3.6 

Controller Settings 

 
The PCC series controllers have several settings (see figure 3).  Most features include system configuration 
adjustments, some of which are user selectable by an eight position DIP-switch located on the face of the 
controller.   
 
Switch 1 is the Remote Switch Logic. With this switch off (down), terminals “RS+” and “GND” must be 
connected  to  turn  the  controller  off.  With  this  switch  on  (up),  terminals  “RS+”  and  “GND”  must  be 
connected to turn the controller on.   
 
Switch 2 is the Low Water Cutoff Logic. With this switch off (down), terminals “RS+” and “GND” must 
be  connected  to  turn  the  controller  off.  With  this  switch  on  (up),  terminals  “RS+”  and  “GND”  must  be 
connected to turn the controller on. 
 
Switches 3 and 4 are delay timer adjustments.  The delay timer is used for the remote switch and the low 
water cutoff.  This timer by default is set for a 3 minutes.  Switch 3 will increase the timer to 10 minutes; 
Switch 4 will increase it to 30 minutes.  See Remote Switch and Low Water Cutoff for more information. 
   
Switch  7  is  used  to  control  the  user  interface.    When  switch  7  is  down,  the  LCD  will  display  various 
screens conveying pump and controller operating parameters.  The display will cycle through each screen 
at  a  predetermined  rate.    For  troubleshooting  and  some  setup  features  certain  screens  are  desired.    By 
turning the switch number 7 on, the display will stop cycling and the current screen will stay on the display.   
 
Switches 5, 6, and 8 are not used at this time and should remain down. 

 
3.7   Auxiliary Control Circuits 

 
The  auxiliary control circuits are  configured and controlled  with the  “Dip Switches”,  “LP  Adj.”, “Speed 
Control” and the “RS”, “LW” and “GND” terminals.  (See Figure 3)   
 
These  circuits  offer  expanded  capability  and  are  described  here.    The  remote  switch  control  is  for  float 
switches (storage tank level), pressure  switches or a remote system “ON/OFF” toggle switch. The  motor 
speed control is for adjusting the flow rate of the pump.  There is also the low water cutoff, low power shut 
down and over current protection circuits.  See each corresponding detailed description below. 
 
NOTE:   

Use only “Shielded Wire” to run from the remote  switch to the controller and the ground 

wire must be grounded to the controller side only. 

Induced voltages from lightning storms or two-way 

radio transmissions could damage the controller.   
 

Over-Current Shut Down Circuit

 

 
The over-current shut down circuit will turn the controller off any time the current exceeds the current limit 
of the controller. When it turns the controller off it  will remain off  for 3 minutes and then turn on again. 
When it turns off an error light will light and the display will say Over-Current. When it turns on again, if it 
is still pulling excessive current it will continue to shut down for 3 minutes and try to restart.  

 
Sensor Low Water Cutoff Circuit 

 
The sensor type low water cutoff circuit is designed as a safety feature to protect your pump from running 
dry or your tank from over flowing.  This feature is designed for use in the submersible SCS systems with 
the ground wire installed.  For use with the SCB or SCP systems contact SunPumps for assistance.  The 
“LW” terminal of the controller should be attached to a low water sensor electrode which is mounted in 
your tank or well.  The system can be used to detect low water or to detect high water depending on the 
position of switch 2 on the dip switch.  When dip switch 2 is in the off position, the low water cutoff circuit 
expects not to touch water.  If water comes into contact with it, and completes the circuit to ground, the 
pump will shut off until the water is removed and the delay timer times out.  A one minute minimum 
timeout is default for this feature but is modifiable by switches 3 and 4 to 10 or 30 minutes respectively.   
At certain times the controller will be off for up to 14 minutes depending on various factors in the 
controller program.  This timeout applies to remote switch and low water cutoff. 
 

Содержание SCP series

Страница 1: ......

Страница 2: ...ring 3 5 Figure 2 Control Panel Figure 3 Dip Switch Settings Controller Settings 3 6 Auxiliary Control Circuits 3 7 Remote Switch Output Power Limit Circuit Low Power Shut Down Circuit Low Water Shut...

Страница 3: ...es controller or product damage and or personal injury may result Do not exceed the voltage rating of the controller Do not splash water on the controller especially when the cover is open Mount the c...

Страница 4: ...rless DC motors No other applications or DC power sources are recommended or warranted unless written approval is provided by the SunPumps factory 3 0 Installation and Operation The following sections...

Страница 5: ...he solar modules as specified by the National Electric Code Wire sized too small will cause a decreased output from the pump Keep the distance from the solar modules to the pump as short as possible R...

Страница 6: ...valves are open and strainer pot temperature is cool to the touch then with extreme caution you can open the strainer lid Do not open the strainer pot lid while the pump in in operation Strainer Clea...

Страница 7: ...ble or call your SunPumps dealer for assistance Wire gauge being too small will cause excessive voltage losses to the motor and will reduce the flow rate of the pump All other system equipment should...

Страница 8: ...Figure 2 Controller Wiring Diagram...

Страница 9: ...9 Connect the DC source supply positive the red conductor to one of the controller terminals labeled Positive on the Solar Array Input NOTE The power should be connected to a disconnect and it should...

Страница 10: ...ic Turns pump off when terminals connect OFF 2 ON Low Water Cutoff Logic Turns pump on when terminals connect OFF 3 ON 10 Minute Delay Increases turn on delay to 10 minutes OFF 4 ON 30 Minute Delay In...

Страница 11: ...tor speed control is for adjusting the flow rate of the pump There is also the low water cutoff low power shut down and over current protection circuits See each corresponding detailed description bel...

Страница 12: ...troller program This timeout applies to remote switch and low water cutoff Low Power Shut Down Sensorless Low Water Cut Off Circuit LPLW The Low Power Shut Down Low Water Cut Off Circuit LPLW turns th...

Страница 13: ...atch the flow rate of the pump to the production of the well 1 With the system installed and controller properly configured allow the pump to run at full power at mid day until the pump starts surging...

Страница 14: ...lay Screens NOTE Dip switch 7 will freeze the display on the current screen If the system is powered up with switch 7 on the display will only show the SUNPUMPS INC screen Turn off switch 7 to unfreez...

Страница 15: ...ote circuit or low water cutoff circuit is preventing the controller from running the pump Set the 1 and 2 dip switches to off and disconnect the remote switch and low water cutoff If the pump starts...

Страница 16: ...complete series string PUMP IS RUNNING BUT THE OUTPUT IS LOW 1 Make sure you have full sun light at midday that there are no clouds and no shadows on any part of the array Then verify power coming ou...

Страница 17: ...heet is a must Pump Model Number ____________________ Pump Serial Number ____________________ Motor Serial Number ____________________ Controller Model Number ____________________ Software Version ___...

Страница 18: ...s or other loss or injury resulting from the use of a SunPumps product The purchaser s exclusive remedy shall be only as stated herein This warranty is in lieu of all other warranties expressed or imp...