Meaning

Module undervoltage level 2 

alarm

Module charging overcurrent 

level 1 alarm

Module charging overcurrent 

level 2 alarm

Module discharge overcurrent 

level 1 alarm

Module discharge overcurrent 

level 2 alarm

Module discharge load short 

circuit (serious)

Single cell overvoltage level 2 

alarm

Single cell undervoltage level 1 

alarm

Single cell undervoltage level 2 

alarm

Module high temperature level 1 

alarm

Module high temperature level 2 

alarm

Remark

-

Rated charging 

current: 50A

Rated charging 

current: 50A

Rated discharge 

current: 50A

Rated discharge 

current: 50A

-

-

-

-

-

-

Code

E62

E71

E72

E81

E82

E83

E92

E101

E102

E111

E112

Solution

The battery is undervoltage, it is recommended to 

charge it as soon as possible.

Check whether the charging current of the charging 

device is too large.

1. Check whether the charging current of the 

charging device is too large;

2. Use a current clamp to test whether the battery 

input current is consistent with the displayed current. 

If the difference is large, the BMS current may be 

inaccurate and needs to be replaced by a professional 

or authorized person.

Check whether the load of the battery is too heavy, 

and appropriately reduce the load.

1. Check whether the load of the battery is too 

heavy, and appropriately reduce the load;

2. Use a current clamp to test whether the battery 

output current is consistent with the displayed 

current. If the difference is large, the BMS current 

may be inaccurate and needs to be replaced by a 

professional or authorized person.

1. Check whether the battery output is short-circuit-

ed;

2. Check whether the battery output load is seriously 

overloaded;

3. If E83 is still displayed after eliminating the above 

conditions, restart the BMS.

Check whether the voltage of a certain cell exceeds 

3.8V on the display screen, but the other voltages are 

normal and basically the same. It is possible that the 

battery cell is faulty and needs to be repaired.

The battery is undervoltage, it is recommended to 

charge it as soon as possible.

The battery is supplied with undervoltage. Charge it 

as soon as possible, otherwise the battery may be 

damaged.

It is recommended to appropriately reduce the charge 

and discharge current.

1. At this time, the BMS has automatically cut off the 

charging and discharging current, and automatically 

resumes charging and discharging when the 

temperature drops, appropriately reducing the 

charging and discharging current to avoid over-tem-

perature protection;

Содержание SLPO48-100

Страница 1: ...LITHIUM BATTERY PACK USER MANUAL MODEL SLPO48 100 Please read this manual before using the battery pack Please keep this manual properly after reading...

Страница 2: ...scharging 20 55 C 1month 20 45 C 3 months 10 45 C 6 months 0 25 C humidity 45 90 RH The battery should be cycled every three months After 6000 cycles at 25 C 50A charge and discharge 80 DOD recoverabl...

Страница 3: ...tonepower com 2 Structural characteristics and interface definition A Basic structure 2mm sheet metal box structure and rack B Installation method screw lock C Surface coating add spray paint 2 1 Over...

Страница 4: ...POWER switch until the red light turns on first the green light turns on but the switch shouldn t be released The system self checks when the red light is flashing about 10S After that the battery wi...

Страница 5: ...and battery pack status OK or abnormal code On the next page you can view the maximum and minimum voltage maximum and minimum tem perature of the battery User can view the voltage of each cell on pag...

Страница 6: ...rm E51 Module overvoltage level 1 alarm E52 Module overvoltage level 2 alarm E61 Module undervoltage level 1 alarm E62 Module undervoltage level 2 alarm E71 Module charging overcurrent level 1 alarm E...

Страница 7: ...ormal operation temp Tpmin Tpmax C 10 Tpmin 35 20 Tpmin 15 Tpmin 20 75 Tpmax 85 Tpmax 85 60 Tpmax 65 Tpmax 65 13 15 65 75 57 60 Code E121 E122 E111 E112 E111 E112 Temp protection recovery value C dela...

Страница 8: ...delay 5S Dry contact output Dry contact 1 action Dry contact 1 action Remark No code displayed Code Charge E71 Discharge E81 Charge E72 Discharge E82 E83 75 75 Imax 105 Imax 105 Imax 200 within 1mS 7...

Страница 9: ...nsistent with the displayed current If the difference is large the BMS current may be inaccurate and needs to be replaced by a professional or authorized person Check whether the load of the battery i...

Страница 10: ...at the charging equipment performs charging according to the voltage and current regulationsent by the BMS to ensure that the battery will not be overcharged 5 Check the connection of the battery pack...

Страница 11: ...onnect the whole system in series or parallel operation with other batteries These operations may cause personal injury or property lose If necessary please contact the relevant technical depart ment...

Отзывы: