Netra X1 Server Product Notes • February 2001
Changes to the User’s Guide
There are some corrections to the Operating Power Statistics table on page 8 of the
Netra X1 Server User’s Guide. The changes are to the BTU rating, the maximum
operating current and the maximum volt-ampere rating. The correct figures are
given in the table below.
Operating Power Statistics
*
The in-rush current decays to the normal operating current in less than 200 msecs.
** This BTU assumes a system fully loaded with hardware option modules (see “Calculating
Heat Dissipation” on page 9 of the Netra X1 Server User’s Guide.
TABLE 0-1
Operating Power Statistics
Maximum operating current
1.3A @ 100 VAC
Typical operating current
See “Calculating Power Consumption” on
page 9 of the Netra X1 Server User’s Guide.
Maximum in-rush
current (cold start)
40A peak at 115V
25˚C
Maximum in-rush
current (warm start, or upon a restart 20 to
200 msecs after power has been removed
*
)
100A peak at 115V
25˚C
Operating input voltage range
90 to 264 Vrms
Voltage frequency range
47 to 63 Hz
Power factor
0.9 to 0.995
Maximum
volt-ampere rating
130 VA
BTU rating
153.54 BTU
**