1-12
Cable Management Guide
• July
2005
1.6.2
Systems With Two Doors (One in Front)
1.6.2.1
For the Front of the System
1. Release the I/O cable bundles from the green maintenance strap and resecure
them to their former black cable hanger straps on the air plenum.
2. Remove the two screws that secure the green cable straps (No. 6) to the cabinet
door on the left and store the green straps for future use.
3. Secure the two screws in their original locations.
4. Remove the two screws that secure the green cable straps (No. 6) to the cable
management brackets and store the straps and screws for future use.
5. Remove the cable management brackets and store them for future use (
).
The brackets have captive fasteners that can be loosened by hand.
6. Close the cabinet doors.
1.6.2.2
For the Rear of the System
The buckle end of the green buckle strap (No. 2) that is used at the top crossbar of
the door measures approximately 17.0 in. (43.2 cm). The other end that used to hold
the cables measures approximately 12.0 in. (30.5
cm).
1. Release the I/O cable bundles from the green maintenance strap and resecure
them to their former black cable hanger straps on the air plenum.
2. Release the buckle and remove the green strap from the top crossbar on the
hinged side of the cabinet door (
3. Remove the two screws that secure the green cable straps (No. 6) to the cable
management brackets and store the straps and screws for future use.
4. Remove the cable management brackets and store them for future use (
).
The brackets have captive fasteners that can be loosened by hand.
5. Close the cabinet doors.