VENTILATION AIR

Ventilation Air From Inside Building 

This fresh air would come from an adjoining 
unconfi ned  space.  When  ventilating  to  an 
adjoining unconfi ned space, you must provide 
two permanent openings: one within 12" of the 
ceiling and one within 12" of the fl oor on the 
wall connecting the two spaces

 (see options 

1 and 2, 

Figure 4

). 

You can also remove door 

into adjoining room

 (see option 3, 

Figure 4

)

Follow  the 

National  Fuel  Gas  Code,  ANSI 

Z223.1/NFPA  54,  Air  for  Combustion  and 
Ventilation

  for  required  size  of  ventilation 

grills or ducts.

AIR FOR COMBUSTION AND VENTILATION

Continued

Ventilation Air From Outdoors

Provide  extra  fresh  air  by  using  ventilation 
grills or ducts. You must provide two perma-
nent openings: one within 12" of the ceiling 
and one within 12" of the fl oor. Connect these 
items directly to the outdoors or spaces open 
to the outdoors. These spaces include attics 
and  crawl  spaces.  Follow  the 

National  Fuel 

Gas  Code,  ANSI  Z223.1/NFPA  54,  Air  for 
Combustion and Ventilation

 for required size 

of ventilation grills or ducts.

IMPORTANT

:

  Do  not  provide  openings 

for  inlet  or  outlet  air  into  attic  if  attic  has  a 
thermostat-controlled power vent. Heated air 
entering the attic will activate the power vent.

Figure 5 - Ventilation Air from Outdoors 

Shown with Optional Mantel

Outlet
Air

Ventilated
Attic 

Outlet
Air

Inlet
Air

Inlet Air

Ve ntilated 

Crawl Space

To  

Crawl

Space

To  Attic

Figure 4 - Ventilation Air from Inside 

Building Shown with Optional Mantel

Or  

Remove  

Door into  
Adjoining  

Room,  

Option 3 

Ventilation Grills  

Into Adjoining Room, 

Option 2 

12" 

12" 

Ventilation

Grills into
Adjoining

Room, 

Option 1

All manuals and user guides at all-guides.com

Содержание VCM3026ZTN

Страница 1: ...vided Refer to Air for Combustion and Ventilation section on Page 7 of this manual PFS US Report No F09 123 WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in s...

Страница 2: ...your guide to safe and proper operation of this heater WARNING FIRE EXPLOSION AND ASPHYXIATION HAZARD Improperadjustment alteration service maintenance orinstallationofthis heater or its controls can...

Страница 3: ...topreventchildrenfromturning on burners with remote Youmustoperatethisheaterwiththe replace screen and hood in place before running heater The replace screenshallhaveopeningsforintro duction of combus...

Страница 4: ...ue within burner box or on adjacent walls or furniture 10 This replace needs fresh air ventilation to run properly This replace has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shuts...

Страница 5: ...appliances may NOT be installed in bedrooms or bathrooms A working smoke detector must be installed in the area where vent free appliances are installed Seller of unvented propane or natural gas red...

Страница 6: ...hood as shown in Figure 3 Make sure hood tabs point toward replace 3 Insert hood tabs between baf e and lou vers see Figure 3 Figure 3 Assembling Hood Hood Louver Hood Tab Baf e Sheet Metal Screw Fir...

Страница 7: ...etween sole plates and oors between wall ceiling joints between wall panels at penetrations for plumbing electrical and gas lines and at other openings If your home meets all of the three criteria abo...

Страница 8: ...mbustion air from the outdoors and vents to the outdoors Example Gas water appliance __________ Btu Hr Gas rebox logs _________ Btu Hr Total _________ Btu Hr 4 Compare the maximum Btu Hr the space can...

Страница 9: ...openings one within 12 of the ceiling and one within 12 of the oor Connect these items directly to the outdoors or spaces open to the outdoors These spaces include attics and crawl spaces Follow the N...

Страница 10: ...o propane LP gas equipment shutoff valve test gauge connection ground joint union sediment trap tee joint pipe wrench A shutoff valve with 1 8 NPT tap is an ac ceptable alternative to test gauge conne...

Страница 11: ...aterial 0 Minimum To Top Surface Of Carpeting Tile Or Other Combustible Material Figure 6 Mounting Clearances As Viewed From Front of Fireplace Shown Built In the Wall NOTE When installing replace dir...

Страница 12: ...with pliers see Figure 10 8 Attach replace to wall studs using nails or wood screws through holes in nailing ange 9 Check all gas connections for leaks See Checking Gas Connections Page 20 10 If usin...

Страница 13: ...alling in Wall Figure 10 Attaching Fireplace to Wall Studs Nails or Wood Screws Nailing Flanges WARNING Do not allow any com bustible noncombustible materials to overlap the firebox front facing WARNI...

