User Manual
21
Do not break the copper wire during stripping.
Select proper terminal to the corresponding cable. For example, LT160012, 16
stands for 16 mm
2,
the cross-sectional area of the crimping cable; 12 stands for
12mm, the length of the crimping tube, see the following figure.
12mm
16mm
2
Cross-section
Terminal type
Stripped length (mm)
Force (N)
2.5mm
2
LT025008
10±0.5
190
4mm
2
LT040010
12±0.5
275
6mm
2
LT060012
15±0.5
360
10mm
2
LT100012
15±0.5
414
16mm
2
LT160012
16±0.5
445
Step 4
Crimp the cable. Insert the stripped cable into the terminal. Crimp the
cable using special tool (mouth of the crimping plier should match the
cable cross section), see the following figure.
Step 5
As shown in the following figure, connect the terminal to the
corresponding terminal of the PVS.
Step 6
Follow the same procedure to connect rest cables. Comb all the input
cables together with cable ties and firm them onto the cable support bar.
Appropriate cable bending space shall be ensured.