13
9.3. GENERAL SPECIFICATIONS
Electrical:
Output Accuracy
Adjustable from 1% to 3%
Response Time
0.025 seconds at 60 Hz,0.030 seconds at 50 Hz
Load Capacity
100% rated continuous
200% rated 60 seconds
400% rated 3 seconds
600% rated 1 second
800% rated 0.5 second
1000% to 2500% 1/2 cycle inrush
Load Power Factor
0 lagging to 0 leading
Load Crest Factor
6 Max (I peak / I RMS)
Efficiency
99% typical, at full load
Heat Generated
BTU (typical) = 35 x rated kVA
Harmonic Distortion
Less than 1% added
Surge Withstand Capability
6000 volts per IEEE C62.41, location category B
Impedance
1% (typical) without transient suppression option
2% (typical) with transient suppression option
Transverse-Mode Noise
Attenuation
40 dB (typical) with transient suppression option
Environmental:
Service Conditions
Units are housed in NEMA 1 ventilated enclosures, intended for indoor use
under usual service conditions.
Temperature
Operating
Average ambient temperature for any 24 hour period not to exceed 30°C
(86°F), and maximum temperature not to exceed 40°C (104°F). Average
ambient temperature for any 24 hour period may be increased to 40°C
(104°F),and the maximum temperature may be increased to 50°C (122°F),if
the load is decreased to 90%of standard rating. Minimum temperature is
0°C (32°F).
Storage
-40°C to +70°C (-40°F to +158°F)
Humidity (Operating and Storage)
Units without tropicalization
10 to 75% average relative humidity for any 7 day period, and maximum
relative humidity not to exceed 95% non-condensing.
Units with tropicalization
10 to 95% average relative humidity and maximum relative humidity not to
exceed 95% non-condensing.
Altitude
Operating
Maximum Altitude
Derating
6,600 Ft.(2,000 meters)
No de-rating
10,000 Ft.(3,000 meters)
load to 95%,ambient 30°C (86°F)
15,000 Ft.(4,500 meters)
load to 90%,ambient 20°C (68°F)
Storage
50,000 Ft.(15,000 meters)max
Содержание STABILINE WHR34 T Series
Страница 2: ...2 ...
Страница 16: ...16 11 0 SCHEMATIC For reference only use full size supplied with unit ...
Страница 17: ...17 12 0 FLOOR MOUNT DIMENSIONS Enclosures A through G Note All dimensions are inches millimeters ...
Страница 18: ...18 Enclosures A through G continues Note All dimensions are inches millimeters ...
Страница 19: ...19 Enclosures A through G continues Note All dimensions are inches millimeters ...
Страница 20: ...20 Enclosures DPLUS through GPLUS Note All dimensions are inches millimeters ...
Страница 21: ...21 Enclosures DPLUS through GPLUS continues Note All dimensions are inches millimeters ...
Страница 22: ...22 Enclosures DD through GG Note All dimensions are inches millimeters ...
Страница 23: ...23 Enclosures DD through GG continues Note All dimensions are inches millimeters ...
Страница 24: ...24 Enclosures EEE through GGG Note All dimensions are inches millimeters ...
Страница 25: ...25 Enclosures EEE through GGG continues Note All dimensions are inches millimeters ...