Страница 14: ...see mantel instruction sheet 7 Attach exible gas line to replace gas regulator See Connecting to Gas Supply Page 18 8 Route electrical cord s through access holes in either side of replace with bushi...

Страница 15: ...uver Assembly Black Screws Blower Bracket Mounting Holes Figure 13 Installing Fireplace into Mantel Assembly 5 Slide other end of adjusting plate shim in slot on mitered edge of side trim see Figure 1...

Страница 16: ...fan kit into 120 Volt grounded power supply and test operation Installing Blower Assembly CAUTION Label all wires prior to disconnection when servicingcontrols Wiringerrors cancauseimproperanddanger o...

Страница 17: ...the wir ing diagram to connect incoming electri cal supply to fan kit wiring harness see Figure 19 5 Plug power cord to the outlet receptacle not provided as shown in Figure 18 Wind the extra power c...

Страница 18: ...e of 1 2 or greater diameter to allow proper gas volume to replace If pipe is too small undue loss of volume will occur Propane LP Supply Tank External Regulator Figure 21 External Regulator with Vent...

Страница 19: ...ort Screen Screen Shipping Screw Shoulder Screw Flexible Gas Line CONNECTING EQUIPMENT SHUTOFF VALVE TO HEATER CONTROL Installation Items Needed Phillips screwdriver sealant resistant to propane LP ga...

Страница 20: ...SYSTEM Test Pressures In Excess Of 1 2 PSIG 3 5 kPa 1 Disconnect appliance with its appliance main gas valve control valve and equip ment shutoff valve from gas supply piping Pressures in excess of 1...

Страница 21: ...actly a re or explosion may result causing property damage per sonal injury or loss of life A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these instructions...

Страница 22: ...en in place Make sure re place screen is installed before running replace NOTICE Duringinitialoperation of new replace burning logs will give off a paper burning smell Orange ame will also be present...

Страница 23: ...on location room size open air temperatures etc Frequent use of your replace will let you determine your own comfort levels MANUAL LIGHTING PROCEDURE 1 Follow steps 1 through 5 under Lighting Instruct...

Страница 24: ...liance Page 23 see Troubleshooting Page 26 Figure 33 Correct Burner Flame Pattern Figure 34 Incorrect Burner Flame Pattern INSPECTING BURNER Check pilot ame pattern and burner ame pattern often PILOT...

Страница 25: ...reas of replace before each use Have replace inspected yearly by a quali ed service person Fireplace may need more frequent cleaning due to excessive lint from carpeting bedding material pet hair etc...

Страница 26: ...in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Free igniter cable if pinched by any metal or tubing Keep igniter cable dry 2 R...

Страница 27: ...t Repeat ignition operation 4 Fully open equipment shut off valve 5 Hand tighten until snug then tighten 1 4 turn more 6 A Contact local propane LP or natural gas company B Clean ODS pilot see Cleanin...

Страница 28: ...minute 2 Operate burner until air is removed from line Have gas line checked by local propane LP gas company 3 Observe minimum installa tion clearances see Pages 10 through 14 4 Clean burner see Clean...

Страница 29: ...k See Warning statement above 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement above 1 Not enough combustion ventilation air REMEDY 1 Ventil...

Страница 30: ...l gas supplier TECHNICAL SERVICE You may have further questions about instal lation operation or troubleshooting Please contact your IHP dealer for any questions or concerns When contacting your deale...

Страница 31: ...Page of this manual Only kits supplied by IHP shall be used in the in stallation of this appliance Use of non approved accessory part kit s can result in poor perfor mance and safety hazards ACCESSORI...

Страница 32: ...25 27 20 4 35 12 24 12 1 14 25 14 40 3 37 26 39 39 5 6 Cat No Model Description F1215 VCM3026ZTN 26 T Stat NG F1216 VCM3026ZTP 26 T Stat LP WARNING Contact an IHP dealer to obtain any of these parts N...

Страница 33: ...nch Support 1 21 J3647 Gas Regulator 1 J3648 Gas Regulator 1 22 J3779 Regulator Bracket 1 23 J3714 Valve Cover and Piezo 1 24 J3635 Pilot Tube 1 25 J3567 Igniter Cable 1 26 J4013 Injector 0 059 1 J401...

Страница 34: ...________________________________________________ ______________________________________________________ ______________________________________________________ _________________________________________...

Страница 35: ...y Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failin...

Страница 36: ...tion Printed in U S A 2014 Innovative Hearth Products P N 126871 01 Rev B 04 2018 SuperiorFireplaces us com Record the following important information about your appliance Appliance model number Appli...

Отзывы: