HOT AIR DUCTING INSTALLATION

The WCT6820WS wood burning fireplace is 

approved for use with a Gravity kit (hot air 

ducting system).

Gravity Kit

The gravity kit is designed for double hot air 

outlets and includes: (See

 Figure 14).

  -  Two (2) telescopic lengths  8” I.D.

  -  Two (2)  90º elbows  8” I.D.

  -  Two (2) hot air outlet kits 

     (grill and frames) 

  -  Two (2) adaptors

See 

Gravity Kit Accessories Page 21

.

For safe installation, the gravity kit must meet 

the following requirements:

 

Minimum height*

  68”  (1,727 mm)

 

Maximum length  

 See 

Figure 14

*  The height of the louver must be measured 

from the base of the WCT6820WS fireplace to 

the middle point of the louver.

The only blower that can be used with the gravity 

kit is the one sold with the fireplace.

To extend the double outlet system, it will be 

necessary to purchase two adjustable lengths 

(H8951).  

Figure 15

When installing the double outlet system, the 

hot air outlets can be installed in the same room 

as the fireplace, or one or both of the outlets 

can be installed in adjacent or upper rooms.  

Installing the ducts at different elevations will 

tend to exhaust more heat out of the higher 

outlet (

Figure 14)

.

Figure 14

Frame

Grill

Noncombustible Facing

Drywall

2 x 3 Min.

Rock Board or Other

Spacer

Figure 12

FIREPLACE BLOWER

The fireplace comes equipped with a heat acti-

vated blower. It is located in the bottom  of the 

fireplace, towards the back. It uses 120V and 

must be connected to the main electrical circuit 

by a qualified electrician. For connection, use the 

electrical box supplied with the unit located on 

the bottom right corner of the fireplace.
If you wish to adjust the blower speed, the 

variable speed control (VRUW) provided must 

be installed in line with the wiring. Again, use 

a qualified electrician for installation.
If the blower requires servicing,

1- Remove the doors and decorative facade.

2- Remove the screw located below the blower 

motor that holds it to the back of  fireplace.

3- Pull the blower out of the unit through the 

square hole located in the front bottom right 

corner.  

Figure 13

Only non-combustible mate-

rial should be superposed or 

projecting over the front of 

the fireplace.

42”

(1067mm)

Min.

WARNING:  Both pipes of 

the double hot air outlet 

must be installed. Any oth-

er installation may cause 

fire and void warranty.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

11

13” x 13”

10’ 

(3.1m)

Max.

Maintain at least 6-1/2” 

(160 mm) clearance from 

the outlet grill framing to 

a combustible ceiling, 

side wall or mantel.

Outlet Grill

Outlet Grill

WARNING: The outlet grills 

should not be installed fac-

ing upward through a floor.  

Danger of burns can result 

if grills in floor are stepped 

on.

(330mm x 330mm)

10’ (3.1m)

Max.

Содержание WCT6820

Страница 1: ...of glass doors Install this fireplace in a square and plumb condition using shims as necessary at sides and or bottom Install the fireplace only as described in these instructions This installation ma...

Страница 2: ...s ensure that the air inlet to the fireplace is free from debris and any other obstructions that can block the entrance of air WARNING Neither the manufacturer nor the seller warrants smoke free opera...

Страница 3: ...del ASHT S 2100 HT6000 HT6103 or AC manufactured by Security Chimneys Inter national only including Chimney lengths Elbows where necessary Associated components as per these installation instructions...

Страница 4: ...ing 10 to 20 minutes after reloading depending on the heat and on the moisture content of the wood Onceyouhavereachedthedesiredtemperature the air boost can be closed and the primary air set to a medi...

Страница 5: ...e Monitor Recommended Carbon Monoxide Poisoning Early signs of carbonmonoxidepoisoningaresimilartotheflu withheadaches dizzinessand ornausea Ifyou have these signs obtain fresh air immediately Somepeo...

Страница 6: ...o 11 20 NOTE The use of a firewood moisture meter is rec ommended to ensure the firewood contains less than 20 moisture Seasoning Guide Softwoods 6 months to 18 months Hardwoods 12 months to 24 months...

Страница 7: ...supplied will be necessary for this adjustment Checking Door Seal A one inch strip of paper may be used to perform a test of the integrity of the door seal Close the door on the paper in at least eigh...

Страница 8: ...cover the entire width of the fireplace The combustible floor in front of the fireplace must be covered with a non combustible ma terial tile marble stone etc See Figure 7 Cold climate INSTALLATIONS...

Страница 9: ...nstallation instructions Product designs materials dimensions specifications colors and prices are subject to change or discontinuance without notice Allframingdimensionscalculatedfor 1 2 dry wall at...

Страница 10: ...tside Walls Of Chase Solid Continuous Surface Outside Base Insulation Thermal Barrier 8 Level 7 2 1 m Min 6 8 2 m Min 8 2 4 m Level 42 1067mm 2 x 3 Min 51mm x 76mm Rock Board or Other Noncombustible F...

Страница 11: ...replace Blower The fireplace comes equipped with a heat acti vated blower It is located in the bottom of the fireplace towards the back It uses 120V and must be connected to the main electrical circui...

Страница 12: ...diameter flexible pipe for the complete run up to thirty 30 feet and a 6 diameter pipe for a run of up to forty 40 feet The duct system must be installed respecting the following 1 Removetheplatesclo...

Страница 13: ...11 When offsets are used the pipe may not penetrate a ceiling or floor unless it is running vertical no 30 offsets Outside Intake Screw Opening Facing Down Wall Aluminum Tape Plastic Cover Insulation...

Страница 14: ...ofs place the flashing under the upper shingles and on top of the lower shingles Nail the flashing to the roof using roofing nails 6 Place the spacers and the storm collar over the flashing and tighte...

Страница 15: ...a plumb bob to line up the center of the hole Cut a hole for the chimney in the ceiling floor Frame this hole as described previously refer to section Chimney Instal lation Instructions 5 From below...

Страница 16: ...22 mm 6 1 8 156 mm 11 280 mm 14 1 8 359 mm 16 7 8 429 mm 18 7 16 468 mm 23 584 mm 26 3 16 665 mm B 27 11 16 703 mm 33 1 2 851 mm 50 7 8 1292 mm 62 1 2 1588 mm 72 5 8 1845 mm 78 7 16 1992 mm 95 3 4 243...

Страница 17: ...bustible wall with the chimney at a 30 or 45 angle an angled firestop or wall radiation shield must be installed Only one is required NOTE 45 angle for Canada only RSMI45 In cold climate locations cli...

Страница 18: ...are maintained at hot temperatures see Refueling For Best Performance To clean the glass there are a numberofspeciallydesignedcleaners YourIHP dealercanrecommendasuitablecleanerwhich is available in y...

Страница 19: ...ns provided with the support CHIMNEY MODEL MAXIMUM HEIGHT OF SUPPORTED CHIMNEY Offset Support Roof Support ASHT HT6103 6 dia 28 feet 8 54 m 29 feet 8 84 m S 2100 HT6000 6 dia 18 feet 5 49 m 20 feet 6...

Страница 20: ...cation Temporarily install the ASHT elbow on the top of the fireplace and using a level mark with an oval the location where the flue liner will enter the masonry chimney 2 In the middle of the oval d...

Страница 21: ...bow 90 8 dia 7B26ZE90 H8948 Elbow 45 8 dia 7B26ZE45 H8949 Telescopic length 8 dia 15 to 26 7B26ZLA H8950 Adjustable length 8 dia 2 5 7B26ZL2A H8951 Length two 2 feet 8KL2 H8954 Length one 1 feet 8KL1...

Страница 22: ...R2324 Log retainer bar PR SR2323 Door rod and lock PR SR2118 Steel door glass gasket PR SR1685D Cast iron door glass gasket PR SR1823H Steel and cast Iron door gasket PR SR1823G Touch up Paint Aerosol...

Страница 23: ...ess Steel Chimney 6 I D and 8 O D Double Wall Stainl Steel Listed to CAN UCL S604 and UL 103HT Description Part Cat No Lengths and Misc Chimney Components 8 length 6 Dia 6L8 6L8 12 length 6 Dia 6L12 6...

Страница 24: ...8 Length 6 Dia 6LL48 6LL48 Adjustable Length 7 to 11 6 Dia 6L7A 6L7A Split Base Tee 6 Dia 6LT 6LT Tee Cap 6 Dia 6TCS 6TCS Twist Lock Tee Cap 6 Dia 6LTC 6LTC Elbow 30 6 Dia 6LE30 6LE30 Elbow 45 6 Dia 6...

Страница 25: ...ormal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with abnormal burning...

Страница 26: ...ct your IHP dealer for any questions or concerns Replacement parts See Page 22 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered...

Отзывы: