SUPERVISOR DESCRIPTION
connected to the network (RS-485 channel). For
example in a three machine system, this parameter
should be set to 3. Up to sixteen machines may be
networked if all have Supervisor Controllers and
limited to eight if some have Supervisor II’s.
Low Press -
This is the lowest pressure allowed
before immediately starting a machine.
Recovery Time -
This parameter keeps multiple
machines from loading, unloading and starting at
the same time. For example if a low pressure con-
dition causes a machine to start, the next machine
will not start unless the Recovery Time has elapsed,
and the pressure has not recovered (i.e., has risen
over ‘Low Press’).
Rotate -
This parameter is used only in very special
cases.
The only time this parameter should be used is in a
situation where, once a machine is started, it never
stops (ie. the unload timer never expires). This can
happen when the load matches the output of the
machine, all the time. In this case the machine will
never unload and shut off. The rotate forces the
machine to stop after it’s Seq Hrs. are greater that
the other machines. For example in a two machine
system, with Rotate set at 100 hrs. The machine
that is running will shut off when the Seq Hrs. are
100 more that the machine that is stopped.
Minute, Hour, Day, Month, Year
- If the
Communications Module is present in the system,
the time and date can be set using these parame-
ters.
2.10 SYSTEM DISPLAY - DISPLAY OF MODES OF
MACHINES IN A SEQUENCING SYSTEM
Note that this display is only applicable when there
are two or more machines connected to the com-
munications network (RS-485) and the Sequence
By parameters on each machine are set to ‘Hours’
or ‘Number’.
The columns are described below
Communication Number
Status -
E -
Emergency Stop
M -
Manual stop
R -
Remote stop
B -
Standby
S -
Starting
U -
Unloaded
L -
Loaded
T -
Trim machine
F -
Full load
Sequencing Hours
Capacity
- Not used at this time.
Local System Pressure
- Pressure read by
machines pressure transducer.
The top line is a legend that describes each column.
The right hand number on the top line is the system
pressure. The system pressure is the highest pres-
sure reading of all the machines. Note that the local
pressure readings can be used to determine what
machines may need to be calibrated. The system
pressure transducers on all machines should read
within 1(one) psi of one another. The calibration
function can be used to set the readings to be the
same.
2.11 CALIBRATION - CORRECTION FACTORS FOR
PRESSURES
The first line of this display is the password. If the
password is 0 then the following parameters are not
protected and can be changed. If the password is
non-zero, then enter the displayed number plus 4 to
enable changing the parameters. For example if the
number displayed is 10 then changing the pass-
word to 14 will enable editing.
The four pressures P1, P2, P3 & P4 as well as the
differential pressure dP1 can be calibrated. The
number on the right hand side of the line is added
to the transducer reading to give the calibrated
reading. The calibrated reading is shown in the mid-
dle of the line.
Cap and KW calibration (VSD packages only) may
be used to adjust values shown on VSD Status dis-
plays. These are factory set to nominal values
(100%), but may be adjusted as desired.
There are also three other parameters in the cali-
bration function:
Protect -
When set to yes, protects the control
parameters from change.
Fault on Warn -
Force fault on warning.
Force Unload -
When set to yes, forces the
machine to unload.
2.12 TEST-
Used by Sullair personnel for troubleshoot-
ing of serial communications.
2.13 FACTORY SETUP-
Model settings.
The factory setup display is used by Sullair person-
nel to initially set up the machine. The following val-
Leave this parameter disabled unless instructed
by Sullair Service Personnel.
Содержание SUPERVISOR CONTROLLER Series
Страница 6: ...Section 1 SAFETY 2 Figure 1 1A Decals...
Страница 8: ...4 Section 2 SUPERVISOR DESCRIPTION Figure 2 1 Supervisor Control Panel...
Страница 16: ...12 NOTES...
Страница 24: ...20 NOTES...
Страница 25: ...21 Section 5 WIRING SCHEMATIC DIAGRAMS 5 1 WIRING DIAGRAM SUPERVISOR COMMUNICATION MODULE 02250131 248R01...
Страница 26: ...22 Section 5 WIRING SCHEMATIC DIAGRAMS 5 2 WIRING DIAGRAM SUPERVISOR CONTROL 02250132 198R00...
Страница 33: ...29 NOTES...