4.2 Daily maintenance of battery pack

1. Check the voltage data on the BMS display and the actual battery voltage value to ensure the accu-
racy of the voltage collection of the BMS. If they are inconsistent, proofreading is required. The error 
between the collected voltage and the actual battery voltage does not exceed 10mV

.

2. Check the temperature collection data and actual temperature value of the BMS, and the data error 
between the collected data and the actual temperature value is not allowed to exceed 3°C, to ensure 
that the battery will not be charged or discharged when the temperature is too high or too low.
3. Check the BMS current collected data and actual current value, the error is not allowed to exceed 
1%, to ensure that the battery will not be charged or discharged by overcurrent.
4. Check the reliability of the charging equipment to ensure that the charging equipment performs 
charging according to the voltage and current regulationsent by the BMS, to ensure that the battery 
will not be overcharged

.

5. Check the connection of the battery pack is good, the contact points are in normal contact, and 
there is no accumulation of dust, powder, metal chips.

4.3 Caution

1. Children are not allowed to use the batteries.
2. It is forbidden to disassemble the battery.
3. Keep batteries or battery packs away from dangerous items or materials, such as corrosive chemi-
cals, dangerous machinery and equipment, and high-temperature environments

.

Meaning

Module high temperature level 2 

alarm

Module low temperature level 1 

alarm

Module low temperature level 2 

alarm

Remark

-

-

-

Code

E112

E121

E122

Solution

2. If E112 is displayed without charging or discharg-

ing, please restart the BMS once. If the problem 

persists, it means that the BMS is damaged and 

needs to be replaced by a professional or authorized 

person.

It is recommended to charge and discharge in a high 

temperature environment.

1. It is recommended to charge and discharge under 

a higher temperature environment;

2. If the current ambient temperature is between 

-20°C and 55°C but E122 is displayed, please restart 

the BMS once. If the problem persists, please check 

whether the internal plug is loose;

3. If the internal wiring harness plug is not loose, it 

means that the BMS is damaged and needs to be 

replaced by a professional or authorized person.

Содержание SLPO48-100

Страница 1: ...LITHIUM BATTERY PACK USER MANUAL MODEL SLPO48 100 Please read this manual before using the battery pack Please keep this manual properly after reading...

Страница 2: ...scharging 20 55 C 1month 20 45 C 3 months 10 45 C 6 months 0 25 C humidity 45 90 RH The battery should be cycled every three months After 6000 cycles at 25 C 50A charge and discharge 80 DOD recoverabl...

Страница 3: ...tonepower com 2 Structural characteristics and interface definition A Basic structure 2mm sheet metal box structure and rack B Installation method screw lock C Surface coating add spray paint 2 1 Over...

Страница 4: ...POWER switch until the red light turns on first the green light turns on but the switch shouldn t be released The system self checks when the red light is flashing about 10S After that the battery wi...

Страница 5: ...and battery pack status OK or abnormal code On the next page you can view the maximum and minimum voltage maximum and minimum tem perature of the battery User can view the voltage of each cell on pag...

Страница 6: ...rm E51 Module overvoltage level 1 alarm E52 Module overvoltage level 2 alarm E61 Module undervoltage level 1 alarm E62 Module undervoltage level 2 alarm E71 Module charging overcurrent level 1 alarm E...

Страница 7: ...ormal operation temp Tpmin Tpmax C 10 Tpmin 35 20 Tpmin 15 Tpmin 20 75 Tpmax 85 Tpmax 85 60 Tpmax 65 Tpmax 65 13 15 65 75 57 60 Code E121 E122 E111 E112 E111 E112 Temp protection recovery value C dela...

Страница 8: ...delay 5S Dry contact output Dry contact 1 action Dry contact 1 action Remark No code displayed Code Charge E71 Discharge E81 Charge E72 Discharge E82 E83 75 75 Imax 105 Imax 105 Imax 200 within 1mS 7...

Страница 9: ...nsistent with the displayed current If the difference is large the BMS current may be inaccurate and needs to be replaced by a professional or authorized person Check whether the load of the battery i...

Страница 10: ...at the charging equipment performs charging according to the voltage and current regulationsent by the BMS to ensure that the battery will not be overcharged 5 Check the connection of the battery pack...

Страница 11: ...onnect the whole system in series or parallel operation with other batteries These operations may cause personal injury or property lose If necessary please contact the relevant technical depart ment...

Отзывы: