User Manual
49
7.5.8 GND Detection
Touch ENT / ESC
to select and
press ENT
to
confirm.
Select
ON
to enable the GND Detection. If the
enclosure of the inverter is not grounded, the error
code 106 will be shown on the main screen. The
buzzer inside will sound at the same time.
OFF
ON
7.5.9 Energy Adjustment
If the accumulative value “E-total” displayed on inverter screen is different from
the value indicated on the metering device, you should adjust the energy
deviation.
(Energy Adj. value) = (Real measured value) - (E-total reading value)
Touch ESC
to add the value and
Touch ENT
to
move the cursor.
Press ENT
to confirm the setting.
The “+” can be changed to “-” by
touching ESC
.
The adjustment rangs from -9999 kWh to +9999
kWh.
+0000 kWh
7.5.10 Setting Communication Parameter
Touch ESC
to set the appropriate value and
touch ENT
to move the cursor. Confirm
settings by
pressing ENT
.
Device address range: 1-247.
Modbus ID: 031
7.5.11 Ethernet Configuration
The Ethernet setting is reserved for later usage.
Touch ENT
to select and
press ENT
to confirm.
OFF:
The IP address should be assigned manually.
ON:
Automatically assign IP address from the home
router.
Touch ESC
to switch between the DHCP and the IP
interfaces.
ON
OFF
IP:
DHCP:
192.168.001.100