background image

 

8

6.2.2. 

Delayed Output

 (A5, K2) 

The  delayed output option allows time for the power to 
stabilize 

before 

energizing 

the 

load. 

This 

is 

accomplished  by  adding  a  contactor  and  timer  to  the 
regulator.  When  the  regulator  is  initially  energized:  the 
timer  starts.  After  the  preset  time  delay  the  contactor 
automatically  closes  energizing  the  load.  The  time 
delay  is  field  adjustable  from  approximately  5  to  30 
seconds  and  factory  adjusted  to  approximately  10 
seconds when shipped. 
 

6.2.3. 

Manual Bypass Switch

 (S3) 

This  two-position  switch,  in  the  REGULATOR  position, 
provides  conditioned  power  from  input  source  through 
the  regulator  to  the  load.  In  the  BYPASS  position  the 
input  power  and  load  are  disconnected  from  the 
regulator’s circuits and connects together directly. THIS 
IS  A  NON-LOAD  BREAK  SWITCH  AND  INPUT 
POWER  MUST  BE  OFF  BEFORE  OPERATING.  On 
three phase units the neutral is not switched. 
 

Caution:

  This  switch  is  designed  to  provide 

unconditioned  power  to  the  load  if  a  fault  condition 
occurs. 

It  does  not  remove  all  live  power  from  the 

enclosure.

 The manual bypass switch does not bypass 

the  input  circuit  breaker  or  zig-zag  transformer  if  so 
equipped. 
 

6.2.4. 

Ammeters

 (M1) 

An  analog  ammeter  displays  load  current  for  each 
phase. Each meter indicates the load current within 2% 
of the meters full range. 
 

6.2.5. 

Frequency meter with alarm contacts

 (M2) 

Frequency  meter  displays  the  source  frequency  and 
provides  alarm  contacts  for  values  outside  the  user's 
settable  limits.  Lower  and  upper  limit  trip  relays  are 
factory  set  at  45  Hz  and  65  Hz  respectively.  If  the 
frequency  becomes  lower  or  higher  than  user  selected 
values,  an  output  relay  is  energized.  The  relay  is 
equipped  with  a  form  “C”  normally  open  /  normally 
closed contact available for customer use. 
 
If  a  circuit  breaker  with  a  trip  coil  is  ordered  with  the 
frequency  meter,  the  system  is  configured  to 
automatically trip the breaker when a limit is exceeded. 
 

6.2.5.1.  Frequency

 

Meter Instructions

 

The  frequency  meter  owner’s  manual  is  included  with 
the  literature  sent  with  the  unit.  The  user  can  change 
the  meters  setting  without  storing  them  in  memory.  If 
the  user  changed  the  factory  settings,  and  did  not 
select  the  store  option,  the  factory  setting  can  be 
reinstated  by  pressing  both  RECALL  buttons  at  the 
same time. The stored factory settings are shown in the 
table below. 
 
To  return  the  stored  settings  to  the  factory  defaut,  tap 
the ENTER key to go to the next feature then use SET 
and  ADVANCE  keys  to  change  the  setting  to  those 
shown  below.  When  the  display  shows  Store,  tap  the 

Enter  key  to  lock  the  setting  into  memory.  If  no  other 
setting  was  stored  after  this  procedure,  pressing  both 
RECALL keys will return the meter to these settings. 
 

Feature 

Setting 

Func 

Freq 

 

Scale 

A / SC 

2.00000 

Offset 

000000. 

 

Range 

FFFF.FF 

 

Slope 

A Pos 

 

Sp lo 

000045 

 

Sp hi 

000065 

 

Gate t 

01.30 

 

Conf 1 

no setting required 

 

Conf 2 

no setting required 

 

No store 

Store 

 

 
A  front  and  rear  view  of  the  frequency  meter  is  shown 
below  with  the  N.O.  alarm  contacts  in  parallel.  The 
alarm contacts are connected to TB4 as follows: 
 

1 – HI relay Com 

 

4 - LO relay COM 

2 – HI relay N.O. 

 

5 - LO relay N.O. 

3 – HI relay N.C. 

 

6 - LO relay N.C. 

 

Frequency Meter 

 

 

 
6.2.6. 

Input Range Alarm

 (K1)

 

Input voltage range alarm closes a N.O. solid state 
contact when the regulator is providing maximum 
voltage correction.  This option senses regulator motor 
drive end of travel limit switch operation. 
 

6.2.7. 

Phase Loss, Phase Reversal Alarm 
Contacts

 (A3) 

Provided  for  three  phase  units  only,  this option senses 
the three phase voltage and operates a relay (form “C ” 
normally  open  /  normally  closed  contact)  when  any 
phase  voltage is lost, or if the voltage sequence of the 
power is reversed.  
 
If  an  input  circuit  breaker  with  a  shunt  trip  is  ordered, 
the  system  is  configured  to  automatically  trip  the 
breaker  when  there  is  a  phase  reversal.  The  system 
might  not  trip  the  breaker  when  there  is  a  phase  loss 
because  power  to  operate  the  shunt  trip  may  not  be 
available. 

Содержание STABILINE WHR34 T Series

Страница 1: ...ng WHR64 T WHR94 T WHRS34 T WHRS64 T or WHRS94 T Superior Electric reserves the right to make engineering changes on all its products Such refinements may affect information given in the instructions Therefore USE ONLY THE INSTRUCTIONS THAT ARE PACKED WITH THE PRODUCT WARNING High voltages are present inside this unit during operation Do not operate this unit unless all covers are in place Install...

Страница 2: ...2 ...

Страница 3: ...e Damage and Shortage instructions packed with the unit outlines the procedure to follow if any parts are missing or damaged 2 0 DESCRIPTION 2 1 GENERAL WHR34 T Series STABILINE Automatic Voltage Regulators are three phase 380Y 220 X 480Y 277 volt fast acting electromechanical regulators These WHR Series voltage regulators regulate each line to neutral voltage independently These voltage regulator...

Страница 4: ... S Single Control D Double Control T Triple Control LNN Size Code 3 or 4 digits R Rack Cabinet T Tall Cabinet CB Input Circuit Breaker CS Input Circuit Breaker w 120vac Shunt Trip CR Input Circuit Breaker w 120vac Under voltage Trip Release D Delayed Output M Manual Bypass Switch T Tropicalization Treatment 0 No Meter Options 1 Ammeter s 2 Frequency Meter w Alarm Contacts 3 Both 1 2 above 0 No Ala...

Страница 5: ...s are provided in the base and the rear panel of the unit for wire entry and exit The location of the power connections varies depending on the options provided On units with an input circuit breaker input connections are made directly to the circuit breaker On units without any options the input connections are located on the POWERSTAT variable transformer The input power connections are labeled ...

Страница 6: ...k for a blown fuse 5 2 SETTING OUTPUT VOLTAGE AND SENSITIVITY POTENTIOMETERS Normally the WHR Series voltage regulator should not be operated without the front panel s of the cabinet in place However during the initial operation of the regulator the front panels can be removed to allow setting the OUTPUT VOLTAGE and SENSITIVITY potentiometers 5 2 1 Energize Regulator On units equipped with a manua...

Страница 7: ...nergized when the breaker opens When alarm contact options and a circuit breaker trip option are ordered together the unit is furnished with 120 volt AC auxiliary power module A2 and the alarm circuit contacts are wired to trip the input breaker The Shunt Trip Connections Diagram shows the typical connections 6 2 1 2 Under Voltage Trip L1 In unit where the model number designates the circuit break...

Страница 8: ...trip the breaker when a limit is exceeded 6 2 5 1 Frequency Meter Instructions The frequency meter owner s manual is included with the literature sent with the unit The user can change the meters setting without storing them in memory If the user changed the factory settings and did not select the store option the factory setting can be reinstated by pressing both RECALL buttons at the same time T...

Страница 9: ...connected for all boost the units will bring extra low voltages up to nominal but will not correct high input voltages Since operation in the all boost mode will increase the voltage and heating in the WHR regulator the rated load current and in some cases the maximum rated nominal input voltage must be reduced Refer to the All Buck and All Boost Rating Chart for the all boost ratings For all boos...

Страница 10: ...less the unit is overloaded there is little likelihood of component failure Warning Voltages are present inside this unit which can cause injury Therefore only personnel qualified to service electrical equipment should perform trouble shooting procedures on this unit If the regulator fails to operate correctly the following checks will help locate and correct the problem Refer to the schematic rat...

Страница 11: ...he motor at the end of travel If the motor operates successfully in this test the problem may be with the control board 8 10 Inspect the POWERSTAT Variable Transformer brush s and commutator s for signs of wear or damage The brush assemblies on the variable transformer section will not need replacement under normal conditions When excessive brush wear or commutator damage occurs it is usually the ...

Страница 12: ...AGE 380Y 220 X 480Y 277 FREQUENCY 50 60 Hz X 60 Hz CONNECTION 3 Phase 4 Wire Wye RANGE 20 to 10 of Selected Output OUTPUT VOLTAGE 380Y 220 X 480Y 277 CONNECTION 3 Phase 3 or 4 Wire Model Number base unit Rated Load Max Input Amps Amps kVA at 380 V 480 V WHR34NTR31 15 10 13 20 WHR34NTS31 28 18 23 35 WHR34NTT31 65 43 54 80 WHR34NTT32 130 85 105 160 WHR34NTT33 195 125 160 240 WHR34NTT34 260 170 215 3...

Страница 13: ...tilated enclosures intended for indoor use under usual service conditions Temperature Operating Average ambient temperature for any 24 hour period not to exceed 30 C 86 F and maximum temperature not to exceed 40 C 104 F Average ambient temperature for any 24 hour period may be increased to 40 C 104 F and the maximum temperature may be increased to 50 C 122 F if the load is decreased to 90 of stand...

Страница 14: ...similar control module but some of the parts are specially treated and therefore have a different part number FLOOR MOUNT CONTROL MODULE ASSEMBLY A1 Standard Tropicalized Reference Symbol Part Description Part Number Part Number A1 CONTROL MODULE 213244 004 213244 008 A1 A1 CONTROL BOARD 227412 001 227412 001 SM A1 F1 F2 F3 F4 FUSE 600V 213274 001 A1 LP1 LP2 LIGHT INDICATOR GREEN 227571 001 A1 M1 ...

Страница 15: ...REPLACEMENT BRUSH ASSEMBLY Each POWERSTAT Variable Transformer contains a durable brush assembly These assemblies are designed to reduce the need for attention or replacement however because these are moving parts that rely on contact friction to operate properly an annual inspection is suggested Refer to the maintenance section of this manual for details The replacement brush assembly is listed a...

Страница 16: ...16 11 0 SCHEMATIC For reference only use full size supplied with unit ...

Страница 17: ...17 12 0 FLOOR MOUNT DIMENSIONS Enclosures A through G Note All dimensions are inches millimeters ...

Страница 18: ...18 Enclosures A through G continues Note All dimensions are inches millimeters ...

Страница 19: ...19 Enclosures A through G continues Note All dimensions are inches millimeters ...

Страница 20: ...20 Enclosures DPLUS through GPLUS Note All dimensions are inches millimeters ...

Страница 21: ...21 Enclosures DPLUS through GPLUS continues Note All dimensions are inches millimeters ...

Страница 22: ...22 Enclosures DD through GG Note All dimensions are inches millimeters ...

Страница 23: ...23 Enclosures DD through GG continues Note All dimensions are inches millimeters ...

Страница 24: ...24 Enclosures EEE through GGG Note All dimensions are inches millimeters ...

Страница 25: ...25 Enclosures EEE through GGG continues Note All dimensions are inches millimeters ...

Страница 26: ...which offer literature technical assistance and a select range of models off the shelf for fastest possible delivery and service In addition Superior Electric Manufacturer s Representatives are available to provide prompt attention to customer needs Call or fax for ordering and application information or for the address of the closest Manufacturer s Representative Authorized Distributor or Reselle...

Отзывы: