2
Sun Server X3-2L Site Planning Guide • December 2012
■
“Minimum Clearance for Service Access” on page 3
■
“Power Source Requirements” on page 3
■
“Agency Compliance Specifications” on page 4
Physical Specifications
Related Information
■
“Minimum Clearance for Service Access” on page 3
■
Sun Server X3-2L Installation Guide,
“Rack Requirements” on page 24
Environmental Specifications
Dimension
Server Dimensions
Measurements
Width
Server chassis
17.5 in. (445 mm)
Depth
Maximum overall
29 in. (737 mm)
Height
2 rack unit (2U) nominal
3.45 in. (87.6 mm)
Weight
Server chassis
70 lbs (31.75 kg)
Specification
Operating
Nonoperating
Ambient temperature
(Does not apply to
removable media)
41˚F to 95˚F (5˚C to 35˚C) up to 2,953 feet (900
meters)
Optimal: 69.8˚F to 73.4˚F (21˚C to 23˚C)
Note -
Maximum ambient operating temperature is
derated by 1 degree C for every 300 meters
elevation beyond 900 meters, up to a maximum
altitude of 3,000 meters elevation.
–
40˚F to 158˚F (
–
40˚C to 70˚C)