Ⅱ.
Installation
1
.
Transport
and
positioning
1
.
1
Transport
1
.
2
Positioning
The
room
where
the
heat
pump
is
to
be
installed
must
meet
the
following
conditions
:
No
risk
from
frost
.
Load
-
bearing
floor
.
Horizontal, level and solid floor as much as possible.
To protect the equipment against damage, it must be transported vertically inside
its dedicated packaging. Storage and transport at temperature below -20
℃
and
in excess of +50
℃
are not permissible.
The
heat
pump
is
designed for installation indoor, dry position.
(1). Remove the heat pump from its pallet and position it where required.
(2). Checking installation conditions:
For a quiet heat pump operation on floating screeds, isolate the screed and the
anti-vibration insulation from the surrounding of the installation location of the
heat pump.
The room must not be subject to a risk of explosions arising from dust, gases or
vapors.
The floor area of the installation room must be at least 3 square meters, and the
room must provide a volume of 6m3(minimum).
When installing the heat pump in a
boiler room together with other
heating equipment, ensure that the
operation of other heating
equipment will not be impaired.
The use of surface water or saline
water is not permitted.
Operation of a water-water heat
pump is not permitted with water
whose condition exceeds any of the
above limits(Up or down).
INSTALLATION & INSTRUCTION
MANUAL
-
11
-