Chapter 2
Hardware Installation and Service
2-17
2.3
Service Procedures
2.3.1
Hot-Swapping the Netra CP3250 Blade Server
You can remove the Sun Netra CP3250 blade server without powering off the entire
chassis by performing these steps.
1. Power off the blade server.
See
Section 2.3.2, “Powering Off the Netra CP3250 Blade Server” on page 2-17
.
2. Remove the blade server.
See
Section 2.3.3, “Removing the Netra CP3250 Blade Server” on page 2-18
.
2.3.2
Powering Off the Netra CP3250 Blade Server
1. Shut down the operating system.
Log in and shut down any OS operating on the blade server or its companion
ARTM.
2. Deactivate the blade server.
Log in to the shelf manager and deactivate the blade server in the target slot.
For example, to shut down the blade server in slot 3, log in to the shelf manager
and type:
Wait for the blue Hot-Swap LED to light steadily before removing the blade
server.
#
clia deactivate board 3
Содержание Sun Netra CP3250
Страница 8: ...viii Sun Netra CP3250 Blade Server User s Guide April 2009...
Страница 12: ...xii Sun Netra CP3250 Blade Server User s Guide April 2009...
Страница 18: ...xviii Sun Netra CP3250 Blade Server User s Guide April 2009...
Страница 34: ...1 16 Sun Netra CP3250 Blade Server User s Guide April 2009...
Страница 69: ...Chapter 2 Hardware Installation and Service 2 35 FIGURE 2 16 Netra CP3250 Blade Server Front Panel Reset button...
Страница 70: ...2 36 Sun Netra CP3250 Blade Server User s Guide April 2009...
Страница 72: ...3 2 Sun Netra CP3250 Blade Server User s Guide April 2009 3 1 Block Diagram...
Страница 80: ...3 10 Sun Netra CP3250 Blade Server User s Guide April 2009...
Страница 94: ...5 10 Sun Netra CP3250 Blade Server User s Guide April 2009...
Страница 96: ...A 2 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 1 BIOS Main Menu...
Страница 97: ...Appendix A BIOS Screens A 3 FIGURE A 2 Advanced Configuration Menu...
Страница 98: ...A 4 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 3 CPU Configuration Menu...
Страница 99: ...Appendix A BIOS Screens A 5 FIGURE A 4 IDE Configuration Menu...
Страница 100: ...A 6 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 5 USB Configuration Menu...
Страница 101: ...Appendix A BIOS Screens A 7 FIGURE A 6 Event Log Control Menu...
Страница 102: ...A 8 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 7 IPMI 2 0 Configuration Menu...
Страница 103: ...Appendix A BIOS Screens A 9 FIGURE A 8 Remote Access Configuration Menu...
Страница 104: ...A 10 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 9 PCI Option ROM Configuration Menu...
Страница 105: ...Appendix A BIOS Screens A 11 FIGURE A 10 Trusted Computing Menu...
Страница 106: ...A 12 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 11 Boot Settings Menu...
Страница 107: ...Appendix A BIOS Screens A 13 FIGURE A 12 Boot Device Priority Configuration Menu...
Страница 108: ...A 14 Sun Netra CP3250 Blade Server User s Guide April 2009 FIGURE A 13 Security Settings Menu...
Страница 109: ...Appendix A BIOS Screens A 15 FIGURE A 14 Exit Menu...
Страница 110: ...A 16 Sun Netra CP3250 Blade Server User s Guide April 2009...
Страница 125: ...Appendix B Physical Characteristics B 15...
Страница 126: ...B 16 Sun Netra CP3250 Blade Server User s Guide April 2009...