4
CAT-5e or aboove cable is recommended.
W
Wiirriin
ng
g M
Me
etth
ho
od
d
Use CAT-5e or aboove cable with one end connected to external device and the other
end connected to the UMCG's“NET2”port.
3.2
RS485 Port Wiring
IIn
nttrro
od
du
uc
cttiio
on
n
The UMCG supports 8-way RS485 terminal connection to equipment such as box
transformer measurement and control equipment, electricity meter, PV combiner box
and environmental monitor.
P
Po
orrtt m
ma
arrkk
F
Fu
un
nc
cttiio
on
n
An
RS485A, RS485 differential
Bn
RS485B, RS485 differential signal-
* n=1~3 or 5~9。
C
Ca
ab
blle
e R
Re
eq
qu
uiirre
em
me
en
nttss
•
0.75mm
2
~1.5mm
2
twisted pair shielded wire is recommended for connection.
•
The RS485 communication distance is less than 1200m.
•
A single RS485 communication port can support the access of 32 devices.
•
A single RS485 communication port does not allow different types of equipment to
be connected.
W
Wiirriin
ng
g M
Me
etth
ho
od
d
step 1
Lead the RS485 cable outgoing from external equipment to the wiring area of the
UMCG.
step 2
Use wire strippers to strip the protective layer and shielded layer of the cable to expose
the copper core of the wire.
step 3
Connect the cable of which the insulation layer has been stripped to the either the
UMCG's“A1B1~A3B3”or“A5B5~A9B9”port as shown in the following figure.
User Manual