background image

SUNDEZ 

 

Ground source Heat Pump

Heating/Cooling Series

(Heating only Series)

Installation&Instruction

 

Manual

 

(

Brine

/

water

 

Содержание SDWW-100

Страница 1: ...SUNDEZ Ground source Heat Pump Heating Cooling Series Heating only Series Installation Instruction Manual Brine water...

Страница 2: ...tion system notice 12 3 Installation of the heat source system 12 4 Installation of the heat consumer system 13 5 Electrical connection 14 6 Commissioning 15 7 Maintenance and cleaning 16 8 Water qual...

Страница 3: ...kable cabinets are designed to minimize installation space Compressor Standard high efficiency scroll compressor design for all units Compressor isolating springs are specially selected for each compr...

Страница 4: ...r Nomenclature SD WW 160 S 100 10 6KW 160 16 6KW 260 26 6KW Manufacturer Power Supply S 380V 3ph 50Hz Omit 220V 1ph 50Hz Type Heating capacity WW ground source water to water SD SUNDEZ INSTALLATION IN...

Страница 5: ...roll Scroll Scroll Scroll Scroll Compressor Quantity pc 1 1 1 1 2 2 Refrigerant R410A R410A R410A R410A R410A R410A Air condition Water Source Pipe Connection 1 1 4 F 1 1 4 F 1 1 2 F 1 1 2 F 2 F 2 F R...

Страница 6: ...front View D W H INSTALLATION INSTRUCTION MANUAL Model Dimension D W H mm SDWW 100 WR 703 611 1340 SDWW 160 SWR 703 611 1340 SDWW 260 SWR 703 611 1340 SDWW 320 SWR 703 611 1340 D W Model Dimension D W...

Страница 7: ...6 INSTALLATION INSTRUCTION MANUAL 70 46 Back View Model SDWW 100 SDWW 160 S SDWW 260 S SDWW 320 S Model SDWW 500 S SDWW 600 S Ground source Ground source Hot Water Hot Water Air Condition Air Conditio...

Страница 8: ...source outlet Ground source inlet For wire controller For power cable DN25 female DN25 female Specification of Water Connections Model SDWW 100 SDWW 160 S SDWW 260 S SDWW 320 S Ground source Ground s...

Страница 9: ...TB2 GROUND SOURCE PUMP AIR CONDITION PUMP RED BLU RED BLU BLK RED WHI BLU COMP 1 4 way valve ground source pump air condition pump BLU BLU BLU BLU BLU YLW COMMON TERMINAL RED BLU DIP double system si...

Страница 10: ...ion setting KT time relay KT L1 L2 L3 N 21 Green Brown Blue Red Brown Yellow white Yellow Brown Green Yellow Blue Red V U W Model Sign A mm2 Model table Wire diameter see the model table A Wire contro...

Страница 11: ...H Wenabl ed El ect r i c heat er G r ade1 enabl ed 5 4 3 2 cool i ng onl y 1 O F F O N D I P sw i t ch Funct i on Set t i ng KT time relay KT L1 L2 L3 N r ed br ow n bl ue r ed r ed bl ack yel l ow bl...

Страница 12: ...nstallation conditions For a quiet heat pump operation on floating screeds isolate the screed and the anti vibration insulation from the surrounding of the installation location of the heat pump The r...

Страница 13: ...he piping system to improve water system operating efficiency 2 6 Water flow switch must be set up in the water pipes and be wired to the heat pump controller system 2 7 The water pipe construction an...

Страница 14: ...lters and settlement basins if there is higher level of solid particles transported in the well water The evaporator can be flushed after removing the connections fittings 3 6 Connection Connect the h...

Страница 15: ...n diffusion Steel components such as radiators and pipes can corrode if plastic under floor heating system pipes which are permeable to oxygen are used The product of corrosion i e rusty sludge can se...

Страница 16: ...pe system Check if the rotation direction of water pump is right if the water flow switch work right and exhaust all air from pipe 6 6 Running commissioning change the jump 5 of FUNCTION SETTING into...

Страница 17: ...es corrosion would lead to system high pressure protection Corrosion may be caused by several reasons A Poor water quality can canker metal the standard of water quality shown in the table below B Eve...

Страница 18: ...ion multiple recycling water quality flow rate structure and materials of heat exchanger process fluid leakage and water temperature every factory is different Therefore the circulating cooling water...

Страница 19: ...on water PH 6 5 hardness of 50mg L have a corrosive effect on copper carbon dioxide 50mg L high solubility and hardness of groundwater will canker copper Therefore recommends that customers should pay...

Страница 20: ...e current temperature of cooling water 3 Memory for power cut off All parameter would be automatically saved without affect by power cut off The heat pump can be set as off or as reset by to previous...

Страница 21: ...period because of the accuracy Users can reset it to meet the local time so that it would not affect the timer function 3 Do not leave the wire controller without power for more than 18 months to avo...

Страница 22: ...the controller reads the setting data from main board the screen will display the code of parameter press or and select the code of d1 to H9 press ENTER to set the value of the parameter at this time...

Страница 23: ...4 Timer on off selection everyday 55 disabled AA enabled 55 disabled Timer on off P5 Monday Timer on HH MM 00 00 23 59 00 00 P6 Monday Timer off HH MM 00 00 23 59 00 00 P7 Tuesday Timer on HH MM 00 00...

Страница 24: ...value of the parameter press ENTER again to come back the menu of code selection then you can press or to select other parameter for inquiry after finishing all parameter s inquiry press ON OFF or pre...

Страница 25: ...defrost Refrigerant is too less Fill refrigerant Valve closed in system Check all valves dry filter jams Replace Expansion valve jams by ice Remove moisture and replace dry filter Expansion valve int...

Страница 26: ...essure protection 2 U ninstall main control board compressor system 2 Auto manual resume 0A High pressure protection 1 U ninstall main control board compressor system 1 Auto manual resume 0B Low press...

Страница 27: ...al use 5 Power should be shut down when the heat pump is without occupation for long time Power should be turn on to the heat pump again 12 24 hours before re use 6 Regularly check the water pipe heat...

Страница 28: ...2 saves up to 10 of heating cost per year If groundwater is available at reasonable depth and temperature you can achieve the highest COP A constant temperature from 8 to 12 guarantees an optional he...

Страница 29: ...vel approx 40W m2 approx 32W m2 Specific abstraction capacity Remark Specific abstraction capacities according to VDI4640 with an installation clearance of 0 8m Foundations Heating hours per year for...

Страница 30: ...period This figure has to be remembered when determining the size of a ground coupled system Utilities often offer a reduced price for electricity for a heat pump Thus they reserve the right to inter...

Страница 31: ...e chosen 1 6 Hot water with the heat pump 2 Installation system drawing 2 1 Heating Hot water Ground to water If one does not select an individual Heat Recovery Ventilation Hot Water Heat Pump for the...

Страница 32: ...31 2 2 Heating Hot water water to water 2 3 Example of integration of water to water heat pump with wells SUNDEZ INSTALLATION INSTRUCTION MANUAL...

Страница 33: ...32 2 3 Example of integration of water to water heat pump with wells INSTALLATION INSTRUCTION MANUAL...

Страница 34: ...al use 5 Power should be shut down when the heat pump is without occupation for long time Power should be turn on to the heat pump again 12 24 hours before re use 6 Regularly check the water pipe heat...

Отзывы: