Chapter 2
Cabinet and Environmental Specifications
21
The particular label shown here identifies that each outlet is
rated at 10 amps. This means that any installed device using
that outlet can not draw more than 10 amps of current. This
label also identifies that the PDU is split up into two 16-amp
zones protected by a circuit breaker. If the PDU was to have
one 10 amp device and three 2 amp devices plugged in, the
other outlets in the zone must remain vacant. Another example
might be six 2.2 amp devices plugged into this zone. This
would result in 13.2 amps of total current draw, which is under
the 16 amps per zone requirement.
Total current draw should not exceed 80% of the rated (30
amps) current draw for the PDU. The label (on the right)
identifies that the entire PDU has already been derated to 24
amps to meet this requirement.
For more on calculating current, see
.
Additional Cabinet-related Information
There are multiple ways of getting information. It can be found on the:
O
software and document product CD
O
Customer Resource Center (CRC)
O
Documents on CD
O
engineering web pages located at: http://gandalf.stortek.com/ctp/
Cabinet information can be found on the CRC by going to Current Products >> Disk
and looking for the
Sun StorageTek 6000 Series
header. Click on
6540 Array
, and
look for the title: CBNT Cabinet, Cabling, and cabinet-related manuals.
Содержание StorageTek 6540
Страница 6: ...vi Sun StorageTek 6540 Rack Ready Site Preparation and Installation Support Guide July 2006 ...
Страница 18: ...6 Sun StorageTek 6540 Rack Ready Site Preparation and Installation Support Guide July 2006 ...
Страница 34: ...22 Sun StorageTek 6540 Rack Ready Site Preparation and Installation Support Guide July 2006 ...
Страница 42: ...30 Sun StorageTek 6540 Rack Ready Site Preparation and Installation Support Guide July 2006 ...
Страница 46: ...34 Sun StorageTek 6540 Rack Ready Site Preparation and Installation Support Guide July 2006 ...