![Super B BIB Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/super-b/bib/bib_manual_1401670007.webp)
7
Be in charge.
Super B.
monitoring and control of the battery bank using the battery monitor software can only be
done on the master port (J1).
•
Three status LED’s to indicate the status of the battery (bank).
3.2. BIB functional behaviour
3.2.1. General description
The BIB monitors all connected Li-ion batteries through the CAN bus. Whenever one or more
Li-ion batteries reports an alarm, or is missing on the bus, the BIB will disconnect the battery
(bank) from the DC bus to avoid misuse of the battery or to prevent an unsafe situation. The
alarms from the battery can differ with each battery type. Because the alarm is indicated to
the BIB as a general alarm, any Super-B battery with CANOpen communication can be used
in combination with the BIB. For alarms detected and signalled by the battery consult the
manual of the battery.
3.2.2. BIB states
The BIB different states, are listed in table 2 below.
State
Main
relay
Pre-
charge
relay
Description
ON
On
Off
Bank is connected to the DC-bus
OFF
Off
Off
Bank is disconnected from the DC-bus
Pre-charge
Off
On
Bank is pre-charging the DC-bus
Error
Off
Off
An error occurred, see below
Shutdown
Off
Off
BIB is in power down mode, see below
Undervoltage
reboot
On
Off
BIB is turned on again after an undervoltage shutdown
Table 2. BIB States
3.2.2.1 ON state
The BIB is in or can be set to the ON state when there are no active errors. In this state the
main relay is enabled, the battery bank is connected to the DC bus. The BIB can be set to ON
state using the battery monitor, or automatically when the auto-on feature is enabled. The
BIB can only reach the ON state via the pre-charge state first.