All In One Heat Pump For Domestic Hot Water
- 32 -
Pilot run of heat pump
Please confirm the followings before pilot run of heat pump
1. The heat pump has been finished well;
2. Assemble pipe and wire are all correct;
3. Drain water is smooth;
4. Insulation materials are complete;
5. Ground wire is installed well;
6. Power voltage is equivalent to rated voltage of heat pump;
7. Inlet and outlet air port have no obstacle;
8. Air attached to water pipe is drained out,and all valve have been opened;
9. Leakage protection device works well;
10. Input water pressure is less than 0.15Mpa;
Maintenance and Solution
I. Maintenance
1. Frequently check power plug and sockets and make sure both of them have been
connected well and reliably, and have no over-heating effect;
2. When not used for a long time, especially where temperature is below 0
℃
,
water
filled in the water tank must be drained out to prevent from damaging inner tank;
(operation shown the above contents)
3. To make heat pump to keep a long-term and high efficiency working state, we
suggest you should clean inner tank up every half a year to remove accumulated
sediment, please obey the following rules to clean inner tank:
(1). Turn off power supply of heat pump;
(2). Turn off cold water inlet valve, and open up hot water tap water;
(3) Connect drainage water with drain outlet through a soft pipe;(temperature resist of
drainage pip is less than 93
℃
,
if drainage pipe do not meet demands, please turn on cold
water inlet valve, and turn on hot water tap water until water is not hot);
(4). Turn on drainage water port of heat pump, clean water tank attached to inner tank up, if
needed, you will wash inner tank for many times to clear sediment;
(5). Turn off drainage water port, re-fill water into inner tank and recover power supply;
4. Each device has been matched with one anode rod, and anode rod will be slowly