24

Section 6

VARIABLE SPEED DRIVE

6.3 INSTALLATION

This variable speed AC drive has been properly
mounted, adjusted, and tested prior to shipment of
the compressor package.  Inspect the unit to ensure
it was not damaged during shipment.  The package
provides a terminal block for connection of three-
phase power and ground.  Refer to the package
wiring diagram for specific connection information.
All internal wiring to the drive and motors has been
provided by the factory, in accordance with the
drive's requirements.  Do not alter factory wiring.  To
ensure proper wiring to the package, use the fol-
lowing guidelines:

• Use heat-resistant copper cables only,

+75°C or higher.

• The minimum input line cable and line fuses

must be sized in accordance with the rated
input current of the unit. See Table 6-1.

• Consistent with UL listing requirements, for

maximum protection of the variable speed
drive, use UL recognized fuses, type RK5.

• Suitable for circuits delivering fault currents

up to 100,000A.

6.4 SUPERVISOR DISPLAY AND MENUS

Refer to Section 2 for a general description of the
Supervisor and its displays and adjustments.  This

section addresses special functions applicable to
VSD packages.

6.4.1. VSD STATUS

This group of displays shows the performance of
the variable speed compressor package.  The fol-
lowing may be used for evaluation of system per-
formance.  The first four lines indicate real-time
conditions:

Capacity - 

Delivery in CFM.

Capacity % - 

Percent of full package capacity.

Power - 

Total package power in KW.

Power % -

Percent of power at full capacity. 

The next eight lines indicate recent longer-term
performance.  See Section 6.4.2 for reset proce-
dure.

Capacity -

Average delivery in CFM.

Capacity % -

Average percent of full package

capacity.

Power - 

Average total package power in KW.

Power % -

Average percent of power at full capac-

ity.

KCF -

Running total of air delivered in thousands of

cubic feet.

Table 6-1: Cable and Fuse Sizes - 460V Ratings

_ UL recognized type RK.
_ Based on a maximum environment of 104°F (40°C).

hp

Size (A)

Fuse (A)

Wire Size

Wire Size

Power

Ground

40

61

80

2

8

50

72

100

2

6

60

87

110

1

6

75

105

125

1/0

2

100

140

175

3/0

2

125

170

200

4/0

2

150

205

250

350MCM

1/0

200

261

350

2 x 250MCM

1/0

NOTE ON ELECTRICAL PREPARATION:

Interior electrical wiring is performed at the factory. Required customer wiring is minimal, but should be
done by a qualified electrician in compliance with OSHA, National Electrical Code, and/or any other appli-
cable State, Federal and local electrical codes concerning isolation switches, fused disconnects, etc.
Sullair provides a wiring diagram for use by the installer.

Customer must provide electrical supply power
disconnect within sight of machine.

Содержание SUPERVISOR CONTROLLER Series

Страница 1: ...Part Number 02250146 049 Sullair Corporation SUPERVISOR CONTROLLER INSTRUCTION MANUAL ALL MODELS OPERATOR S MANUAL KEEP FOR FUTURE REFERENCE...

Страница 2: ...r s corporate headquarters in Michigan City Indiana Instruction includes discussion of the function and installation of Sullair service parts troubleshooting of the most common problems and actual equ...

Страница 3: ...VE MAINTENANCE INFORMATION AND TIMERS 7 2 7 FAULT LOG LOG OF PREVIOUS FAULTS 7 2 8 SENSOR LOG 7 2 9 SEQUENCING SEQUENCING COMMUNICATION PARAMETERS 8 2 10 SYSTEM DISPLAY DISPLAY OF MODES OF MACHINES IN...

Страница 4: ...T 19 Table 4 3 Machine Power Outage Behavior 19 Table 4 4 Remote Start Stop Input Section 5 WIRING SCHEMATIC DIAGRAMS 21 5 1 WIRING DIAGRAM SUPERVISOR COMMUNICATION MODULE 22 5 2 WIRING DIAGRAM SUPERV...

Страница 5: ...mover so others who may not know of the unsafe condition cannot attempt to operate it until the condition is corrected Use and operate the air compressor only in full compliance with all pertinent OSH...

Страница 6: ...Section 1 SAFETY 2 Figure 1 1A Decals...

Страница 7: ...ber quantity 1 decal warning auto start 250017 903 1 2 decal danger breath air I 250027 935 1 3 sign warning food grade lube 250003 144 1 4 decal auto start 041065 1 I OSHA and FDA guidelines are supe...

Страница 8: ...4 Section 2 SUPERVISOR DESCRIPTION Figure 2 1 Supervisor Control Panel...

Страница 9: ...m Machine running loaded and modulating in a sequenced system Line 2 Fault or Warning blank means no fault or warning is present If there are multiple alarms they will be shown for 2 seconds each If a...

Страница 10: ...by machine model The Control Parameters are Unload pressure The pressure where the machine is unloaded For example if this parameter is set to 110 psi 7 6 bar the machine will unload when the line pr...

Страница 11: ...log shows the last 16 faults that occurred The top line of the display shows the run hours where the fault occurred and the second line shows the fault The faults can be scrolled through using the up...

Страница 12: ...y S Starting U Unloaded L Loaded T Trim machine F Full load Sequencing Hours Capacity Not used at this time Local System Pressure Pressure read by machines pressure transducer The top line is a legend...

Страница 13: ...rol Master Control for special external sequence con trol Stop Timer Time to run machine before stopping Protect Protect control parameters Load Hours Hours machine was running and loaded Run Hours Ho...

Страница 14: ...ost Savings Lifetime Usages Hours Capacity Capacity Power Power KCF KWH Cost Savings Drive Status P2 Motor RPM Frequency Drive Temp Motor Prot Status VSD Status Control Parameters Maintenance Sensor L...

Страница 15: ...be used to make the initial start up of the compressor 1 Be sure that all preparations and checks described in the Installation Section have been made 2 Read the preceding pages of this manual thor o...

Страница 16: ...12 NOTES...

Страница 17: ...h Auxiliary Motor Tripped on Cooling Fan Oil Pump or Other Motor E Stop Button Active Auxiliary E Stop String Open Cooling Water Pressure Below 10 psi 0 7bar Maintenance Due Main Motor Overload 4 1 TR...

Страница 18: ...mation Needs to be Reviewed for Correct Values Sump Pressure High Poppet Sullicon Spiral Blowdown or Pneumatic Valve Failed Check motor starter contacts for proper operation Check line voltage if low...

Страница 19: ...r up or Setup Incorrect Factory or VSD Setup Fault Detected by Drive Solenoid valves check operation and wiring Pressure regulator check adjust ment and operation Check minimum pressure check valve no...

Страница 20: ...yed for temp spikes T_1 High Warn 245 0 0 Constantly Immediate Warning T_1 High Fault 255 0 0 Constantly Immediate Fault T_1 High Fault 500 0 0 Constantly Sensor failure fault T_2 Low Fault 40 0 0 Con...

Страница 21: ...y Sensor failure fault T_2 High Warn 245 5 30 Constantly Delayed for temp spikes T_2 High Warn 255 0 0 Constantly Immediate Warning T_2 High Fault 255 5 30 Constantly Delayed for temp spikes T_2 High...

Страница 22: ...7 7 P4 Cal Always 0 0 1 Fault on Warn Force shutdown on warning User X200 110 30 220 Unload 250psi transducer unload pressure User X250 110 30 185 Unload 200psi transducer unload pressure User X500 1...

Страница 23: ...loss or voltage dips for those installations that are susceptible to this kind of power interruption The controller alone is not as sensitive to these interruptions as is the switchgear and must be t...

Страница 24: ...20 NOTES...

Страница 25: ...21 Section 5 WIRING SCHEMATIC DIAGRAMS 5 1 WIRING DIAGRAM SUPERVISOR COMMUNICATION MODULE 02250131 248R01...

Страница 26: ...22 Section 5 WIRING SCHEMATIC DIAGRAMS 5 2 WIRING DIAGRAM SUPERVISOR CONTROL 02250132 198R00...

Страница 27: ...Failure to observe this precau tion could result in death or severe injury Line terminals L1 L2 L3 motor terminals U V W and the DClink brake resistor terminals are live when the drive is connected t...

Страница 28: ...ormance of the variable speed compressor package The fol lowing may be used for evaluation of system per formance The first four lines indicate real time conditions Capacity Delivery in CFM Capacity P...

Страница 29: ...spiral valve control systems Reset Load Est This resets the Recent Usage values to zero in the VSD Status calculations This functions similarly to a trip odometer in a car 6 4 3 CALIBRATION Two additi...

Страница 30: ...stantly monitors drive performance through the serial channel The following messages are specifically displayed by the Supervisor in the event of problems FAULT VSD Param Lim Fault VSD Com Error VSD E...

Страница 31: ...et the fault and restart Should the fault re occur contact Sullair service Determine the reason for the Emergency stop and remedy it Cannot be reset from the keypad Switch off power If this fault appe...

Страница 32: ...different power rating of drive option board added drive of different power rating added Current at the analog input is 4 mA Digital input set as an external fault input has been triggered The data co...

Страница 33: ...29 NOTES...

Страница 34: ...PORATION 3700 East Michigan Boulevard Michigan City Indiana 46360 U S A www sullair com Telephone 1 800 SULLAIR U S A Only or 1 219 879 5451 Fax 219 874 1273 PARTS DEPARTMENT Telephone 1 888 SULLAIR U...

Отзывы: