Chapter 1
Safety, Tools, and Configuration Requirements
1-5
1.5
Configuration Requirements
Systems must be installed in the cabinet from the bottom up.
Storage devices must be installed directly above server systems in the cabinet, and
installed from the bottom up.
Sun StorEdge D240 media trays must be installed from the top of the cabinet down.
The Sun Fire cabinet does not support any side-to-side cooled devices such as the
Sun Enterprise™ 3500/4500/5500/6500 or Sun StorEdge A5X00 array. Only front-to-
back cooled products are supported.
Up to three Sun Fire 3800 systems are supported in the Sun Fire Cabinet.
For maximum compute density, the Sun Fire 3800 systems should be mounted in the
Sun Fire Cabinet. The Sun Fire 3800 system is also designed to fit in racks which
meet the requirements of EIA-310-D.
The Sun Fire 3800 system rack mounting kits are designed to be used in the Sun Fire
Cabinet, are not adjustable and may or may not work in other racks. When
considering third party rack mounting, the third party thermal guidelines and the
third party rack mounting guidelines should be reviewed.
The Sun Fire 280R, Sun Enterprise 420R, Sun Netra T1 AC200/DC200, and Sun Fire
V100/V120 servers must be mounted above the Sun Fire systems.
Front plastic filler panels must be installed to fill in any open spaces within the Sun
Fire cabinet. The 1RU plastic filler panel comes with the Sun Fire cabinet. If
mounting either the Sun Fire 280R, Sun Enterprise 420R, Sun Netra T1 AC200/
DC200, or Sun Fire V100/V120 server in a cabinet with two Sun Fire 3800 systems,
you will need a 1/2 RU metal filler panel.
Caution –
All empty spaces in the cabinet must be filled with front plastic filler
panels to prevent the recycling of heated exhausted cooling air from the rear of the
system.
Maximum amperes supported from each RTU (with two RTSs installed) is 24
amperes. Each RTU has eight switched, two unswitched, and two dedicated Sun Fire
6800 outlets. A second RTU must be installed when more than 24 amperes are
required or more than eight switched outlets are required.
Maximum weight capacity of a cabinet is 1200 pounds.
Содержание Fire 6800
Страница 4: ...4 Sun Fire 6800 System and Sun Fire Cabinet Rackmount Placement Matrix June 2003...
Страница 22: ...2 4 Sun Fire 6800 System and Sun Fire Cabinet Rackmount Placement Matrix June 2003...
Страница 32: ...4 6 Sun Fire 6800 System and Sun Fire Cabinet Rackmount Placement Matrix June 2003...
Страница 48: ...6 4 Sun Fire 6800 System and Sun Fire Cabinet Rackmount Placement Matrix June 2003...
Страница 66: ...A 18 Sun Fire 6800 System and Sun Fire Cabinet Rackmount Placement Matrix June 2003...