basic National Codes the Standard Me chanicalCodeandtheUniformBuildingCodes When complete these fireplace systems con sists of five basic sub systems 1...

Страница 4: ...ermal Barrier 8 Level Chase Enclosure A chase is a vertical box like structure con structedtosurroundthefireplaceandchimney Refer to Figure 2 for a typical chase configura tion As with all chimney ins...

Страница 5: ...l safety strips beneaththefireplaceasillustrated Figures6 7 and 8 The safety strips should overlap for continual coverage of the floor Note Safety strips are not required when fire place rests on a no...

Страница 6: ...surface If a wall covering such as drywall is to be attached to the rear wall then the 20 524 mm must be measured from the drywall surface It is important that this dimension be exact If the appliance...

Страница 7: ...Shown FOAK Combustion Air Kit Optional Note All framing dimensions calcu lated for 1 2 dry wall at the fireplace face Ifsheathingthechaseorfinish ing with other thickness materials calculations will...

Страница 8: ...nsions In new construction to determine chimney cen terline useplumblinefromrooforceilingabove fireplace to center of flue collar on fireplace For remodeling plumb to center of flue collar from ceilin...

Страница 9: ...ign which ensures an immediate tight assembly between sections Plan your chimney require ments carefully before assembly as chimney is difficult to disassemble after installation If disassembled the t...

Страница 10: ...ht dam age the chimney section refer to Figure 32 Note If chimney extends more than 8 above roof surface guy wires are also recommended Use three 3 guy wires attach to locking band assembly extend and...

Страница 11: ...Thetopofthechimneymustbeatleast2 above this reference point In all cases the chimney cannotbelessthen3 abovetheroofattheedge of the chimney The 2 in 10 rule is necessary in the interest of safety but...

Страница 12: ...374 31 2 0 1 1 7 380 31 8 1 0 0 8 Step 2 Use Height of Chimney Only column in The Vertical Elevation Chart to determine combinations of chimney used above return elbow to achieve desired heights Refer...

Страница 13: ...35 69 1 0 0 1 0 1 37 73 1 0 0 2 1 0 38 75 1 0 0 0 2 0 39 77 1 0 2 1 1 0 41 80 1 0 1 4 0 0 43 83 1 0 1 0 2 0 44 85 1 0 0 0 1 1 45 87 1 0 0 3 1 0 46 89 1 0 0 1 2 0 48 91 1 0 2 0 2 0 49 94 1 0 1 0 1 1 50...

Страница 14: ...ection Joints No 8 x 1 2 SMS S c r e w s R e q u i r e d A t E v e r y J o i n t P a s t 6 N o S c r e w s R e q u i r e d I n J o i n t s F o r F i r s t 6 o f O f f s e t 4 6 Underside Of Chimney Ch...

Страница 15: ...ck all connections with soap suds leaks will bubble Never test any gas line con nection with a match or open flame This provision is intended for connection to a decorative gas appliance incorporating...

Страница 16: ...of millboard or a du rable noncombustiblematerialhavinganequal or greater insulating value than K 54BTU IN FT2 HR F At no time may a perpendicular side wall be positioned closer than 9 inches Figure...

Страница 17: ...R values are used to determine acceptable combinations of materi als because R values are additive where r and k values are not Hearth Extension Dimensions A 16 B 35 C 8 D 51 A B D C C R value 1 r x...

Страница 18: ...um of all R values is 70 10 068 10 968 This would not be an acceptable combination of material for the hearth extension since the total calculated R value of the materials used is under the required R...

Страница 19: ...63L42 FTF8 CTD Chase Termination Square 63L48 FTF8 CT1 Chase Termination Round 63L45 FTF8 CTDT Chase Termination Square 63L51 FTF8 CT2 Forced Air Blower Kits Single Speed 80L84 FBK 100 Variable Speed...

Страница 20: ...M REV C 11 2003 The manufacturer reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your...

Отзывы: