4.7 MONITOR SET

The function of monitor set is real time monitor of over current, over heat and freezing, on Home interface, short 

press          MONITOR SET to enter into monitor set interface as follows: 

For configuration method and modification, please refer to Automatic Mode 

(Energy Save Mode) Schedule:

4.6 Dry Mode Schedule

For example, in order to quickly dry the water on the floor of the bathroom, the device can be set to quickly heat 

in a short time to dry the floor. Enter the configuration interface as follows:

Duration: set how long the dry mode lasts, can be configured through the proprietary attribute DryTime 

(0x1006) of Thermostat Cluster (0x0201), the configurable range is 5-100 minutes.  

After Mode: set the mode after the drying mode ends, can be configured through the proprietary attribute 

ModeAfterDry (0x1007) of Thermostat Cluster (0x0201).

Remain: shows the remaining time of the drying mode

To enter into the setting interface and setting method, please refer to the 1.4 

Auto Mode (Energy Save Mode) Schedule.

D means date, M means month, Y means year (2019-2099).

Start and end mean away time.

4.5 Away Mode Schedule

User can set time to leave home and time to go home according to the requirements of themselves, and set how 

the device will control the temperature during this period.

1.If away mode has already been activated, the end time for away mode is valid, the device will execute Away 

Mode Temperature Schedule before the end time.

2.If away mode has already been activated, the values of end time for away mode are set as 0, the device will 

always execute current set temperature with no time limitation. The device will consider the mode as anti-

freeze mode, the recommended temperature setting is 4-10

℃, 

and

 

factory

 

default

 

setting

 

is

 

6

℃.

Max floor temp (27°C by default)

This function is similar to the function of “Internal Over Heat Protection” 

described in chapter 4.9. When the control type is configured as “Room+Floor 

sensor”, this function will be valid:

The alarm will be triggered when the floor sensor temperature > Max floor temp,  

the relay will be forced to off by the device, and the state will be reported to the 

gateway. The following indication figure will prompt on the display.

Max Current (16A by default)

If current is over the set value, the relay will be forced to off by the device, and the state will be reported to the 

gateway. The over current alarm function can be disabled, which can be set directly through the device. Or can 

be configured through the ACAlarmsMask and ACCurrentOverload of Electrical Measurement (0X0B04), for 

details please refer to the configuration value. 

Note: When over current alarm is triggered, the beeper will beep, to cancel the alarm, just press and 

hold button  

     

 for over 3 seconds or reset power of the device. After cancel manually, the relay will 

show heating forbidden icon 

     

  within 120 seconds, but other operations are allowed.

Short press button

      

to select the item would like to modify, then short press 

move up and move down buttons                to modify value of selected item, then 

short press button

  

   to save and quit, short pressing button  

    

only quits 

without saving.

F

When

 

set

 

temperature

 

using

 

buttons

if

 

the

 

unit

 

is

 

degree

 

Celsius, the step value is 1

, if the unit is degree 

Fahrenheit, the step value is 1

℃ (

approximately equal to 2

).

7:30,24

  ~ 12:00,20

℃  

18:00,16

 ~  22:30,18

  

Saturday~Sunday

7:30,24

  ~  12:00,20

  

18:00,18

 ~  22:30,18

After the floor sensor temperature < (Max floor temp - Hysteresis), the alarm will be cancelled automatically 

and the device will restore to previous operation mode.

To cancel the alarm manually,  just press and hold button  

     

 for over 3 seconds, but the relay will show 

heating forbidden icon 

     

  within 120 seconds and the alarm will not be triggered again, after 120 seconds 

expire, the device will restore to previous operation mode and continue to detect alarm temperature.

This function can be disabled, which can be configured directly through the device,

 

or can be configured 

through the attribute Max floor temp (0x2001) of Thermostat Cluster (0x0201), when this value is set as 0, this 

function is disabled.

Hysterersis (0.5°C by default)

To prevent the undulation of sensor temperature when the sensor temperature is 

approaching the set

 

temperature, which will cause that the controller may keep 

switching on/off the relay. Here hysterersis enables the controller to control the 

relay only when the sensor temperature is lower than the set temperature minus 

the hysteresis value , this value can be set. 

For instance, when hysterersis is set as 0.5 degree, then only when current 

sensor temperature < (the set temperature - 0.5 degree), will the controller heat.

This value can also be configured through the proprietary attribute Hysterersis 

(0x100A) of Thermostat Cluster (0x0201).

When

 

set

 

temperature

 

using

 

buttons

if

 

the

 

unit

 

is

 

degree

 

Celsius, the step value 

is 0.5

, if the unit is degree Fahrenheit, the step value is 0.5

℃ (

approximately 

equal to 1

).

Window Open Detect (disabled by default)

Once the device is powered on and stable, referring to the room temperature sensor, if the temperature 

decreases to the threshold of this setting, the window open mark will be enabled, the relay will be forced to turn 

off to save energy, then the icon        will appear.

After window open mark is enabled, if the temperature increases to the threshold of this setting in 3 minutes, 

the window open mark will be disabled.

Once the window open mark is enabled, it will be disabled after 10 minutes, and the device will keep current 

working mode.

This value can also be configured through the proprietary attribute WindowOpenCheck (0x1009) of Thermostat 

Cluster (0x0201), 0 means this function is disabled.

Note: this function will work better when the device is installed beside the window or door.

When set temperature using buttons: if the unit is degree Celsius, the step value is 0.5

, if the unit is degree 

Fahrenheit, the step value is 0.5

 (approximately equal to 1

).

Short press button 

    

  to select the item would like to modify, then short 

press move up and move down buttons     

     

to modify value of selected 

item, then short press button  

    

 to save and quit, short pressing button 

   

  

only quits without saving.

F

4.8 TIME/DATE SET

Select TIME/DATE on Home Interface to enter into TIME/DATE SET interface as follow:

The device Time Cluster is client, if the bound device supports local time of Time Cluster, the device will 
acquire local time from the bound device spontaneously under 3 situations: acquire after this device is added 
to a network, acquire when the device already added to a network and power is reset, acquire every 24 hours .

Содержание SR-ZG9092A

Страница 1: ...C RF EN IEC 61000 3 2 2019 EN 61000 3 3 2013 A1 2019 EN 60730 1 2016 A1 2019 EN 60730 2 19 2019 A1 2019 A2 2020 EN 50663 2017 ETSI EN 301 489 1V2 2 3 ETSI EN301 489 3V2 1 1 ETSI EN300 220 1 v3 1 1 ETS...

Страница 2: ...Warnings 4 Basic Function Introduction 4 1 Switch Operation modes Short press button on Home interface to switch operation modes the icons of Away Manual Comfort Automatic Energy Save Drying OFF modes...

Страница 3: ...lsius the step value is 1 if the unit is degree Fahrenheit the step value is 1 approximately equal to 2 7 30 24 12 00 20 18 00 16 22 30 18 Saturday Sunday 7 30 24 12 00 20 18 00 18 22 30 18 After the...

Страница 4: ...tatus 0x1004 of Thermostat Cluster 0x0201 Display Temp type Home Temp by default This parameter defines which sensor temperature will be displayed on Home page Floor Temp floor temperature external se...

Страница 5: ...x0002 of Thermostat 0x0201 is 1 3 The proprietary attribute 0x2002 Manufacturer Code 0x1224 of the cluster 0x0201 can be modified to configure whether it is away mode or at home Note Away Mode uses at...

Страница 6: ...0 Heat State Proprietary Attributes Attribute Type Description Manufacturer code 0x0003 bool read only SceneValid If true the scene identified by CurrentGroup and CurrentScene is currently active i e...

Страница 7: ...de after reset power of the device Value 0 default mode Value 1 last status before power off Default 0x1224 0x100B ENUM8 reportable DisplayAutoOffEnable 0 disable Display Auto Off function 1 enable Di...

Страница 8: ...Mask of Electrical Measurement The Alarm Server cluster can generate the following commands 0x0802 int16S reportable read only ACCurrentOverload Alarms when the current is over a certain value 0 10 16...

Страница 9: ...t temperature when energy save mode is selected The temperature schedule of auto mode energy save mode is not configured correctly 3 Current temperature is not executed when away mode is selected Chec...

Отзывы: