23
-
10. Enquiry of running situation
(
1).No matter under the stage of ON or OFF, you all can inquiry the running
parameter.
(2).When under the stage of setting, it can not enter enquiry.
(3).Under the stage of non-inquiry and non-setting, press “CHECK” for 3
seconds and enter the stage of inquiry, then the controller will read dada from main
board and display the setting data. If the connection between controller and main
board is cut, then “--” will be display and the setting stops.
(4).After the controller reads the setting data from main board, the screen displays
the code of parameter, press “
△
” or “
▽
” to select the code, press ENTER” to
display the value of the parameter, press “ENTER” again to come back the menu of
code selection, then you can press “
△
” or “
▽
” to select other parameter for inquiry,
after finishing all parameter’s inquiry, press ON/OFF, or press“CHECK” , or no key
pressing for long time, to quit the enquiry.
“
Code
Content of Parameter
Range
Remark
C1
Inquiry of fault code
00~FF
Display Max.256 faults
C2
Inquiry of function jump
00~FF
A0
Temperature of air con. return
-40~80
℃
A1
Temperature of air con. outlet
-40~80
℃
A2
Temperature of ground water/brine
inlet
-40~80
℃
A3
Temperature of ground water/brine
outlet
-40~80
℃
A4
Temperature of DHW cylinder
-40~80
℃
Code of Inquiry
Note:
The controller displays “--” if there is communication fault when inquiry. The function
of button operation is permitted at this time, not until the communication fault resumes.
INSTALLATION & INSTRUCTION
MANUAL