74
Parameter
Definition/Setting
Description
Range
QP_P3
Output power at P3 on the Q
(P) mode curve (in
percentage)
20.0%~100.0%
QP_K1
Power factor at P1 on the Q(P)
mode curve
Curve A/Curve
C:0.800~1.000
Curve B: [-0.600~0.600]*Ac-
tive Overload Rate/1000
QP_K2
Power factor at P2 on the Q(P)
mode curve
Curve A/Curve C:
0.800~1.000
Curve B: [-0.600~0.600]*Ac-
tive Overload Rate/1000
QP_K3
Power factor at P3 on the Q(P)
mode curve
Curve A/Curve C:
0.800~1.000
Curve B: [-0.600~0.600]*Ac-
tive Overload Rate/1000
QP_EnterVoltage
Voltage percentage for Q(P)
function activation
100.0%~110.0%
QP_ExitVoltage
Voltage percentage for Q(P)
function deactivation
90.0%~100.0%
QP_EXitPower
Power percentage for Q(P)
function deactivation
1.0%-20.0%
QP_EnableMode
Unconditional activation/deac-
tivation of Q(P) function
Yes/No
Q(U)Curve
Select the corresponding
curve according to local
regulations
Curve A/Curve B/Curve C*
QU_V1
Pre-set grid voltage U1 that is
reactive according to the grid
voltage
80.0%~100.0%
QU_Q1
Pre-set proportion of reactive
power according to the grid
voltage U1
[-60.0%-0]* Overload Rate/
1000