0x1007

ENUM8
reportable

ModeAfterDry

The mode after Dry Mode:
Value=0 : OFF
Value=1 : Manual mode
Value=2 : Auto mode –schedule (default)
Value=3 : Away mode

0x1224

0x1008

ENUM8
reportable

TemperatureDisplay : 

Value=0 : Room Temp (Default)
Value=1 : Floor Temp

0x1224

0x1009

INT8U
reportable

WindowOpenCheck

The threshold to detect open window, range is 0.3-8, unit is 
0.5ºC,
0 means disabled, default is 0

0x1224

0x100A

INT8U
reportable

Hysterersis

Hysterersis setting, range is 5-50, unit is 0.1ºC, default value 
is 5

0x1224

0x2001

INT8U,
reportable

Max floor temp

Floor temperature over heating threshold, range is 0-35, unit 
is 1ºC, 0 means this function is disabled, default value is 27.

0x1224

5.2.5 Simple Meter-0x0702 (Server)

Attributes supported:

0x0000

bitmap32 ,
read-only

MeasurementType 

Indicates the physical entities that this devices is able to measure. Supports 
only bit0: Active measurement (AC) 

0x0505

int16U ,
read-only,
reportable 

RMSVoltage

Single phase valid voltage, unit is V

0x0508

int16U ,
reportable,
read-only

RMSCurrent

Single phase valid current, unit is A

0x050B

int16S ,
reportable
read-only

ActivePower 

Single phase valid power, unit is W

0x0600

int16U,
read-only

ACVoltageMultiplier

0x0601

int16U,
read-only

ACVoltageDivisor

Used together with above attributes, the real displayed voltage = 
RMSVoltage* ACVoltageMultiplier
/ ACVoltageDivisor

0x1006

INT8U
reportable 

DryTime

The duration of Dry Mode, range is 5-100, unit is min.
Default value is 5.

0x1224

0x1005

INT8S,
reportable

FloorSenserCalibration

The temp compensation for the external (floor) sensor, range 
is -30-30, unit is 0.1°C. default value 0

0x1224

0x1004

ENUM8
reportable 

PowerUpStatus

The mode after reset power of the device:
Value=0 : default mode
Value=1 : last status before power off (Default)

0x1224

0x100B

ENUM8
reportable

DisplayAutoOffEnable

0, disable Display Auto Off function
1, enable Display Auto Off function

0x1224

5.2.6 Electrical Measurement-0x0b04(Server)

Attributes supported:

Attribute

Type

Description

0x0306

bitmap8,
read-only

MeteringDeviceType

Metering data type, this is always Electric Metering (0x00)

0x0302

Int24U,
read-only

Divisor

0x0303

map8 ,
read-only

SummationFormatting

The decimal point on the left and right sides of the data, this is always  0x00

ENUM8
reportable 

ControlType

The referring sensor for heat control:
Value=0 : Room sensor(Default)
Value=1 : floor sensor
Value=2 : Room+floor sensor 

0x1002

ENUM8
reportable 

FloorSenserType

Select external (Floor) sensor type:
Value=5 : NTC 12K/25
Value=4 : NTC 100K/25
Value=3 : NTC 50K/25 
Value=2 : NTC 15K/25 
Value=1 : NTC 10K/25 (Default)

0x1224

0x1003

0x1224

0x0301

Int24U,
read-only

Multiplier

0x0000

unsigned48 ,
read-only,
reportable 

CurrentSummationDelivered 

Indicates the current amount of electrical energy delivered to the load.

0x0200

bitmap8 ,
read-only

Status

Flags indicating current device status,  always is 0x00

0x0300

enum8 ,
read-only

UnitOfMeasure

The unit of metering data, this is always kWh(0x00)

Attribute

Type

Description

ButtonVibrationLevel

Key beep volume & vibration level:
Value=0 : off(default)
Value=1 : Low Level
Value=2 : High Level

0x1000

ENUM8,
reportable 

OperateDisplayLcdBrightnesss

OLED brightness when operate the buttons:
Value=0 : Low Level
Value=1 : Mid  Level(default)
Value=2 : High Level

0x1224

0x1001

ENUM8
reportable 

0x1224

Command supported:

Command

Description

0x0000

Setpoint Raise/Lower

Increase or decrease the set temperature according to current mode, unit is 
0.1ºC

0x2002

ENUM8
reportable

Away Mode Set:

Value=0: not away (default)
Value=1: away

0x1224

Содержание SR-ZG9092A

Страница 1: ...C RF EN IEC 61000 3 2 2019 EN 61000 3 3 2013 A1 2019 EN 60730 1 2016 A1 2019 EN 60730 2 19 2019 A1 2019 A2 2020 EN 50663 2017 ETSI EN 301 489 1V2 2 3 ETSI EN301 489 3V2 1 1 ETSI EN300 220 1 v3 1 1 ETS...

Страница 2: ...Warnings 4 Basic Function Introduction 4 1 Switch Operation modes Short press button on Home interface to switch operation modes the icons of Away Manual Comfort Automatic Energy Save Drying OFF modes...

Страница 3: ...lsius the step value is 1 if the unit is degree Fahrenheit the step value is 1 approximately equal to 2 7 30 24 12 00 20 18 00 16 22 30 18 Saturday Sunday 7 30 24 12 00 20 18 00 18 22 30 18 After the...

Страница 4: ...tatus 0x1004 of Thermostat Cluster 0x0201 Display Temp type Home Temp by default This parameter defines which sensor temperature will be displayed on Home page Floor Temp floor temperature external se...

Страница 5: ...x0002 of Thermostat 0x0201 is 1 3 The proprietary attribute 0x2002 Manufacturer Code 0x1224 of the cluster 0x0201 can be modified to configure whether it is away mode or at home Note Away Mode uses at...

Страница 6: ...0 Heat State Proprietary Attributes Attribute Type Description Manufacturer code 0x0003 bool read only SceneValid If true the scene identified by CurrentGroup and CurrentScene is currently active i e...

Страница 7: ...de after reset power of the device Value 0 default mode Value 1 last status before power off Default 0x1224 0x100B ENUM8 reportable DisplayAutoOffEnable 0 disable Display Auto Off function 1 enable Di...

Страница 8: ...Mask of Electrical Measurement The Alarm Server cluster can generate the following commands 0x0802 int16S reportable read only ACCurrentOverload Alarms when the current is over a certain value 0 10 16...

Страница 9: ...t temperature when energy save mode is selected The temperature schedule of auto mode energy save mode is not configured correctly 3 Current temperature is not executed when away mode is selected Chec...

Отзывы: