background image

 

2

 

TABLE OF CONTENTS 

 
SECTION

 

PAGE 

 

SECTION

 

PAGE 

1.0 

INSPECTION

 ..............................................   2 

 

1.1  UNPACKING .......................................   2 

2.0 

DESCRIPTION

............................................   2 

 

2.1  GENERAL ...........................................   2 

 

2.2  STANDARD MODEL NUMBER SYSTEM 3 

 

2.3  THEORY OF OPERATION ..................   4 

3.0 

INSTALLATION

 ..........................................   4 

 

3.1  TRANSPORTING THE REGULATOR .   4 

 

3.2  MECHANICAL INSTALLATION ...........   4 

 

3.3  ELECTRICAL INSTALLATION ............   4 

4.0 

START UP

 ..................................................   4 

5.0 

OPERATION

 ...............................................   5 

 

5.1  CONTROL MODULE ASSEMBLY .......   5 

 

5.2  SETTING OUTPUT VOLTAGE AND 

 

 

SENSITIVITY POTENTIOMETERS .....   5 

 

5.3  REMOTE SENSING ............................   5 

6.0 

OPTIONS

 ....................................................   6 

 

6.1  NON DESIGNATED OPTIONS............   6 

 

6.2  MODEL No. SPECIFIED OPTIONS .....   6 

 

6.3 

ALL-BUCK AND ALL-BOOST OPERATION

  8 

7.0 

MAINTENANCE

 ..........................................   9 

8.0 

TROUBLESHOOTING

 ................................   9 

9.0 

RATING

 ......................................................   11 

 

9.1  POWER RATINGS ..............................   11 

 

9.2  VOLTAGE RANGE CHART .................   11 

 

9.3  GENERAL SPECIFICATIONS .............   12 

10.0 

REPLACEMENT PARTS

 ............................   13 

 

10.1 ORDERING .........................................   13 

 

10.2 CONTROL MODULE ASSEMBLY .......   12 

 

10.3 POWER COMPONENTS .....................   13 

 

10.4 REPLACEMENT BRUSH ASSEMBLY .   14 

 

10.5 AUX. POWER MODULE ......................   14 

 

10.6 RACKMODELS ....................................   14 

11.0 

SCHEMATIC

 ...............................................   15 

12.0 

FLOOR MOUNT DIMENSIONS

 ..................   16 

12.0 

RACK MOUNT DIMENSIONS

 .....................   25 

 

 
 
 

1.0. 

INSPECTION 

 
1.1.  UNPACKING 

When  unpacking  the  unit,  examine  it  carefully  for  any 
shipping  damage.  The  "Damage  and  Shortage" 
instructions packed with the unit outlines the procedure 
to follow if any parts are missing or damaged. 
 

2.0. 

 

DESCRIPTION 

 
2.1.  GENERAL 

WHR22*S***  Series  STABILINE

®

  Automatic  Voltage 

Regulators  are  single  phase,  3  wire,  240/120  volt,  fast 
acting  electromechanical  regulators.  These  WHR 
Series  voltage  regulators  regulate  the  line-to-line 
voltage.  These  voltage  regulators  have  an  analog 
electronic control section, and have a power section for 

each  line-neutral  consisting  of  one  or  more  motor 
driven, 

limited 

range 

POWERSTAT

®

 

Variable 

Transformers.  Units  with  a  suffix,  starting  with  a  dash, 
at  the  end  of  the  model  numbers  are  equipped  with 
standard  options.  Refer  to  the  WHR  model  numbering 
system  in  the  next  section  for  more  details.  See  the 
enclosed rating charts and unit nameplate for complete 
specifications. 
 
Advantages  of  all  WHR  Series  voltage  regulators 
include  high  efficiency  (99%  typical),  high  overload 
capacity  and  low  impedance.  These  voltage  regulators 
are insensitive to the magnitude and power factor of the 
load,  and  have  little  to  no  effect  on  system  power 
factor.  This  means  these  regulators  can  be  used  with 
any type load. 
 

 
 
 

Содержание STABILINE WHR22 Series

Страница 1: ...to make engineering changes on all its products Such refinements may affect information given in the instructions Therefore USE ONLY THE INSTRUCTIONS THAT ARE PACKED WITH THE PRODUCT WARNING High vol...

Страница 2: ...xamine it carefully for any shipping damage The Damage and Shortage instructions packed with the unit outlines the procedure to follow if any parts are missing or damaged 2 0 DESCRIPTION 2 1 GENERAL W...

Страница 3: ...nge S Single Control D Double Control T Triple Control LNN Size Code 3 or 4 digits R Rack Cabinet T Tall Cabinet CB Input Circuit Breaker CS Input Circuit Breaker w 120vac Shunt Trip CR Input Circuit...

Страница 4: ...mum rated current as specified by local and national code requirements The front panel s of the voltage regulator must be removed to allow access to the input and load terminals To remove a panel use...

Страница 5: ...5 2 SETTING OUTPUT VOLTAGE AND SENSITIVITY POTENTIOMETERS Normally the WHR Series voltage regulator should not be operated without the front panel s of the cabinet in place However during the initial...

Страница 6: ...eaker if the coil voltage is lost The trip coil is rated 120 volt AC The coil voltage must be present in order to close the circuit breaker 6 2 1 3 Circuit Breaker Trip Coil Alarm Contacts When alarm...

Страница 7: ...ged the factory settings and did not select the store option the factory setting can be reinstated by pressing both RECALL buttons at the same time The stored factory settings are shown in the table b...

Страница 8: ...ted load current and in some cases the maximum rated nominal input voltage must be reduced Refer to the All Buck and All Boost Rating Chart for the all boost ratings For all boost operation the input...

Страница 9: ...ess the unit is overloaded there is little likelihood of component failure Warning Voltages are present inside this unit which can cause injury Therefore only personnel qualified to service electrical...

Страница 10: ...e motor at the end of travel If the motor operates successfully in this test the problem may be with the control board 8 10 Inspect the POWERSTAT Variable Transformer brush s and commutator s for sign...

Страница 11: ...F38 850 200 1200 INPUT VOLTAGE 240 120 FREQUENCY 50 60 Hz CONNECTION 1 Phase 3 Wire RANGE 20 to 10 of Selected Output OUTPUT VOLTAGE 240 120 CONNECTION 50 60 HZ Model Number base unit Rated Load Max I...

Страница 12: ...ilated enclosures intended for indoor use under usual service conditions Temperature Operating Average ambient temperature for any 24 hour period not to exceed 30 C 86 F and maximum temperature not to...

Страница 13: ...ONTROL MODULE ASSEMBLY A1 Standard Reference Symbol Part Description Part Number A1 CONTROL MODULE 213243 002 A1 A1 CONTROL BOARD 227412 001 A1 F1 F2 F3 F4 FUSE 600V 104364 003 A1 LP1 LP2 LIGHT INDICA...

Страница 14: ...n 10 5 AUX POWER MODULE There is one standard power module used throughout this WHR Series of STABILINE Automatic Voltage Regulators It is used for Line to Line connections Line Line Reference Symbol...

Страница 15: ...15 11 0 SCHEMATIC For reference only use full size supplied with unit...

Страница 16: ...16 12 0 FLOOR MOUNT DIMENSIONS Enclosures A through G Note All dimensions are inches millimeters...

Страница 17: ...17 Enclosures A through G continues Note All dimensions are inches millimeters...

Страница 18: ...18 Enclosures A through G continues Note All dimensions are inches millimeters...

Страница 19: ...19 Enclosures DPLUS through GPLUS Note All dimensions are inches millimeters...

Страница 20: ...20 Enclosures DPLUS through GPLUS continues Note All dimensions are inches millimeters...

Страница 21: ...21 Enclosures DD through GG Note All dimensions are inches millimeters...

Страница 22: ...22 Enclosures DD through GG continues Note All dimensions are inches millimeters...

Страница 23: ...23 Enclosures EEE through GGG Note All dimensions are inches millimeters...

Страница 24: ...24 Enclosures EEE through GGG continues Note All dimensions are inches millimeters...

Страница 25: ...25 13 0 RACK MOUNT DIMENSIONS OPEN Enclosures R1 and R2 Note All dimensions are inches millimeters...

Страница 26: ...hich offer literature technical assistance and a select range of models off the shelf for fastest possible delivery and service In addition Superior Electric Manufacturer s Representatives are availab...

Отзывы: