7
step 3
Connect cables outing from NO, NC and COMs to the corresponding ports of the UMCG.
-- -- E
En
nd
d
3.5
PT100 Port Wiring
IIn
nttrro
od
du
uc
cttiio
on
n
The UMCG has two PT100 sampling ports, which are used for transformer oil
temperature sampling and copper busbar temperature sampling respectively.
W
Wiirriin
ng
g R
Re
eq
qu
uiirre
em
me
en
nttss
Recommended cable specifications:0.75mm
2
~1.5mm
2
.
W
Wiirriin
ng
g M
Me
etth
ho
od
d
step 1
Lead the sampling signal line to the wiring area of the UMCG.
step 2
When connecting a two-wire cable, connect the PT + cable to the "PT +" port; connect
the PT- cable to the "PT-" port. (N
No
otte
e: "PT-" port and "GND" port are short-circuited)
When connecting a three-wire cable, PT + cable connects to "PT +" port; PT- cable
connects to "PT-" port; ground cable Connect to the "GND" port.