background image

3.1   Location 

 
As  the  majority  of  system  installations  vary  greatly,  only  general  comments  can  be  made  as  to  location.  
Prior to installing the system, it is suggested to make a system layout plan.  During the system layout, take 
into  consideration  any  potential  shading  of  the  solar  electric  modules,  wire  runs,  wire  size,  conduit  runs, 
trenching, controller accessibility, tank location, pump head etc. Shading even a small portion of the array 
can reduce the output of the entire array and thus reduce or completely stop the output of the pump. There 
is no substitute for a good plan! 
 
The  PCC-series  controller  can  either  be  mounted  indoors  or  outdoors.    Locate  all  system  equipment  as 
close as possible to each other. For top of pole mount racks, the controller is usually mounted on the north 
side (shaded side) of the mounting pole. The controller must be mounted in a vertical position for proper 
cooling and to keep the electronics dry. The controller should be located close to the pump if possible.  This 
general physical layout is conducive to clean installation both aesthetically and electrically. 
 

3.2

 

System Design Basics  

(Read carefully before installation)

 

 
 

1.

 

The  pump  discharge  piping  should  be  sized  for  efficient  pump  operation.  Pipe  size  being  too 
small will create greater friction losses which require more power to operate and thus a higher 
solar module cost.    
 

2.

 

Make sure the pool filter is size correctly for the flow rate of the pump. A filter sized too small 
will create higher friction losses and will increase the power requirements and thus the cost of 
the system.  

 

3.

 

For optimum pump performance make sure that the wire is sized properly for the length of run 
between the pump and the solar modules as specified by the National Electric Code.  Wire sized 
too  small  will  cause  a  decreased  output  from  the  pump.    Keep  the  distance  from  the  solar 
modules to the pump as short as possible. Refer to a DC wire loss chart for proper sizing. It is 
recommended  to  keep  the  voltage  drop  under  3%.  Refer  to  the  wire  sizing  guide  on  the 
SunPumps web site under Engineering.  

 

4.

 

Never install the controller in direct sunlight. Direct sunlight on the controller may cause over-
heating of the controller.   

 

5.

 

 Never  lay  the  controller  on  the  ground  or  mount  the  controller  in  a  horizontal  position. 

The 

controller  should  be  mounted  in  a  vertical  position  only.

  A  convenient  place  to  mount  the 

controller is on the north side (shaded side) of the solar module array.   

 

6.

 

The controller should be grounded to the pump motor housing, the frame of the solar modules 
and to an 8-foot ground rod. Use only a copper lug to attach the ground rod. Always use a DC 
surge/lightning  arrestor  on  the  panel  side  of  the  controller.  (Midnight  Solar  MN-SPD  surge 
arrestor is recommended)  

 

7.

 

Do not ground the array positive or negative electrical wires.   

 

 

3.3   Pump Installation         

 

 
1.

 

The pump should be located next to the pool filter. It is highly recommend that you install unions on 

both the suction and the discharge ports for easy pump removal for future service.  

 

2.

 

Write the pump, motor and controller model number and serial number in the space provided on the 

last page in this Instruction Manual. This information will be needed when filling out the Warranty Card.  
And will aide in any troubleshooting which may be necessary. 

 
3.

 

Inspect  all  components  for  shipping  damage  and  insure  that  you  have  all  the  components  that  are 

required for a complete installation. 

 
4.

 

Select  a  well-ventilated,  shaded  location  in  which  to  vertically  mount  the  controller.  Mount  the 

controller far enough from the pool where it could not get wet.   

 

Содержание SCP series

Страница 1: ......

Страница 2: ...ring 3 5 Figure 2 Control Panel Figure 3 Dip Switch Settings Controller Settings 3 6 Auxiliary Control Circuits 3 7 Remote Switch Output Power Limit Circuit Low Power Shut Down Circuit Low Water Shut...

Страница 3: ...es controller or product damage and or personal injury may result Do not exceed the voltage rating of the controller Do not splash water on the controller especially when the cover is open Mount the c...

Страница 4: ...rless DC motors No other applications or DC power sources are recommended or warranted unless written approval is provided by the SunPumps factory 3 0 Installation and Operation The following sections...

Страница 5: ...he solar modules as specified by the National Electric Code Wire sized too small will cause a decreased output from the pump Keep the distance from the solar modules to the pump as short as possible R...

Страница 6: ...valves are open and strainer pot temperature is cool to the touch then with extreme caution you can open the strainer lid Do not open the strainer pot lid while the pump in in operation Strainer Clea...

Страница 7: ...ble or call your SunPumps dealer for assistance Wire gauge being too small will cause excessive voltage losses to the motor and will reduce the flow rate of the pump All other system equipment should...

Страница 8: ...Figure 2 Controller Wiring Diagram...

Страница 9: ...9 Connect the DC source supply positive the red conductor to one of the controller terminals labeled Positive on the Solar Array Input NOTE The power should be connected to a disconnect and it should...

Страница 10: ...ic Turns pump off when terminals connect OFF 2 ON Low Water Cutoff Logic Turns pump on when terminals connect OFF 3 ON 10 Minute Delay Increases turn on delay to 10 minutes OFF 4 ON 30 Minute Delay In...

Страница 11: ...tor speed control is for adjusting the flow rate of the pump There is also the low water cutoff low power shut down and over current protection circuits See each corresponding detailed description bel...

Страница 12: ...troller program This timeout applies to remote switch and low water cutoff Low Power Shut Down Sensorless Low Water Cut Off Circuit LPLW The Low Power Shut Down Low Water Cut Off Circuit LPLW turns th...

Страница 13: ...atch the flow rate of the pump to the production of the well 1 With the system installed and controller properly configured allow the pump to run at full power at mid day until the pump starts surging...

Страница 14: ...lay Screens NOTE Dip switch 7 will freeze the display on the current screen If the system is powered up with switch 7 on the display will only show the SUNPUMPS INC screen Turn off switch 7 to unfreez...

Страница 15: ...ote circuit or low water cutoff circuit is preventing the controller from running the pump Set the 1 and 2 dip switches to off and disconnect the remote switch and low water cutoff If the pump starts...

Страница 16: ...complete series string PUMP IS RUNNING BUT THE OUTPUT IS LOW 1 Make sure you have full sun light at midday that there are no clouds and no shadows on any part of the array Then verify power coming ou...

Страница 17: ...heet is a must Pump Model Number ____________________ Pump Serial Number ____________________ Motor Serial Number ____________________ Controller Model Number ____________________ Software Version ___...

Страница 18: ...s or other loss or injury resulting from the use of a SunPumps product The purchaser s exclusive remedy shall be only as stated herein This warranty is in lieu of all other warranties expressed or imp...

Отзывы: