Preparing the Site for Installation
3
Related Information
■
“Operating Environment Requirements” on page 6
■
“Airflow Considerations” on page 7
■
Sun Server X3-2L Installation Guide,
“Installation Prerequisites” on page 24
Minimum Clearance for Service Access
Related Information
■
“Physical Specifications” on page 2
■
Sun Server X3-2L Installation Guide,
“Installing the Server Into a Rack” on page 23
Power Source Requirements
The server uses AC power. The values in the following table are the power supply
specifications.
Relative humidity
10% to 90% noncondensing, short term
25˚F to 113˚F (
–
5˚C to 55˚C)
Up to 93% noncondensing
100.4˚F (37.7˚C) maximum wet
bulb
Altitude
Up to 9,840 feet (3,000 meters) maximum ambient
temperature is derated by 1˚ C per 300 meters
above 900 meters.
Note -
In China markets, regulations may limit
installations to a maximum altitude of 6,562 feet
(2,000 meters).
Maximum 39,370 feet (12,000
meters)
Acoustic Noise
• Maximum condition: 7.61 Bels A weighted
• Idle condition: 5.65 Bels A weighted
Not applicable
Description
Specification
Clearance, front of server
48.5 inches (123.2 cm)
Clearance, rear of server
36 inches (91 cm)
Specification
Operating
Nonoperating