11
Step 8
Screw cap-nut tightly onto the cable.
Step 9
Seal the gaps between the AC cable and the gland inside the lower part
of the cabinet with duct seal.
3-6 Internal PE Cable Connection
Step 1
Prepare the cable and crimp cord end terminal.
E
L = E + (2~3)mm
1
2
1: Heat shrink tubing
2
:
Cord end terminal
Step 2
Loosen the swivel nut of the gland terminal (Marked as
“PE cable”) and
select an appropriate seal according to cable outer diameter. Lead the
cable through the swivel nut and seal successively.
Step 3
Connect the PE cable to the corresponding terminal. (The cabinet
includes two PE terminals inside. Wire either or both of them in an
appropriate manner according to local regulations.)
M8
7~9 N.m
PE(right)
PE(left)