97
Parameters
SG40CX
SG50CX
(1)
SG50CX
(2)
Arc fault circuit interrupter
(AFCI)
Opt.
/
Opt.
Surge protection
DC Type II (Type
I + II Opt.) / AC
Type II
DC Type II / AC
Type II
DC Type II (Type I +
II Opt.) / AC Type II
General Data
Dimensions (W*H*D)
782×645×310mm
Weight
58kg
62kg
62kg
Topology
Transformerless
Degree of protection
IP66
Night power consumption
≤2 W
Operating ambient tempera-
ture range
-30 to 60
℃
(> 45
℃
derating)
Allowable relative humidity
range
0 - 100%
Cooling method
Smart forced air cooling
Max. operating altitude
4000 m (> 3000 m derating)
Display
LED, Blu App
Communication
RS485 / Option-
al: WLAN,
Ethernet
RS485 / WLAN
/ Optional:
Ethernet
RS485 / Optional:
WLAN, Ethernet
DC connection type
MC4 (Max. 6 mm
2
)
AC connection type
OT or DT terminal (Max.70 mm
2
)
Grid Support
Q at night function, LVRT, HVRT, active & reactive power
control and power ramp rate control
Country of manufacture
/
China
/
(1) For Countries “AU” and “NZ”.
(2) For other countries.
(3) The inverter enters the standby state when the input voltage ranges between 1000V and
1100V.
Parameters
SG30CX-NI
SG50CX-NI
Input (DC)
Recommended max. PV in-
put power
45kW
76kW
Max. PV input voltage
1100V
(1)
Min. PV input voltage /
Start-up input voltage
200V / 250V