background image

 

- 2 - 

 

Fixing 

1.  The metal mounting  plate supplied, should be positioned with a minimum of 70mm clearance all around to allow adequate air flow. 
2.  Fix the mounting plate directly to a flat wall using the wall plugs and screws provided. 
3.  Remove the battery insulating strip protruding from the rear of the unit. Check the unit is functioning and fit to the metal mounting 

plate on the wall 

 

Configuring

 

The unit is supplied with a 5°C minimum temperature set point  and configured as a heating thermostat as factory defaults. 
Two internal links can be used to re-configure these defaults. 
1.  Isolate the thermostat from the mains supply  before proceeding 
2.  Open the unit by slackening the retaining screw on the lower side and hinge unit upward along the top edge to separate it from the 

plastic base. Remove batteries. 

3.  Locate and identify the two option links 1 and 2. Use a pair of small wire cutters to carefully cut the appropriate links to give the 

required configuration. 

4.  Cutting link 1 will give a minimum temperature set point of 16°C (factory default is 5°C). Cut link 2 to display cooling symbol 

instead of heating symbol. 

5.  Carefully replace batteries being sure to observe the correct polarities. Re-fit to plastic base and tighten retaining screw. Check 

unit is functioning as required. 

6.  Re-connect to mains supply. 

 

Battery replacement 

This is the only maintenance required for this product and should be carried out by a competent person. 
 
A flashing ‘low batt’ symbol will appear at the bottom left of the display when the batteries start to approach the end of their life. This 
indicates that they should be replaced within the next month. Normal operation will be maintained during this period. Ultimately the 
complete display will start flashing, at which time the thermostat will switch off the heating and shut down until the batteries are 
replaced. 
 
To replace the batteries the following procedure should be carried out. The thermostat should be isolated from the mains before 
proceeding. 
 
1.  Remove the unit from the wall plate by sliding upwards and gently pulling away from the wall. Slacken the retaining screw on the 

unit and open by hinging upwards along the top of the unit. 

2.  Carefully remove batteries from the battery compartment and fit two new ‘AA’ alkaline cells taking care to observe the correct 

battery polarities. Check unit is functioning and re-fit to the plastic base by hinging downwards from the top edge. Ensure unit is 
properly closed and re-tighten screw. Check unit is functioning correctly. 

Re-mount onto the metal wall-plate and check the TLX 7506 is still in radio communication with the RF receiver. This is easily done by 
adjusting the SET POINT to switch the heating system on and off several times and checking the green indicator on the RF receiver 
goes on and off accordingly 
 
To clear any problems when fitting batteries, I.E. a blank or partial display, reset the unit by REMOVING the batteries and pressing any 
key for 10 secs. To fully discharge any residual voltage. 
 

 

Commissioning

 

This is the process of establishing communication between the Sunvic TLX 7506 (RF transmitter) and the TLX 1206 (RF receiver).  
 
The following assumes that the TLX 7506 room thermostat and the TLX 1206 RF receiver have been installed in accordance with the 
appropriate instructions. 
 
The commissioning procedure is simple and straightforward, however, should difficulties be experienced, see the ‘Hints & Tips’ section 
below. It is important to read through these instructions once before carrying out the procedure. 
 
The procedure consists of putting the TLX 7506 thermostat in a mode where it repeatedly sends a unique security install code. During 
this time, the RF receiver is put into install mode when it receives and holds this unique security code. The receiver will then respond to 
signals from that particular TLX 7506 thermostat. 
 

 
 
 
RF Receiver LED’s (indicators) 
 

Red LED 

Flashing  

-indicates receiving an RF signal 

 

Red LED 

Содержание TLX 7506

Страница 1: ...a temperature that is reasonable for the whole house If you do have TRVs you can choose a slightly higher setting to make sure that even the coldest room is comfortable then prevent any overheating in other rooms by adjusting the TRVs Room thermostats need a free flow of air to sense the temperature so they must not be covered by curtains or blocked by furniture Nearby electric fires televisions w...

Страница 2: ...ce the batteries the following procedure should be carried out The thermostat should be isolated from the mains before proceeding 1 Remove the unit from the wall plate by sliding upwards and gently pulling away from the wall Slacken the retaining screw on the unit and open by hinging upwards along the top of the unit 2 Carefully remove batteries from the battery compartment and fit two new AA alka...

Страница 3: ...s been received When this happens the RED LED will start pulsing slowly and the INSTALL button can be released The RED LED will pulse for a further 3 seconds and then go off The INSTALL code has been successfully received 4 Go to the thermostat transmitter and press any key to stop the transmission The display will stop transmitting and return to normal 5 The TLX 1206 RF receiver will now only res...

Страница 4: ...e display will revert back to actual temperature To change the SET POINT I e the temperature requested press and hold the SET button and at the same time press or to increase or decrease the temperature setting The display will continue to show the SET POINT until the SET button is released The display will then show actual temperature When the TLX 7506 instructs your heating system to switch on A...

Отзывы: