User Manual

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

REVO-II 
 

3-5KVA  INVERTER

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
                                                                                                                                           

Version: 1.1

 

Содержание REVO II 3K-48

Страница 1: ...User Manual REVO II 3 5KVA INVERTER Version 1 1...

Страница 2: ...he unit Take it to a qualified service center when service or repair is required 4 To reduce risk of electric shock disconnect all wirings before attempting any maintenance or cleaning Turning off the...

Страница 3: ...ting 5 Smart battery charger design for optimized battery performance 6 Compatible to mains voltage or generator power 7 Enegy generated load history information and fault record 8 External Wifi devic...

Страница 4: ...Product Overview 15 AC input 16 AC Output 17 PV input 18 ON OFF switch 19 DC input 20 Parallel connection terminal 21 RS232 USB terminal 22 Dry contactor...

Страница 5: ...optimal operation 6 The recommended installation position is to be adhered to the wall vertically 7 Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat diss...

Страница 6: ...lease do NOT mis connect input and output connectors WARNING All wiring must be performed by a qualified personnel It s very important for system safety and efficient operation to use appropriate cabl...

Страница 7: ...es not exceeds max PV array open circuit voltage of inverter 2 Open circuit Voltage Voc of PV modules should be higher than min battery voltage INVERTER MODEL 3 5KVA Max PV Array Open Circuit Voltage...

Страница 8: ...mply press On Off switch located on the button of the case to turn on the unit Operation and Display Panel The operation and display panel shown in below chart is on the front panel of the inverter It...

Страница 9: ...lude fault and warning code Input voltage and frequency information Output voltage and frequency information PV voltage and power information Battery voltage and current information Load power and pre...

Страница 10: ...Indicates the load Function Button Description This button for back to default display screen The setting button include language working mode input output battery AC charging MPPT parallel date time...

Страница 11: ...power to the loads only when Solar energy is not available or low level warning voltage or the setting point Battery Battery energy provides power to the loads as first priority utility energy will su...

Страница 12: ...crement of each click is 1A Parallel Single phase Include Enparallel and ID setting Three phase Include Enparallel and A B C phase setting Date Time Date and time setting This parameter can seting dat...

Страница 13: ...circuited or over temperature is detected by internal converter components 06 Output voltage is too high 07 Overload time out 08 Bus voltage is too high 09 Bus soft start failed 10 Over current or su...

Страница 14: ...ng code Warning Event 20 Fan is locked when inverter is on 21 Over temperature 22 Battery is over charged 23 Low battery 24 Overload 25 Output power derating 26 PV energy is low 27 High AC input 280VA...

Страница 15: ...y to Utility first When the unit is turned on internal relay is switched on and off repeatedly LCD display and LED sare flashing Battery is disconnected Check if battery wires are connected well Buzze...

Страница 16: ...epair center Fault code 08 09 12 14 Internal components failed Return to repair center Fault code 10 Over current or surge Restart the unit if the error happens again please return to repair center Fa...

Страница 17: ...range 120 450VDC MPPT tracker number 1 Grid tie operation Nominal output voltage 220 230 240VAC Output voltage range 184 264 5VAC Nominal output current 13A 17 4A 21 7A Power factor 0 99 Efficiency D...

Страница 18: ...iency DC AC 93 Charger Nominal DC voltage 48VDC Max solar charge current 80A Max AC charge current 60A Max charger current 80A General Parallel function Communication USB or RS232 Humidity 0 90 RH No...